background image

JOHNSON CONTROLS

15

FORM 160.00-O10 

ISSUE DATE: 8/24/2020

2

SECTION 2 - SAFETY SHUTDOWNS

period (150 seconds for centrifugal chillers or 

shorter for those chillers that contain the optional 

“Quick Start” feature).

•  The message “VSD Shutdown - Requesting Fault 

Data”...will be displayed when the Control Center 

is requesting the fault data from the OSCD.

•  The OSCD Logic Board will send a shutdown 

code via the communications link to the Control 

Center. The Micro Board will interpret the shut-

down code and display a shutdown message on 

the display of the Control Center.

After the coastdown period has timed out, the chiller 

may be restarted if the shutdown is no longer active, 

and the CLEAR FAULT key is pressed

TABLE 2 - 

SAFETY SHUTDOWNS MESSAGE

MESSAGE

DESCRIPTION

VSD – DC BUS LOCKOUT – 

DO NOT CYCLE POWER

When the unit is stopped in a mode where no command exists to energize the DC bus, 

the DC bus voltage is monitored and checked against a threshold level of 100 VDC every 

five minutes. If the DC bus voltage is higher than the threshold value, this shutdown 

is generated. When the condition clears and the VSD input modules are tested and 

determined acceptable the chiller can be started. 

VSD – DC BUS PRE-

REGULATION LOCKOUT

If the unit fails to complete pre-regulation (due to VSD – DC BUS PRE-REGULATION 

fault), it shall have to repeat pre-charge in order to attempt another pre-regulation. The 

VSD shall wait 10 seconds before clearing the DC bus voltage pre-regulation fault and 

allowing another pre- charge to start. The unit’s fan(s) and water pump(s) shall remain 

energized during this wait time. The VSD shall allow up to three consecutive pre-

regulation-related faults (i.e. VSD-DC BUS PRE-REGULATION) to occur. After the third 

consecutive fault, this shutdown is generated.

VSD – GROUND FAULT

This message is generated when the sum of the 3 phases of instantaneous input current 

values are greater than the shutdown value for a period of 1 second for the given model 

of drive listed below.

DRIVE MODEL

GROUND CURRENT SHUTDOWN VALUE

1100/1300

200 Amps

VSD – HIGH PHASE A INPUT 

BASEPLATE TEMPERATURE

This shutdown occurred because the Input Baseplate Temperature exceeded the 

shutdown value for the given model of drive listed below. After the unit trips, the VSD 

fan(s) and water pump(s) shall remain energized for 2 minutes after the fault occurred. 

DRIVE MODEL

HIGH PHASE A INPUT BASEPLATE 

TEMPERATURE SHUTDOWN VALUE

1100

170°F (76.6°C)

1300

150°F (65.5°C)

VSD – HIGH PHASE B INPUT 

BASEPLATE TEMPERATURE

See “VSD – HIGH PHASE A INPUT BASEPLATE TEMPERATURE” message preceding.

General Information

The Shutdowns are organized in alphabetical order 

based on the OptiView™ Control Center messages.
Whenever a Safety Shutdown is generated by the 

OSCD, a series of events will occur.

•  If the chiller is not running at the time of the shut- 

down, the OSCD Logic Board will not turn on the 

gate drivers.

•  The K3 relay on the OSCD logic board will de-

energize to indicate to the Control Center that the 

OSCD has shutdown. The K3 relay will remain 

de-energized until the cause of the shutdown has 

been corrected.

•  If the chiller is running at the time of the shut- 

down, the Control Center will start a coastdown 

Содержание YORK HYP1100A

Страница 1: ...415 VAC 371 06172 XXX 1300 HP 60 HZ 460 VAC 371 06172 XXX MODELS HYP1100A HYP1300A LIQUID COOLED OPTISPEED COMPRESSOR SPEED DRIVE OPERATION MANUAL Supersedes 160 00 O10 217 Form 160 00 O10 820 Issue...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...g and operating service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chill...

