Wiring

 CAUTION

Risk of Electric Shock

Disconnect the power supply before making electrical

connections to avoid electric shock.

 ATTENTION

Risque de décharge électrique

Débrancher l'alimentation avant de réaliser tout rac-

cordement électrique afin d'éviter tout risque de

décharge électrique.

Important: 

Do not connect supply power

to the controller before finishing wiring and

checking all wiring connections. Short circuits

or improperly connected wires can result

in damage to the controller and void any

warranty.

Important: 

Do not exceed the controller

electrical ratings. Exceeding controller electrical

ratings can result in permanent damage to the

controller and void any warranty.

Important: 

Use copper conductors only. Make

all wiring in accordance with local, national, and

regional regulations.

Important: 

Electrostatic discharge can

damage controller components. Use proper

electrostatic discharge precautions during

installation, setup, and servicing to avoid

damaging the controller.

For information on configuring and wiring

a BACnet/IP network, refer to the 

Metasys IP

Networks for BACnet/IP Controllers Configuration

Guide (LIT-12012458).

 For detailed information on

configuring and wiring a SA Bus, refer to the 

MS/TP

Communications Bus Technical Bulletin (LIT-12011034).

VMA terminals and bus ports

See  for input and output terminal and bus port

locations on the controllers. Observe the following

guidelines when wiring a VMA controller.

Input and Output terminals

The input spade terminals are located on the

bottom of the VMA near the FC Bus terminal block.

The output spade terminals are located on the

top of the controller near the power supply spade

terminals. For more information, see Table .

FC bus terminal block (Or N2 protocol as

required)

The FC Bus terminal block is a blue, removable, 4-

terminal plug that fits into a board-mounted jack.
Wire the removable FC Bus terminal block plugs

on the VMA and other controllers in a daisy-chain

configuration using 3-wire twisted, shielded cable as

shown in Figure 3. See Table  for more information.

Figure 3: FC bus terminal block wiring

Note: 

 The Shield terminal (SHLD) on the FC

Bus terminal block is isolated and can be used

to connect the cable shields on the bus (Figure

3).

SA Bus spade lugs

Wire the SA Bus spade lugs on the VMA and other

SA Bus devices in a daisy-chain configuration using

4-wire twisted, shielded cable as shown in Figure 4.

See Table  for more information.

VMA1617 and VMA1632 VAV Controllers Installation Guide

6

Содержание VMA1617

Страница 1: ...ning support and include tips for efficient and safe replacement Refer to the N2 Compatibility Options chapter of the Controller Tool Help LIT 12011147 for information about mapping N2 Objects in cont...

Страница 2: ...25 mm 1 in screw Materials and special tools needed Several 6 mm 1 4 in female spade terminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade scr...

Страница 3: ...pler Bolt see Mounting for information on setting the coupler bolt 9 Universal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A9...

Страница 4: ...ng the sheet metal screw from the original installation preferred option On panel or enclosure mount applications observe these additional guidelines Do not install the controller in an airtight enclo...

Страница 5: ...y installed on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in...

Страница 6: ...For detailed information on configuring and wiring a SA Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus...

Страница 7: ...Wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1617 or VMA1632 controller The supply power terminal on a new VMA is a two posi...

Страница 8: ...to the appropriate device address Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1617 or VMA1632 controller with the Wireless...

Страница 9: ...tive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 seco...

Страница 10: ...e Size Gauge and Type Maximum Cable Length and Type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted w...

Страница 11: ...sted wire B 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to...

Страница 12: ...er VAV Balancing Tool One to One Wireless Receiver Network Sensor 24 AWG 4 pair CAT 5 Cable 30 5 m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC 24 COM 24 VAC Power Supply Commo...

Страница 13: ...gures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input...

Страница 14: ...External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output...

Страница 15: ...damaging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and uniqu...

Страница 16: ...ZFR182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in...

Страница 17: ...F 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication pr...

Страница 18: ...efer to the Controller Tool Help LIT 12011147 and Controller Provisioning with Tools LIT 12013247 for detailed information about commissioning field controllers Note The MAP Gateway serves as a replac...

Страница 19: ...must be no short circuit Note Some installations require the Secondary of the Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared betw...

Страница 20: ...Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify the appropriate product for your region MS DIS1710 0 Local Controller Display MS BTCVTCBL 700 Cable Replacement S...

Страница 21: ...F 1000 326 Flexible Tubing Extension with Barbed Fitting for VMA1617 and VMA1632 35 56 cm 14 in Length Bulk Pack of 20 MS VMAACT 701 VMA Actuator Assembly Gearbox Replacement Kit TE730 29C 0 Sensor wi...

Страница 22: ...or N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable between BACnet MSTP or N2 FC Bus 0 6 mm 22 AWG standard 3 wire twisted shielded cable recommende...

Страница 23: ...Testing Laboratories BTL Protocol Revision 7 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application...

Страница 24: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: