Function and Control
Domestic Air Conditioner
19
malfunction will be stored in the malfunction resume and will not be revealed.
5.1.12 High load protection control
The outdoor system will be stopped if the coil temperature is above 65
ć
for 2 minutes. The indoor fan
will be controlled by the thermostat. The outdoor system can be restarted when the coil temperature is
below 42
ć
and the system has been stopped for 3 minutes. The malfunction will be stored in the
malfunction resume and will not be revealed.
5.1.13 Abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system,
the abnormal operation malfunction will be reported. 10s after the report, the indoor system will be
closed.
Outdoor system mode
Indoor system mode
conflicts
cooling
heating
yes
cooling
cooling
no
cooling
airflow
no
heating
heating
no
heating
airflow
yes
heating
cooling
yes
5.1.14 Malfunction list resume.
Nothing is presented if there is no code list.
The malfunction display will automatically finish in 10 seconds.
The remote control only receives the sigals for stop. According to the signals, the malfunction resume
presentation finishes.
The resume restores after the power supply restores.
5.1.15 Abnormality confirmation approaches.
LQGRRUWHPSHUDWXUHVHQVRUDEQRUPDOLW\
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
LQGRRUKHDWLQWHUDFWLRQVHQVRUDEQRUPDOLW\
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
LQGRRUPDOIXQFWLRQ
Out door malfunction: When the indoor system receives the outdoor malfunction codes, it will store
the code into E2 for the malfunction list resume. The indoor system will continue to operate
YJHJZH024BARRAFX
-SM
Содержание YJHJXH024BARR-FX
Страница 44: ...1 6 2 1 The Instruction For AS24GS1ERA YJHJZH024BARRAFX SM...
Страница 82: ...79 Domestic air conditioner Installation WARNING CAUTION YJHJZH024BARRAFX SM...
Страница 83: ...80 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 86: ...Installation 83 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 87: ...Installation 84 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 88: ...Installation 85 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 91: ...88 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 92: ...e g 1U18FS1ERA 89 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 117: ...114 Domestic air conditioner Step Procedure Points 4 Remove the YDOYH EUDFNHW Removal of procedure YJHJZH024BARRAFX SM...
Страница 118: ...LULQJ LDJUDPV Domestic Air Conditioner 115 10 Wiring Diagrams 10 1 Indoor unit YJHJZH024BARRAFX SM...
Страница 123: ...The end YJHJZH024BARRAFX SM...