Страница 4: ...173 Retrofit Package YK Filter Model HYP1100RKC30B 50A 371 06172 175 Retrofit Package YK Filter Model 1100 HP 400 VAC HYP1100RKC30B 42A 371 06172 185 Retrofit Package YK Filter Model HYP1100RKC30B 50...

Страница 5: ...Demand Distortion 16 VSD Input Current Overload 16 VSD Input DCCT Offset Lockout 16 VSD Inverter Program Fault 16 VSD Line Voltage Phase Rotation 16 VSD Logic Board Hardware 16 VSD Logic Board Plug 1...

Страница 6: ...B Input Gate Driver 21 VSD Phase C Input Gate Driver 21 VSD Phase A Motor Gate Driver 21 VSD Phase B Motor Gate Driver 21 VSD Phase C Motor Gate Driver 21 VSD Precharge Low DC Bus Voltage 1 21 VSD Pre...

Страница 7: ...power devices required for one phase of input and output In other words the rectifier and inverter are integrated into one power unit This design has 2 methods of detecting a ground fault The circuit...

Страница 8: ...COMPRESSOR DRIVE DETAILS The 1300 HP drive contains 3 power assemblies Each power assembly contains 2 capacitors with the rectifier of the left side of the power assembly and the inverter on the righ...

Страница 9: ...OSCD to provide input current limit ground fault detection and information for the harmonic current filtering The bus voltage is moni tored to verify that bus voltage is present The line volt age is...

Страница 10: ...SSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 1 HYP1100A HYP1300A HP COMPLETE DRIVE CABINET Cooling Coil Supply Contactor Fan Assembly A Phase Power Assembly B Phase Power Assembly BUS Stru...

Страница 11: ...RMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 2 LEFT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Voltage Transient Board Line Voltage Isolation Board Drive Logic Board Cooling Fans Cooling Coil...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O10 ISSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 3 RIGHT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Inlet Coolant Hose Step Down Transformers LD21854...

Страница 13: ...JOHNSON CONTROLS 13 SECTION 1 GENERAL INFORMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 4 DRIVE LOGIC BOARD LD16293 Figure 5 RECTIFIER SIDE OF THE POWER UNIT HYP1100A AND HYP1300A LD16292...

Страница 14: ...ogether through a ModBus communication link Data such as output currents baseplate temperatures and input voltage are communicated from the OSCD to the microboard for display through the ModBus commun...

Страница 15: ...pre charge to start The unit s fan s and water pump s shall remain energized during this wait time The VSD shall allow up to three consecutive pre regulation related faults i e VSD DC BUS PRE REGULAT...

Страница 16: ...he input current overload value must be greater than the shutdown value for 10 continuous seconds for this shutdown to occur DRIVE MODEL INPUT CURRENT OVERLOAD MAXIMUM SHUTDOWN VALUE 1100 1300 1305 Am...

Страница 17: ...unt of current is flowing to the motor If at the end of the 1 5 second time a minimum of 25 amps peak is not detected then this shutdown is generated VSD PHASE B MOTOR DCCT See VSD PHASE A MOTOR DCCT...

Страница 18: ...JOHNSON CONTROLS 18 FORM 160 00 O10 ISSUE DATE 8 24 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 19: ...ltage exceeds the value for the given model of drive then this shutdown will occur Typically this shutdown will occur when there is a sudden change in the input voltage due to storms utility power pro...

Страница 20: ...this fault There are several causes for an unsuccessful initialization as follows Serial data communications must be established Refer to VSD Serial Communications fault If communications between the...

Страница 21: ...message preceding VSD PHASE A INPUT GATE DRIVER The gate driver board for the input rectifier monitors the power supplies within the gate driver circuit and verifies that the input rectifier can be p...

Страница 22: ...IVE This shutdown is generated when the VSD logic board has not received a valid communications packet from the control center for 10 consecutive seconds VSD SHUTDOWN REQUESTING FAULT DATA The VSD has...

Страница 23: ...tice we have no objections as long as the OSCD is properly grounded Can I apply an OptiSpeed Compressor Drive to a generator Yes the OSCD can be applied to a generator No modi fications are required f...

Страница 24: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O10 820 Issue Date Augus...

Отзывы: