VMA1617 and VMA1632 VAV Controllers

Installation Guide

Applications

The VMA1617 and VMA1632 programmable digital

controllers are designed for Variable Air Volume

(VAV) applications that communicate through the

BACnet

®

 MS/TP or N2 protocol. These Variable

Air Volume Modular Assembly (VMA) controllers

feature combinations of an integral digital pressure

sensor (DPT), a damper actuator, and a 32-bit

microprocessor. The controllers' small package size

facilitates quick field installation and efficient use

of space without compromising high-tech control

performance. These VMA controllers connect easily

to the non-communicating sensor for zone air

temperature sensing.

Switchable communications
protocols

By default, 

 Metasys

®

 system controllers and

network sensors communicate using the standard

BACnet protocol, based on the ANSI/ASHRAE

135-2004.
The BACnet

®

 protocol is a standard for ANSI,

ASHRAE, and the International Standards

Organization (ISO) for building controls.
VMA16 controllers are BTL-tested and listed as

BACnet Application Specific Controllers (B-ASCs).
Release 10.1 and higher of Controller Configuration

Tool (CCT) can be used to switch the Field Bus

communications protocol in this controllers

to be either the standard BACnet MS/TP or

the N2 protocol. BACnet MS/TP is the default

communications protocol for all new controllers.

Switchable communications protocols provide a

cost-effective upgrade and modernization path

for customers with existing N2 controllers. The

Modernization Guide for Legacy N2 Controllers

(LIT-12012005)

 and the controller-specific

documentation provide installation and

commissioning support and include tips for

efficient and safe replacement. Refer to the 

N2

Compatibility Options 

chapter of the 

Controller

Tool Help (LIT-12011147)

 for information about

mapping N2 Objects in controllers with switchable

communications protocols.
The N2-capable controllers can be used as functional

replacements for legacy N2 controllers. The N2-

capable controllers have the following features and

benefits:
• Have the I/O quantities and characteristics of

Metasys

 family controllers

• Must be programmed with CCT, which has similar,

but not identical programming capabilities as

HVACPro, GX9100, GPL, and other legacy tools

• Support SA Bus devices
• Support WRZ wireless sensors from the controller

using the WRZ-7860 receiver

• Are available in Buy American versions (most

models)

The N2-capable controllers 

do not

 support the

following features:
• Zone Bus (for example, TMZ sensors and M100

actuators) or XT-Bus (System 91) devices (for

example, XT, XTM, and XP modules)

• Wireless connection to the N2 bus
• NxE passthrough

North American emissions
compliance

United States

This equipment has been tested and found to

comply with the limits for a Class A digital device

pursuant to Part 15 of the FCC Rules. These limits

are designed to provide reasonable protection

against harmful interference when this equipment

is operated in a commercial environment. This

equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications.

Operation of this equipment in a residential area

may cause harmful interference, in which case the

users will be required to correct the interference at

their own expense.

*2410143349E*

Part No.  24-10143-349 Rev. E

2019-10-18

(barcode for factory use only)

MS-VMA1617, MS-VMA1632

Содержание VMA1617

Страница 1: ...ning support and include tips for efficient and safe replacement Refer to the N2 Compatibility Options chapter of the Controller Tool Help LIT 12011147 for information about mapping N2 Objects in cont...

Страница 2: ...25 mm 1 in screw Materials and special tools needed Several 6 mm 1 4 in female spade terminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade scr...

Страница 3: ...pler Bolt see Mounting for information on setting the coupler bolt 9 Universal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A9...

Страница 4: ...ng the sheet metal screw from the original installation preferred option On panel or enclosure mount applications observe these additional guidelines Do not install the controller in an airtight enclo...

Страница 5: ...y installed on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in...

Страница 6: ...For detailed information on configuring and wiring a SA Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus...

Страница 7: ...Wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1617 or VMA1632 controller The supply power terminal on a new VMA is a two posi...

Страница 8: ...to the appropriate device address Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1617 or VMA1632 controller with the Wireless...

Страница 9: ...tive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 seco...

Страница 10: ...e Size Gauge and Type Maximum Cable Length and Type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted w...

Страница 11: ...sted wire B 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to...

Страница 12: ...er VAV Balancing Tool One to One Wireless Receiver Network Sensor 24 AWG 4 pair CAT 5 Cable 30 5 m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC 24 COM 24 VAC Power Supply Commo...

Страница 13: ...gures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input...

Страница 14: ...External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output...

Страница 15: ...damaging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and uniqu...

Страница 16: ...ZFR182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in...

Страница 17: ...F 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication pr...

Страница 18: ...efer to the Controller Tool Help LIT 12011147 and Controller Provisioning with Tools LIT 12013247 for detailed information about commissioning field controllers Note The MAP Gateway serves as a replac...

Страница 19: ...must be no short circuit Note Some installations require the Secondary of the Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared betw...

Страница 20: ...Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify the appropriate product for your region MS DIS1710 0 Local Controller Display MS BTCVTCBL 700 Cable Replacement S...

Страница 21: ...F 1000 326 Flexible Tubing Extension with Barbed Fitting for VMA1617 and VMA1632 35 56 cm 14 in Length Bulk Pack of 20 MS VMAACT 701 VMA Actuator Assembly Gearbox Replacement Kit TE730 29C 0 Sensor wi...

Страница 22: ...or N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable between BACnet MSTP or N2 FC Bus 0 6 mm 22 AWG standard 3 wire twisted shielded cable recommende...

Страница 23: ...Testing Laboratories BTL Protocol Revision 7 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application...

Страница 24: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: