Function and Control
Domestic Air Conditioner
28
5.2.6.6 The frequency limitation of modification rate
In the field which is controlled by high frequency, if the modification rate is not high enough, the
control-driven on chip will enter into weak magnetic control, this will help to relieve the problem of
modification rate. If during the course of weak magnetic control, the modification rate is still not high
enough, enter into the control of decreasing frequency until the alarm of modification rate is relieved.
5.2.6.8 Temperature protection of the outdoor refrigerating coil
When the defrosting temperature and the sensor’s temperature are higher than 65
ć
, the frequency of
the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to the lowest
frequency. When the temperatures are lower than 65
and higher than 60
, keep the frequency of
ć
ć
the compressor. When the temperatures are lower than 60
, relieve the defrosting temperature
ć
protection.
5.2.6.9
˖
Malfunction display and malfunction handling
a)
ǃ
For the complete appliance’s malfunctions
˖
Annex 2
If there’s malfunction with the outdoor unit, the light of the outdoor unit will flash and its frequency is
1HZ, the number of times is according to the table, when a round of flashing is finished, the light
shoud be off for 5 seconds.
b)
ǃ
For the units’ malfunctins
˖
Annex 1
If there’s malfunction with the units, this will not affect the run of the complete appliance, but this can
be displayed by the malfunction light, the light flashing frequency is 0.5HZ, the number of times is
according to the malfunction table of the indoor units. When a round of flashing is finished, the light
shoud be off for 10 seconds. Then report according to the order : unit A→unit B→unit C→unit D, that
is, if there’s malfunction with several units, then just report the indoor unit with the highest priority level.
Among the unit malfunctions, the priority level of the communication malfunction is the highest, for
others, that appears first will have the priority.
Remarks: in 3 minutes when the compressor stops, the units’ malfunctions are not displayed; the
complete appliance’s malfunctions are prior to the units’ malfunctions.
Annex 1
˖
Malfunction codes of the whole unit
Remarks: under the mode of refrigeration, the malfunctions of each unit’s thin pipe temperature
sensor are not reported, under the mode of heating, the malfunctions of each unit’s thick pipe
temperature sensor are not reported.
YJHJZH024BARRAFX
-SM
Содержание YJHJXH024BARR-FX
Страница 44: ...1 6 2 1 The Instruction For AS24GS1ERA YJHJZH024BARRAFX SM...
Страница 82: ...79 Domestic air conditioner Installation WARNING CAUTION YJHJZH024BARRAFX SM...
Страница 83: ...80 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 86: ...Installation 83 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 87: ...Installation 84 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 88: ...Installation 85 Domestic air conditioner YJHJZH024BARRAFX SM...
Страница 91: ...88 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 92: ...e g 1U18FS1ERA 89 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Страница 117: ...114 Domestic air conditioner Step Procedure Points 4 Remove the YDOYH EUDFNHW Removal of procedure YJHJZH024BARRAFX SM...
Страница 118: ...LULQJ LDJUDPV Domestic Air Conditioner 115 10 Wiring Diagrams 10 1 Indoor unit YJHJZH024BARRAFX SM...
Страница 123: ...The end YJHJZH024BARRAFX SM...