Table 10: XAH airflow data (CFM) - horizontal left
CFM
400
600
800
1000
1200
1400
1600
1800
2000
Models
External static pressure (in. W.C.)
XAHC60H
0.02
0.05
0.08
0.12
0.17
0.23
0.30
0.37
0.46
XAHD60H
0.02
0.04
0.06
0.08
0.12
0.16
0.20
0.25
0.30
XAHD60J
0.03
0.06
0.09
0.13
0.17
0.22
0.29
0.35
0.43
Note:
- Airflow data is for dry coil conditions only, tested without filters.
- For optimal performance, external static pressures of 0.2 in. W.C. to 0.6 in. W.C. are recommended.
Applications above 0.6 in. W.C. are not recommended.
Table 11: XAH airflow data (CFM) - horizontal right
CFM
400
600
800
1000
1200
1400
1600
1800
2000
Models
External static pressure (in. W.C.)
XAHA18A
0.07
0.14
0.23
n/a
n/a
n/a
n/a
n/a
n/a
XAHA24B
0.06
0.13
0.21
0.31
n/a
n/a
n/a
n/a
n/a
XAHB24B
0.05
0.09
0.15
0.20
n/a
n/a
n/a
n/a
n/a
XAHB30C
0.04
0.08
0.13
0.18
0.25
n/a
n/a
n/a
n/a
XAHC30C
0.04
0.07
0.11
0.15
0.20
n/a
n/a
n/a
n/a
XAHB36D
0.05
0.11
0.17
0.25
0.35
0.48
n/a
n/a
n/a
XAHC36D
0.04
0.07
0.12
0.16
0.23
0.30
n/a
n/a
n/a
XAHC42E
0.03
0.07
0.11
0.15
0.21
0.28
0.37
n/a
n/a
XAHD42E
0.03
0.06
0.09
0.13
0.17
0.22
0.29
n/a
n/a
XAHC48F
0.03
0.06
0.10
0.14
0.20
0.26
0.34
0.43
n/a
XAHD48F
0.00
0.04
0.06
0.09
0.13
0.17
0.22
0.27
n/a
XAHC60G
0.03
0.06
0.09
0.13
0.19
0.25
0.33
0.41
0.50
XAHD60G
0.02
0.04
0.07
0.09
0.13
0.18
0.23
0.28
0.34
XAHC60H
0.03
0.06
0.09
0.13
0.19
0.25
0.33
0.40
0.49
XAHD60H
0.02
0.04
0.06
0.09
0.13
0.17
0.22
0.27
0.33
XAHD60J
0.03
0.06
0.10
0.14
0.19
0.25
0.33
0.40
0.49
Note:
- Airflow data is for dry coil conditions only, tested without filters.
- For optimal performance, external static pressures of 0.2 in. W.C. to 0.6 in. W.C. are recommended.
Applications above 0.6 in. W.C. are not recommended.
Table 12: XAU airflow data (CFM)
CFM
400
600
800
1000
1200
1400
1600
1800
2000
Models
External static pressure (in. W.C.)
XAUA18A
0.05
0.11
0.18
n/a
n/a
n/a
n/a
n/a
n/a
XAUA24B
0.05
0.11
0.19
0.28
n/a
n/a
n/a
n/a
n/a
XAUB30C
0.04
0.07
0.11
0.15
0.21
n/a
n/a
n/a
n/a
XAUB36D
0.03
0.06
0.11
0.16
0.23
0.30
n/a
n/a
n/a
Installation Manual: XAF, XAH, and XAU Series - Full Cased and Uncased Coils for Cooling and Heat Pumps
32
Johnson Controls Ducted Systems