Y99AB-4 BASO Test Kit Application Note

General Instructions

When using the test kit, insert the plugs securely
and squarely into the jacks. The thermocouple
adapters and nuts must be clean and tight. Any
meter fluctuation caused by the movement of these
parts may be due to loose connections. Poor
connections cause false readings. Three “D” size
batteries are required.

!

  WARNING: Risk of Fire or Explosion.

In order to test the thermocouple under actual
flame conditions, it is necessary to hold the BASO
power unit open with the DC power pack provided
with the test kit. This eliminates the safety function
provided by the BASO power unit. Care must be
exercised during this test to ensure that gas is not
permitted to flow to the main burner.

!

  CAUTION: Risk of Equipment Damage.

This meter is designed and calibrated for
Direct Current (DC) voltages up to 1000 millivolts
only. Any attempt to measure Alternating Current
(AC) voltage or DC voltage over 1000 millivolts will
damage the meter.

Open Circuit Millivolt Readings

Refer to Figure 8 through Figure 10 for typical
thermocouple-operated gas valve,
electrically-operated gas valve, and safety shutoff
device connection diagrams.

Perform the following procedure for taking open
circuit millivolt readings.

1.  Shut off the gas supply at the main manual

shutoff valve.

2.  Disconnect the thermocouple from the BASO

control.

3.  Attach the test cable lead 44549-8 to the

thermocouple. Connect the red clip to the
copper tubing of the thermocouple and the black
clip to the terminal at the end of the
thermocouple (see Figure 2).

4.  Set the slide switch on the meter to the 0-50 or

0-1000 position.

5. Re-establish 

pilot 

flame.

6.  The millivolt reading should agree with the

values listed in Table 1 with a normal pilot flame
(see Figure 3).

Note:  When taking an open circuit millivolt reading on
a junction block thermocouple, the junction block
terminal must be shorted (see Figure 4). This will isolate
the thermocouple from the high limit.

DC MILLIVOTS

PENN -BASO C ONT ROLS

0

10

20

30

40

50

100

300

500

700

900

MILLIAMPS

0-500

MILLIVOLTS

0-1000 0-50

ADJUST

MILLIVOLTS

MILLIAMPS

44549-8

Black

Red

Thermocouple

Lead

Figure 2: Open Circuit Millivolt Reading Connection

Diagram

Approximately

12.7 mm (1/2 in.)

Figure 3: Normal Pilot Flame

High
Limit

Switch

Shorting Wire

Figure 4: Junction Block Thermocouple

Содержание Y99AB-4

Страница 1: ...res for each division on the dial Continuity Tester for detecting a broken or open circuit Definitions Automatic Pilot A device employed with gas burning equipment which automatically shuts off the gas supply to the burner being served by either direct or indirect means when the pilot flame is extinguished The pilot burner may or may not be constructed integrally with the device Closed Circuit Mil...

Страница 2: ... thermocouple operated gas valve electrically operated gas valve and safety shutoff device connection diagrams Perform the following procedure for taking open circuit millivolt readings 1 Shut off the gas supply at the main manual shutoff valve 2 Disconnect the thermocouple from the BASO control 3 Attach the test cable lead 44549 8 to the thermocouple Connect the red clip to the copper tubing of t...

Страница 3: ...p to the copper tubing of the adapter assembly and the black clip to the control end of the adapter assembly see Figure 5 3 Set the slide switch on the meter to the 0 50 or 0 1000 position 4 Reestablish pilot flame 5 The millivolt reading should agree with the values listed in Table 1 with a normal pilot flame see Figure 3 Note When taking a fixed load millivolt reading on a junction block thermoc...

Страница 4: ... The milliampere reading at the moment of release is the dropout point of the BASO power unit Take two more readings by the same process and average the readings The milliampere dropout point must lie within the high and low range listed in Table 2 7 Pilot and main burner should extinguish within a few seconds If flames do not extinguish refer to the Troubleshooting section 44549 8 H17 Gas Valve R...

Страница 5: ...llowing procedure for closed circuit testing 1 Disconnect the thermocouple from the BASO control 2 Attach the adapter assembly 64119 1D to the control and thermocouple 3 Remove the shorting jumper clip from the adapter assembly 4 Set the slide switch on the meter to the 0 50 position 5 Attach the test cable lead 44549 8 Connect the red clip to the copper tubing of the thermocouple and the black cl...

Страница 6: ... 44549 8 Figure 8 Typical Thermocouple operated Gas Valve Connection Diagram Power Source Thermostat Transformer 44549 7 44549 8 BASO Magnetic Operator BASO Power Unit Reset Button B Valve Shutoff Valve Pilot Burner Gas Line Thermocouple Lead Red Black Figure 9 Typical Electrically operated Gas Valve Connection Diagram ...

Страница 7: ...it Application Note 7 Transformer Shutoff Valve Pilot Burner Gas Line 44549 7 Black Red 44549 8 B Valve L Series Control Power Source Thermostat Thermocouple Lead Figure 10 Typical Safety Shutoff Device Connection Diagram ...

Страница 8: ...r burning manual valve if included turned to the On position thermostat calling for heat Main burner does not come on Defective operator Check for operator input voltage If present replace the valve If not check voltage source Shorted thermostat circuit Perform the Continuity Testing procedure Thermostat not calling for heat or turned down manual valve if included in the On position Main burner do...

Отзывы: