Table 5: Communication bus and supply power terminal blocks, functions, ratings, requirements, and
cables
Terminal block/Port label
Terminal labels
Function, electrical ratings/
Requirements
Recommended cable type
+
-
SA Bus Communications
COM
SA Bus Signal Reference and 15 VDC
Common
SA BUS
3
POWER
15 VDC Supply Power for Devices on the
SA Bus
0.6 mm (22 AWG) stranded, 4-wire
(2 twisted-pairs), shielded cable
recommended
Note:
The + and - wires are one
twisted pair, and the COM and
SA PWR wires are the second
twisted pair.
TSTAT
TSTAT
RJ-45 8-Position Modular Connector
pr15 VDC Power for:
•
Wireless Commissioning
Converter
•
VAV Balancing Tool
•
One-to-One Wireless Receiver
•
Network Sensor
24 AWG 4-pair CAT 5 Cable <30.5 m
(100 ft)
HOT
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)
24~
COM
24 VAC Power Supply Common
The terminal is isolated from the FC bus
common.
0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire
1
To determine wire size and cable lengths for cables other than the recommended cables, see Table .
2
The SA Bus and FC Bus wiring recommendations in this table are for MS/TP Bus communications at 38.4k baud. For more
information, refer to the
MS/TP Communications Bus Technical Bulletin (LIT-12011034)
.
3
The SA bus wiring recommendations are for MS/TP Bus communications at 38.4k baud. For more information, refer to the
MS/TP
Communications BusTechnical Bulletin (LIT-12011034)
.
VMA1617 and VMA1632 VAV Controllers Installation Guide