Y99AB-4 BASO Test Kit Application Note

Dropout Testing

Refer to Figure 8 through Figure 10 for typical
thermocouple-operated gas valve,
electrically-operated gas valve, and safety shutoff
device connection diagrams.

Perform the following procedure using the
milliammeter for dropout testing.

1.  Shut off the gas at the main manual shutoff

valve.

2.  Disconnect the thermocouple lead from the

BASO control.

3.  Connect the test cable lead 44549-7 to the

milliamperes jack on the test kit meter, connect
the other end to the BASO control
(see Figure 6).

4.  Set the slide switch on the meter to the 0-500

(50 on scale) position.

5.  Turn the adjust knob on the meter clockwise to

the full scale deflection of the needle. Reset the
control by pressing in the reset button on the
control firmly.

6.  Turn the adjust knob on the meter

counterclockwise slowly until the BASO control
power unit releases. The milliampere reading at
the moment of release is the dropout point of the
BASO power unit. Take two more readings by
the same process, and average the readings.
The milliampere dropout point must lie within the
high and low range listed in Table 2.

7.  Pilot and main burner should extinguish within a

few seconds. If flames do not extinguish, refer to
the Troubleshooting section.

44549-8

H17

Gas Valve

Reset

Button

44549-7

MILLIAMPS

MILLIVOLTS

20

0

10

10

0

300

DC MILLIVOLTS

PENN-BASO CONTROLS

500

700

90

0

30

40

50

MILLIAMPS

0-500

0-1000  0-50
MILLIVOLTS

JOHNSON CONTROLS, INC

WATERTOWN, WI., U.S.A

ADJUST

Figure 6: Dropout Testing Connection Diagram

Table 2: Milliampere Dropout Range

mA Range of Power

Unit Assembly

BASO Control

Part Number

Low

High

H15A_, H15C_, H15D_, H15H_

100

300

H15E_, H15F_

60

150

H17_A

100

300

H17_B

50

165

H19A_

100

300

H19ME

45

165

H19L_, H19N_, H19R_, H19T_

100

300

H43AA, H43BA, H43GA

100

300

H43AB, H43BB

50

165

G92 (All models except
G92CAA-19 and G92CBA-10)

100

300

G92CAA-19 and G92CBA-10

100

200

G93

100

300

G292

100

300

L61LL

75

200

L62AA

100

300

L62GB

100

300

Содержание Y99AB-4

Страница 1: ...res for each division on the dial Continuity Tester for detecting a broken or open circuit Definitions Automatic Pilot A device employed with gas burning equipment which automatically shuts off the gas supply to the burner being served by either direct or indirect means when the pilot flame is extinguished The pilot burner may or may not be constructed integrally with the device Closed Circuit Mil...

Страница 2: ... thermocouple operated gas valve electrically operated gas valve and safety shutoff device connection diagrams Perform the following procedure for taking open circuit millivolt readings 1 Shut off the gas supply at the main manual shutoff valve 2 Disconnect the thermocouple from the BASO control 3 Attach the test cable lead 44549 8 to the thermocouple Connect the red clip to the copper tubing of t...

Страница 3: ...p to the copper tubing of the adapter assembly and the black clip to the control end of the adapter assembly see Figure 5 3 Set the slide switch on the meter to the 0 50 or 0 1000 position 4 Reestablish pilot flame 5 The millivolt reading should agree with the values listed in Table 1 with a normal pilot flame see Figure 3 Note When taking a fixed load millivolt reading on a junction block thermoc...

Страница 4: ... The milliampere reading at the moment of release is the dropout point of the BASO power unit Take two more readings by the same process and average the readings The milliampere dropout point must lie within the high and low range listed in Table 2 7 Pilot and main burner should extinguish within a few seconds If flames do not extinguish refer to the Troubleshooting section 44549 8 H17 Gas Valve R...

Страница 5: ...llowing procedure for closed circuit testing 1 Disconnect the thermocouple from the BASO control 2 Attach the adapter assembly 64119 1D to the control and thermocouple 3 Remove the shorting jumper clip from the adapter assembly 4 Set the slide switch on the meter to the 0 50 position 5 Attach the test cable lead 44549 8 Connect the red clip to the copper tubing of the thermocouple and the black cl...

Страница 6: ... 44549 8 Figure 8 Typical Thermocouple operated Gas Valve Connection Diagram Power Source Thermostat Transformer 44549 7 44549 8 BASO Magnetic Operator BASO Power Unit Reset Button B Valve Shutoff Valve Pilot Burner Gas Line Thermocouple Lead Red Black Figure 9 Typical Electrically operated Gas Valve Connection Diagram ...

Страница 7: ...it Application Note 7 Transformer Shutoff Valve Pilot Burner Gas Line 44549 7 Black Red 44549 8 B Valve L Series Control Power Source Thermostat Thermocouple Lead Figure 10 Typical Safety Shutoff Device Connection Diagram ...

Страница 8: ...r burning manual valve if included turned to the On position thermostat calling for heat Main burner does not come on Defective operator Check for operator input voltage If present replace the valve If not check voltage source Shorted thermostat circuit Perform the Continuity Testing procedure Thermostat not calling for heat or turned down manual valve if included in the On position Main burner do...

Отзывы: