• Where the return air duct is short or sound may

be a problem, use acoustical duct liner inside the

duct. You must insulate duct work that runs through

an unheated space during the heating season or

an uncooled space during the cooling season. It

is best practice to use a vapor barrier to prevent

absorption of moisture from the surrounding air into

the insulation.

• Correctly size the supply air duct by using a

transition to match the unit opening. Suspend

all ducts using flexible hangers and never fasten

ducts directly to the structure. Fabricate and install

duct work in accordance with local and/or national

codes. This includes the standards of the National

Fire Protection Association for Installation of Air

Conditioning and Ventilating Systems, NFPA No. 90B.

 CAUTION

Equipment should never be operated without filters.

Connecting the condensate drain

Adhere to the following:

• Pitch all drain lines 1/4 in./ft away from the unit

drain pan and make sure that the drain lines are no

smaller than the coil drain connection.

• Route the drain line so that it does not impede

access to the coil, furnace, air handling system, or

filter and is not exposed to freezing temperatures.

• Instruct the homeowner that the indoor coil drain

pan must be inspected and cleaned regularly to

prevent odors and ensure proper drainage.

 NOTICE

For XAF and XAH coils, when the coil is installed in

an attic or above a finished ceiling, an auxiliary drain

pan must be provided under the coil as is specified by

most local building codes.

• Install the coil level or pitched slightly toward the

drain end. Suggested pitch must not exceed 1/4 in./

ft of coil.

• Note that you can remove drain plugs using a

standard 3/8-in. drive socket ratchet.

• If the coil has a secondary drain, pipe it to a location

that gives the occupant a visual warning that the

primary drain is clogged. If a secondary drain is not

used, you must plug the secondary drain. See Figure

39, Figure 40, Figure 41, or Figure 42.

 CAUTION

Avoid double trapping.

 CAUTION

Threaded drain connections should be hand

tightened, plus no more than one turn.

• Do not use PTFE tape, pipe thread compound, or

other sealants. Use of a sealant can cause damage

and premature failure of the drain pan.

 NOTICE

If the coil is installed in a draw-through application

(modular blower), the installer must trap the primary

and secondary drain line. If the secondary drain line is

not used, it must be plugged.

Connecting refrigerant lines

About this task:

 CAUTION

Coil is under inert gas pressure. Relieve pressure

from coil by depressing Schrader core at end of

suction manifold stub out.

 CAUTION

Dry nitrogen should always be supplied through

the tubing while it is being brazed, because the

temperature required is high enough to cause

oxidation of the copper unless an inert atmosphere

is provided. The flow of dry nitrogen should continue

until the joint has cooled. Always use a pressure

regulator and safety valve to insure that only low

pressure dry nitrogen is introduced into the tubing.

Only a small flow is necessary to displace air and

prevent oxidation.

Installation Manual: XAF, XAH, and XAU Series - Full Cased and Uncased Coils for Cooling and Heat Pumps

27

Johnson Controls Ducted Systems 

Содержание XAF Series

Страница 1: ...ll Cased and Uncased Coils for Cooling and Heat Pumps XAF full cased upflow or downflow XAH full cased horizontal left or right and XAU uncased upflow or downflow York International Corporation 5005 Y...

Страница 2: ...2 Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Cooling and Heat Pumps Johnson Controls Ducted Systems...

Страница 3: ...coils 20 Repositioning the transition angle for downflow or horizontal right application with a furnace XAF and XAH coils 20 Horizontal right and left applications XAH coils 20 Installing the coil XA...

Страница 4: ...4 Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Cooling and Heat Pumps Johnson Controls Ducted Systems...

Страница 5: ...njury or property damage Refer to this manual for assistance For additional information consult a qualified installer or service agency CAUTION This product must be installed in strict compliance with...

Страница 6: ...r Figure 2 Inspect the coil for possible damage during transit If damage is evident note the extent of the damage on the carrier s delivery receipt Make a separate request for inspection by the carrie...

Страница 7: ...AF upflow or downflow full cased coil Figure 4 Dimensions XAF upflow or downflow full cased coil Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Cooling and Heat Pumps 7 Jo...

Страница 8: ...20 20 XAFD42EXXN1 25 24 1 2 23 1 2 23 1 2 XAFD42EBCN1 25 24 1 2 23 1 2 23 1 2 XAFC48FXXN1 27 21 20 20 XAFC48FBAN1 27 21 20 20 XAFC48FBCN1 27 21 20 20 XAFD48FXXN1 27 24 1 2 23 1 2 23 1 2 XAFD48FBAN1 27...

Страница 9: ...l cased horizontal left or right coil Figure 6 Dimensions XAH full cased horizontal left or right coil Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Cooling and Heat Pump...

Страница 10: ...20 XAHC48FBCN1 33 21 20 20 XAHD48FXXN1 32 3 4 24 1 2 23 1 2 23 1 2 XAHD48FBAN1 32 3 4 24 1 2 23 1 2 23 1 2 XAHD48FBCN1 32 3 4 24 1 2 23 1 2 23 1 2 XAHC60GXXN1 37 1 4 21 20 20 XAHC60GBAN1 37 1 4 21 20...

Страница 11: ...AH coils Figure 8 Component location XAU uncased upflow or downflow coil Figure 9 Dimensions XAU uncased upflow or downflow coil Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils...

