54
JOHNSON CONTROLS
FORM 201.21-NM4 (616)
54
JOHNSON CONTROLS
TECHNICAL DATA
LEGEND
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RATED LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
VOLTAGE CODE
-50 = 380/415-3-50
1. As standard, all units have single point power connection. Contact factory for information regarding dual point
power units.
2. Maximum Inverse Time Circuit Breaker - 250% of the rated input current of the drive per NEC 430.52 (C1).
3. Maximum Dual Element (Time Delay) Fuse - 225% of the rated input current of the drive per NEC 430.52 (C1).
4. MCA - Minimum Circuit Ampacity - 125% of the largest compressor RLA plus 100% of the remaining compressor
RLA’s plus the sum of all condenser fan FLA’s per NEC 440.33
5. Recommended time delay or dual element fuse size - 150%of the largest compressor RLA plus 100% of the
remaining compressor RLA’s plus the sum of all condenser fan FLA’s.
6. RLA - Rated Load Amps - rated in accordance with UL standard 1995 at 400VAC.
7. Local codes may take precedence.
8. Control KVA includes operational controls and evaporator heaters.
9. System inrush current is less than RLA due to the use of York Variable-speed Drive technology. Typical
Compressor Starting Current ( first four seconds of startup):
Rated Voltage
Typical Starting Current per Compressor
400/50/3
28A
10. Optional Compressor Service Disconnect switch is available on all units.
11. Voltage Utilization Range:
Rated Voltage
Utilization Range
380-415/50/3
360-440
12. Condenser fan FLA applies to both low sound and ultra quiet fans.
NOTES:
1. U.L. Label is provided on 50 Hz units for these electrical wiring configurations.
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with local
codes. Group Rated breaker must be HACR type for cUL machines.
ELECTRICAL NOTES
Содержание York YCAV1039-1909
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM4 616 43 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 55: ...55 JOHNSON CONTROLS FORM 201 21 NM4 616 55 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 67: ...67 JOHNSON CONTROLS FORM 201 21 NM4 616 67 JOHNSON CONTROLS 6 This page intentionally left blank ...
Страница 83: ...83 JOHNSON CONTROLS FORM 201 21 NM4 616 83 JOHNSON CONTROLS 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Страница 229: ...229 JOHNSON CONTROLS FORM 201 21 NM4 616 229 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM4 616 249 JOHNSON CONTROLS 8 This Page intentionally left blank ...
Страница 277: ...277 JOHNSON CONTROLS FORM 201 21 NM4 616 277 JOHNSON CONTROLS 8 This page intentionally left blank ...
Страница 308: ...308 JOHNSON CONTROLS FORM 201 21 NM4 616 308 JOHNSON CONTROLS MAINTENANCE NOTES ...
Страница 309: ...309 JOHNSON CONTROLS FORM 201 21 NM4 616 309 JOHNSON CONTROLS 9 NOTES ...