8) Parameter Setting Interface-8
Press F1 to return to the parameter setting interface-3
Press F3 to return to the previous setting interface
Press F4 to enter into the next parameter setting interface
ITS SETTING
HOLD LOAD D.P.
1030KPa
UNLOAD D.P.
1060KPa
HIGH D.P.SHUTDOWN
1090KPa
UNLOAD CURR.
95%
DELTA T
4.5
℃
LISV TEMP
70.0
℃
MINIMUM LOAD
15%
BACK
NEXT
RETU
Setting scope and default value of the parameter:
HOLD LOAD D.P: 100
~
1300kPa Default: 1030kPa
UNLOAD D.P: 100
~
1300kPa Default: 1060kPa
HIGH D.P.SHUTDOWN : 100
~
1350kPa Default: 1090kPa
UNLOAD CURR: 10
~
98 % Default: 95 %
DELTA T: 2.0
~
6.0
℃
Default: 4.5
℃
LISV TEMP: 50.0
~
80.0
℃
Default: 70.0
℃
MINIMUM LOAD: 15~75%
Default: 35%
(9) Parameter Setting Interface-9
Press F1 to return to the parameter setting interface-3
Press F4 to enter into the next parameter set interface
LHL TEMP SET
55.0
℃
LHL TEMP CR
1.0
℃
CR BUFFER
2.5
℃
LOW LELT
2.0
℃
HIGH LHLT
62.0
℃
L E.P UNLOAD
175KPa
L E.P SHUTDOWN
165KPa
RETU
NEXT
Setting scope and default value of the parameter:
LHL TEMP SET: 30.0
~
60.0
℃
Default: 55.0
℃
LHL TEMP CR: 0.5
~
2.0
℃
Default: 1.0
℃
LOW LELT: 1.0
~
7.0
℃
Default: 2.0
℃
HIGH LCLT: 30.0
~
62.0
℃
Default: 62.0
℃
L E.P UNLOAD: 150
~
300kPa Default: 175kPa
L E.P SHUTDOWN: 150
~
300kPa Default: 165kPa
CR BUFFER: 1.0
–
2.5
℃
Default: 2.5
℃
(10) Parameter Setting Interface-10
Press F1 to return to the parameter setting interface-3
Press F3 to return to the previous setting interface
Press F4 to enter into the next parameter setting interface
HEAT(D1-HP/E-HP2) SETTING
RETU
NEXT
HOLD LOAD D.P 1660KPa
UNLOAD D.P 1685KPa
HICH D. P. SHUTDOWN 1745KPa
UNLOAD CURR. 95%
DELTA T 4.5
℃
LISU TEMP 80.0
℃
MINIMUM LOAD 35%
BACK
Setting scope and default value of the parameter:
HOLD LOAD D.P. : 1000
~
1600kPa Default: 1581kPa
UNLOAD D.P.: 1000
~
1700kPa Default: 1700kPa
HIGH D.P.SHUTDOWN: 1000
~
1800kPa Default: 1790kPa
UNLOAD CURR. : 10
~
98 % Default: 95%
DELTA T: 2.0
~
6.0
℃
Default: 4.5
℃
LISV TEMP: 50.0
~
80.0
℃
Default: 80.0
℃
MINIMUM LOAD: 15~75%
Default: 35%
YEWS-E Water Cooling Screw Chiller/Heat Pump
(11) Parameter Setting Interface-11
Press F1 to return to the parameter setting interface-3
Press F4 to enter into the next parameter set interface
HEAT(E-HP) SETTING
LHL TEMP SET 45.0
LHL TEMP CR 1.0
CR BUFFER 2.5
LOW LELT 2.0
HIGH LHLT 52.0
L E.P UNLOAD 175KPa
L E.P SHUTDOWN 165KPa
℃
℃
℃
℃
℃
RETU
NEXT
Setting scope and default value of the parameter:
LHL TEMP SET: 30.0
~
50.0
℃
Default: 45.0
℃
LHL TEMP CR: 0.5
~
2.0
℃
Default: 1.0
℃
LOW LELT: 1.0
~
7.0
℃
Default: 2.0
℃
HIGH LCLT: 30.0
~
52.0
℃
Default: 52.0
℃
L E.P UNLOAD: 150
~
300kPa Default: 175kPa
L E.P SHUTDOWN: 150
~
300kPa Default: 165kPa
CR BUFFER: 1.0
–
2.5
℃
Default: 2.5
℃
HEAT(D1-HP/E-HP2) SETTING
34
Содержание YEWS Series
Страница 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Страница 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Страница 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Страница 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Страница 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Страница 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Страница 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Страница 86: ...YEWS field connection for 60Hz power 81...
Страница 87: ...Transformer for230V 3P 60Hz Application 82...
Страница 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...