Страница 12: ...6 Connect the refrigerant lines See Connecting refrigerant lines 7 Clean the coil See Cleaning the coil 8 Check and adjust airflow as required See Adjusting the air system 9 Instruct the homeowner as...

Страница 13: ...if the coil was in the upflow position and adjust as necessary See Figure 10 3 Install the Schrader valve core supplied with the outdoor unit into the equalizer fitting connection port using a valve c...

Страница 14: ...potentially causing leaks 5 Slide the nut removed in Step 3 over the supplied liquid line Place the supplied PTFE washer from the TXV kit in place on the TXV and install the liquid line to the top of...

Страница 15: ...Cover the bulb completely to insulate it Figure 13 TXV bulb and equalizer line installation 9 When the refrigeration piping is installed leak test the system Figure 14 Correct bulb location for TXV In...

Страница 16: ...t the communication 4 wire cable included to the communicating 4 pin connector on the furnace or modular blower control board See Figure 15 and Figure 16 for the connection diagrams and see Figure 17...

Страница 17: ...17 Wiring diagram EEV Figure 18 XAF and XAH coils with an EEV installed Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Cooling and Heat Pumps 17 Johnson Controls Ducted S...

Страница 18: ...ecure the flanges in place using screws as shown in Figure 19 For field installed duct flanges XAH only attach the flanges shipped in the bag with the coil as shown in Figure 20 2 Use the tie plates t...

Страница 19: ...ations with furnaces Figure 23 Vertical upflow applications with modular air handlers Figure 24 Vertical downflow applications with modular air handlers Installation Manual XAF XAH and XAU Series Full...

Страница 20: ...screws that fasten the transition angle to the bottom front side of the cabinet 2 Remove the two screws from the top front side of the cabinet 3 Remove the transition angle rotate the transition angle...

Страница 21: ...o place with two screws as shown in Figure 29 2 Install the horizontal right drain pan extension with four screws as shown in Figure 29 Install the horizontal right drain pan extension onto the coil c...

Страница 22: ...es The following installation steps are provided only for reference for those who want to follow them Experienced sheet metal duct work technicians can choose to follow their own practices provided th...

Страница 23: ...m at a 90 angle See Figure 33 Table 7 Duct work dimensions in XAU coils Cabinet width Cabinet height Coil shelf opening width pre form Panel height Duct connector lower Duct connector upper Opening wi...

Страница 24: ...n in Figure 34 Figure 34 Coil shelf 7 Install the coil shelf through the plenum opening so that the duct flanges on the furnace support the coil shelf See Figure 35 Install the coil shelf level or pit...

Страница 25: ...anel installation See Figure 36 and Table 7 for the designated sizes Install standard S Locks onto the sides and top edges of the plenum access opening 12 Install the coil access panel onto the plenum...

Страница 26: ...ited to the installation You can use upflow horizontal or downflow applications Adhere to the following The vast majority of problems encountered with heating and cooling systems can be linked to inco...

Страница 27: ...uilding codes Install the coil level or pitched slightly toward the drain end Suggested pitch must not exceed 1 4 in ft of coil Note that you can remove drain plugs using a standard 3 8 in drive socke...

Страница 28: ...iers Important For EEV equipped coils only The EEV in this unit is shipped in the closed position to protect the valve during transportation Before brazing do the following i Connect the communication...

Страница 29: ...r to the furnace or modular air handler instructions for more information To check the CFM you measure the static pressure drop across the coil using a portable manometer and static pressure tips The...

Страница 30: ...a n a n a XAFC42E 0 02 0 04 0 08 0 11 0 16 0 21 0 27 n a n a XAFD42E 0 02 0 05 0 07 0 10 0 13 0 17 0 21 n a n a XAFC48F 0 01 0 04 0 07 0 10 0 14 0 19 0 24 0 30 n a XAFD48F 0 02 0 04 0 06 0 08 0 11 0...

Страница 31: ...16 0 21 0 27 0 33 XAFD60J 0 02 0 04 0 07 0 11 0 16 0 22 0 28 0 34 0 42 Note Airflow data is for dry coil conditions only tested without filters For optimal performance external static pressures of 0...

Страница 32: ...16 0 23 0 30 n a n a n a XAHC42E 0 03 0 07 0 11 0 15 0 21 0 28 0 37 n a n a XAHD42E 0 03 0 06 0 09 0 13 0 17 0 22 0 29 n a n a XAHC48F 0 03 0 06 0 10 0 14 0 20 0 26 0 34 0 43 n a XAHD48F 0 00 0 04 0 0...

Страница 33: ...low data is for dry coil conditions only tested without filters For optimal performance external static pressures of 0 2 in W C to 0 6 in W C are recommended Applications above 0 6 in W C are not reco...

Страница 34: ...plugged drain connections XAU Figure 41 Location of coil trapped and plugged drain connections with furnace XAF and XAH Installation Manual XAF XAH and XAU Series Full Cased and Uncased Coils for Coo...

Страница 35: ...of coil trapped and plugged drain connections with modular air handler XAF and XAH Note Verify that all drains are tapped or plugged Installation Manual XAF XAH and XAU Series Full Cased and Uncased...

Страница 36: ...ess door Third Party Trademarks Notice For information about third party trademarks refer to the relevant company websites Subject to change without notice Published in U S A Copyright 2021 by Johnson...

Отзывы: