Y99AB-4 BASO Test Kit Application Note

Troubleshooting

The following table indicates symptoms and corrective actions.

Table 3: Troubleshooting Symptoms and Corrective Actions

Symptom

Possible Cause

Corrective Action

Excessive draft

Baffle secondary air or shield pilot burner.

Recirculation of flue products

Check venting and main orifice sizing and
correct where necessary.

Excessive temperature

Check main burner input and correct if
necessary.

Improper pilot flame size or
characteristic

Check gas pressure, clean pilot burner,
and adjust flame.

Defective thermocouple

Perform the 

Open Circuit Millivolt

 

Readings

procedure.

Pilot burner outage, varying
performance, or poor mV output.

Weak holding BASO power unit

Perform the 

Dropout Testing

 procedure.

Defective thermostat

Perform the 

Continuity Testing

 procedure.

Pilot burner burning, manual valve
(if included) turned to the “On”
position, thermostat calling for
heat. Main burner does not come
on.

Defective operator

Check for operator input voltage. If present,
replace the valve. If not, check voltage
source.

Shorted thermostat circuit

Perform the 

Continuity Testing

 procedure.

Thermostat not calling for heat, or
turned down, manual valve (if
included) in the “On” position. Main
burner does not shut off.

Foreign particles lodged between
the valve seat

Replace the valve.

Thermocouple out of position

Reposition thermocouple properly.

Thermocouple lead dirty or loose

Clean and tighten thermocouple lead
connection.

Defective thermocouple

Perform the 

Open Circuit Millivolt Readings

procedure.

Defective BASO power unit

Perform the 

Dropout Testing

 procedure.

Defective orifice

Clean or replace orifice.

No burner flame or flame does not
stay on.

Unusually strong drafts

Baffle secondary air or shield burner.

Controls Group

507 E. Michigan Street
P.O. Box 423

Printed in U.S.A.

Milwaukee, WI  53201

www.johnsoncontrols.com

Содержание Y99AB-4

Страница 1: ...res for each division on the dial Continuity Tester for detecting a broken or open circuit Definitions Automatic Pilot A device employed with gas burning equipment which automatically shuts off the gas supply to the burner being served by either direct or indirect means when the pilot flame is extinguished The pilot burner may or may not be constructed integrally with the device Closed Circuit Mil...

Страница 2: ... thermocouple operated gas valve electrically operated gas valve and safety shutoff device connection diagrams Perform the following procedure for taking open circuit millivolt readings 1 Shut off the gas supply at the main manual shutoff valve 2 Disconnect the thermocouple from the BASO control 3 Attach the test cable lead 44549 8 to the thermocouple Connect the red clip to the copper tubing of t...

Страница 3: ...p to the copper tubing of the adapter assembly and the black clip to the control end of the adapter assembly see Figure 5 3 Set the slide switch on the meter to the 0 50 or 0 1000 position 4 Reestablish pilot flame 5 The millivolt reading should agree with the values listed in Table 1 with a normal pilot flame see Figure 3 Note When taking a fixed load millivolt reading on a junction block thermoc...

Страница 4: ... The milliampere reading at the moment of release is the dropout point of the BASO power unit Take two more readings by the same process and average the readings The milliampere dropout point must lie within the high and low range listed in Table 2 7 Pilot and main burner should extinguish within a few seconds If flames do not extinguish refer to the Troubleshooting section 44549 8 H17 Gas Valve R...

Страница 5: ...llowing procedure for closed circuit testing 1 Disconnect the thermocouple from the BASO control 2 Attach the adapter assembly 64119 1D to the control and thermocouple 3 Remove the shorting jumper clip from the adapter assembly 4 Set the slide switch on the meter to the 0 50 position 5 Attach the test cable lead 44549 8 Connect the red clip to the copper tubing of the thermocouple and the black cl...

Страница 6: ... 44549 8 Figure 8 Typical Thermocouple operated Gas Valve Connection Diagram Power Source Thermostat Transformer 44549 7 44549 8 BASO Magnetic Operator BASO Power Unit Reset Button B Valve Shutoff Valve Pilot Burner Gas Line Thermocouple Lead Red Black Figure 9 Typical Electrically operated Gas Valve Connection Diagram ...

Страница 7: ...it Application Note 7 Transformer Shutoff Valve Pilot Burner Gas Line 44549 7 Black Red 44549 8 B Valve L Series Control Power Source Thermostat Thermocouple Lead Figure 10 Typical Safety Shutoff Device Connection Diagram ...

Страница 8: ...r burning manual valve if included turned to the On position thermostat calling for heat Main burner does not come on Defective operator Check for operator input voltage If present replace the valve If not check voltage source Shorted thermostat circuit Perform the Continuity Testing procedure Thermostat not calling for heat or turned down manual valve if included in the On position Main burner do...

Отзывы: