background image

TFP620

Page 7 of 8

Care and 

Maintenance

The TYCO Model WS Specific Applica-

tion Window Sprinklers  must be main-

tained and serviced in accordance with 

this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

systems from the proper authorities 

and notify all personnel who may be 

affected by this action.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers - before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. Refer to the  Instal-

lation section for additional information.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

recognized by the Approval agency 

(e.g., NFPA 25), in addition to the stan-

dards of any authorities having jurisdic-

tion. Contact the installing contractor 

or product manufacturer regarding any 

questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

INSTALLATION NOTE:

NO MAXIMUM

ARROW POINTED

MODEL WS SPRINKLER

GLAZING FOR CLARITY

SHOWN ON ONE SIDE OF

TOWARD GLAZING

3" (76,2 mm)

± 1" (25,4 mm)

4" (101,6 mm)

HEIGHT

TO 12" (304,8 mm)

POSITION SPRINKLER

EXPOSED

HEIGHT

GLAZING

13'-0"

MAXIMUM

(3,96 m)

TO GLAZING AND

DEFLECTOR FLOW

ALIGNED PARALLEL

WITH FRAME ARMS

NON-OPERABLE
GLASS WINDOW

FLOW DIRECTION

DEFLECTOR

INDICATED ON

SPRINKLER

MAXIMUM

NO

FRAME

WINDOW

DISTANCE

STRUCTURE

CENTERLINE

OF SPRINKLER

WATERWAY

BUILDING

FOR GLASS TYPES

OTHER THAN FIRELITE

PLUS WS CERAMIC GLASS

BY TGP, ALL COMBUSTIBLE

MATERIALS SHALL BE

KEPT 2" (50,8 mm) MINIMUM

FROM SPRINKLERED FACE

OF GLAZING. THIS MAY BE

DONE THROUGH USE OF

MINIMUM 3'-0" (0,9 m)

PONY WALL

FIGURE 3D 

MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER 

TYPICAL INSTALLATION

Содержание tyco WS

Страница 1: ...nklers is based on their fast response thermal sensitivity and on their specially designed deflectors that ensure that the spray pattern wets the entire surface of the window Based on successful testing the Model WS Window Sprinklers can be used as interior protection of windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Mat...

Страница 2: ...ulb allowing the sprinkler to activate and water to flow Temperature 1 5 8 DIA 41 3 mm NPT WATERWAY OF SPRINKLER CENTERLINE NOMINAL MAKE IN 7 16 11 1 mm Screw Deflector 6 THREAD 1 2 RELIEF Components Button Sealing Compression Frame Assembly 1 5 4 2 3 Bulb 54 0 mm FLATS WRENCH 2 1 8 WINDOW 20 6 mm 13 16 TOWARDS DEFLECTOR ORIENT INDICATED TOP DEFLECTOR OF SPRINKLER SPRINKLER FRAME ARMS 1 2 3 4 5 6 ...

Страница 3: ...parated by a baffle or mullion of sufficient depth to act as a baffle A mullion will act as a baffle when in the case of the Pendent Vertical Side wall the mullion extends to the back of the sprinkler deflector and in the case of the Horizontal Sidewall the mullion extends to the sprinkler wrench flat Refer to Figures 3B 1 and 3B 2 Minimum Distance from Standard Sprinklers 6 ft 1 83 m unless separ...

Страница 4: ...or sprinkler spacing less than 6 ft 1 83 m Maximum Pressure per Sprinkler Horizontal Sidewall 70 psi 4 83 bar The 70 psi is only for cold solder purposes If there is a baffle or a mullion of sufficient depth to act as a baffle separating the sprinklers the maximum pressure is 175 psi 12 07 bar Vertical Sidewall 175 psi 12 07 bar When acceptable to the Authority Having Jurisdiction the Model WS Spe...

Страница 5: ...indow Sprinklers is 6 0 baffle by a baffle or mullion of MULLION MINIMUM SPRINKLER MODEL WS OR VERTICAL HORIZONTAL 0 4 101 6 mm MINIMUM 4 0 1 22 m MAXIMUM 8 0 2 44 m MAXIMUM when intermediate horizontal Window Sprinklers are NOT listed to protect windows mullions are present MULLION WS SPRINKLER VERTICAL MODEL INTERMEDIATE MULLION HORIZONTAL OR FIGURE 3B B 1 TO B 3 WINDOW MULLIONS AND BUTT JOINTS ...

Страница 6: ...sition with the center line of the sprinkler per pendicular to the glass surface Orient the sprinkler so that the word Top indicated on the sprinkler deflector is facing the top of window frame Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 With reference to Figures 1 or 2 apply End A of W Type 20 Sprinkler Wrench only Figur...

Страница 7: ...m its bulb Refer to the Instal lation section for additional information The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards recognized by the Approval agency e g NFPA 25 in addition to the stan dards of any authorities having jurisdic tion Contact the installing co...

Страница 8: ...fy Model WS Specific Application Window Sprinkler TY3488 Pendent Vertical Sidewall with specify tem perature rating specify finish and P N specify 155 F 68 C Natural Brass 50 304 1 155 Signal White RAL9003 Polyester 50 304 4 155 Jet Black RAL9005 Polyester 50 304 5 155 Chrome Plated 50 304 9 155 200 F 93 C Natural Brass 50 304 1 200 Signal White RAL9003 Polyester 50 304 4 200 Jet Black RAL9005 Pol...

Отзывы: