14-88360-03206, Rev. A
Installing the Six-way Valve to a System
1
2
3
4
5
6
Note:
Source 1 and 2 can be used for hot or cold water.
Attaching the Actuator to the Six-Way Valve
4
Valve port Description
Analog Input Control
1
Source 1 supply Controlled by the gray wire
2
Coil supply
3
Coil return
4
Source 1 return Controlled by the gray wire
5
Source 2 supply Controlled by the orange wire
6
Source 2 return Controlled by the orange wire
The diagram below illustrates the input and output flows for the 6-way valve. Use this diagram as a guide on how to
install the 6-way valve to your system.
Note:
Valve port 2 must only be used as coil supply. Valve port 3 must only be used as coil return.
Clearance Required to Install an Actuator
The diagrams below illustrate the clearance required to install an actuator to the VG1600 Valve Series.
100 mm (3 -15/16 in.)
89 mm
(3 - 1/2 in.)
75 mm
(2 - 15/16 in.)
150 mm (5 - 29/32 in.)
66 mm (2 - 19/32 in.)
114 mm
(4 - 31/64 in.)