Clearance
Clearances should be adhered to as follows:
•
Rear and above unit: 2 ft (61 cm).
•
Front of unit: 3 ft (91 cm).
•
Tube Removal:
- 14 ft. (4.3 m) (either end)
- 16 ft (4.9 m) on shell codes Q-Q, N-N, R-R, X-T and X-X.
- 18 ft (5.5 m) on shell code S-S, S-V, Z-Z.
- 22 ft (6.7 m) on shell code W-W.
Model YK (Style G) Centrifugal Liquid Chiller
18
Содержание YORK YK Series
Страница 2: ...2 Model YK Style G Centrifugal Liquid Chiller...
Страница 14: ...Figure 3 Long term storage tube side Model YK Style G Centrifugal Liquid Chiller 14...
Страница 19: ...Figure 6 Neoprene isolators in mm 19 Model YK Style G Centrifugal Liquid Chiller...
Страница 20: ...Figure 7 Spring isolators in mm Model YK Style G Centrifugal Liquid Chiller 20...
Страница 21: ...Figure 8 Spring isolators continued in mm 21 Model YK Style G Centrifugal Liquid Chiller...