Table 3: Dimensions - XAU uncased upflow or
downflow coil
Dimensions
Height Width
Refrigerant
connections
line size
Models
A (in.) B (in.)
Liquid
(in.)
Vapor
(in.)
XAUA18AXXN1 16 5/8
13
XAUA24BXXN1 18 3/4
13
XAUB30CXXN1 21 1/4
16
XAUB36DXXN1 21 1/2
16
3/4
XAUC42EXXN1
23
19 1/2
XAUC48FXXN1
25
19 1/2
XAUC60GXXN1 29 1/4 19 1/2
XAUD60GXXN1 28 3/4
23
XAUD60HXXN1
33
23
3/8
7/8
Note:
• Refrigerant line sizes may require larger lines
for extended line lengths. Refer to application
data part number 247077.
• The adapter fitting must be field installed for
any refrigeration piping sizes not shown in the
table.
• Refer to the
Technical Guide
for the outdoor unit
for the proper refrigeration piping size.
Limitations
Install the coil in accordance with all national and local
Table 4: Coil airflow limits
CFM limits
Coil size
Outdoor
unit (ton)
Minimum
Maximum
18
1 1/2
525
675
1 1/2
525
675
24
2
700
900
2
700
900
30
2 1/2
875
1125
2 1/2
875
1125
36
3
1050
1350
3
1050
1350
42
3 1/2
1225
1575
3
1050
1350
3 1/2
1225
1575
48
4
1400
1800
4
1600
1800
60
5
1750
2250
Installation overview
1. Before installation, review the installation aids
. During
installation, use the installation aids to verify that
tasks are completed as required. See Figure 7 for an
overview of components and their location.
2. Install the coil metering device as required. See
3. Install the coil. See
Installing the coil: XAF and XAH
Installing the coil: XAU coils
4. Connect the duct system. See
.
5. Connect the condensate drain lines. See
.
6. Connect the refrigerant lines. See
.
7. Clean the coil. See
8. Check and adjust airflow as required. See
9. Instruct the homeowner as needed. See
Using a coil metering device
You must install a piston or TXV (flex coil models) in the
field, unless you are using a coil with a factory installed
TXV or a coil equipped with an electronic expansion valve
Using a coil equipped with an EEV: XAF and XAH
Technical Guide
for outdoor units for
information on the piston or TXV required for the indoor
coil. It is best practice to install the piston or TXV kit before
installing the coil and brazing the refrigeration piping.
Note:
Do not install the TXV sensing bulb until you
have completed the brazing and the piping has
cooled.
For TXV installation, refer to the
Installation Manual
provided with the TXV kit and see
.
For piston installation, see
and the Schrader valve core are supplied with the outdoor
unit if applicable. Some outdoor sections require a TXV. If
using a piston instead of a TXV, install the Schrader valve
core in the suction line equalizer connection port and cap
the Schrader valve core with the plastic cap supplied. Do
not install the Schrader valve core if a TXV is installed,
because the TXV equalizer line attaches to the equalizer
connection port or suction line port.
CAUTION
COIL UNDER PRESSURE
Verify that pressure has been released by depressing
Schrader valve core shown in Figure 1 and Figure
2. The coil requires a metering device to be added.
Refer to outdoor unit documentation for correct TXV
or piston to be used.
Installation Manual: XAF, XAH, and XAU Series - Full Cased and Uncased Coils for Cooling and Heat Pumps