Design Criteria

The TYCO Model WS Specific Appli-

cation Window Sprinklers are UL and 

C-UL Listed and NYC Approved (MEA 

335-01-E) for use as “Specific Appli-

cation Window Sprinkler” and as open 

sprinklers for “Outside” use.
These sprinklers are also recognized by 

Underwriters Laboratories of Canada 

(ULC), and the Ontario Building Code 

for use in the Province of Ontario, 

Canada as providing a two-hour equiv-

alency for a fire separation assembly 

when installed in accordance with this 

code.

Area of Use

When acceptable to the Authority 

Having Jurisdiction and unless modi-

fied by a local jurisdictional standard or 

code mentioned previously, the TYCO 

Model WS Window Sprinklers may be 

used in either a sprinklered or unsprin-

klered building to protect non-operable 

window openings that are part of a fire 

separation provided:
•  in an interior fire separation, the win-

dow sprinklers are installed on both 

sides of the window in the fire sepa-

ration (Figure 3A-1),

•  in jurisdictions where exterior spatial 

separation (that is, separation from 

adjacent space) is defined as pro-

tecting an adjacent building from a 

fire in your building, window sprin-

klers are installed on the interior side 

of the building (Figure 3A-2), or

•  in jurisdictions where exterior spatial 

separation is defined as protecting 

your building from a fire in an adja-

cent building (that is, exposure pro-

tection), open window sprinklers are 

installed on the exterior side of the 

building (Figure 3A-3).

System Protection Type

•  Interior: Wet Systems
•  Outside Exposure: Deluge 

Glass Type

The following types and thicknesses of 

glass are recognized for use with TYCO 

Model WS Window Sprinklers:
•  Non-operable, heat-strengthened, 

tempered, single-glazed (single 

pane), not less than 1/4 in. (6 mm) 

thick;

•  Non-operable, heat-strengthened, 

tempered, double-glazed (double 

pane or insulated), not less than 1/4 

in. (6 mm) thick;

•  Non-operable, UL Classified and 

labeled FireLite Plus WS ceramic 

glass by Technical Glass Products 

(TGP), not less than 5/16 in. (8 mm) 

thick; or,

NOTE: Refer to FireLite Plus WS 

ceramic glass technical data sheet for 

other classification limitations at www.

fireglass.com.

•  Non-operable, stronger glass win-

dow assemblies, not less than 1/4 

in. (6 mm) thick.

Type of Window Frame/Mullion

Non-combustible Frame with a stan-

dard EPDM rubber gasket seal
Vertical joints of glass panes must be 

connected by butt-joints using a sili-

cone sealant between the individual 

panes or by Noncombustible Mullions.
(Refer to Figures 3B-1 and 3B-2)

Maximum Length of 

Window Assembly

Unlimited

Maximum Height of 

Window Assembly

13 ft (3,96 m)
(Refer to Figures 3C and 3D)

Maximum Distance Between 

Window Sprinklers

8 ft (2,44 m)
(Refer to Figures 3B-1 and 3B-2)

Minimum Distance Between 

Window Sprinklers

6 ft (1,83 m) unless separated by a 

baffle or mullion of sufficient depth to 

act as a baffle.
A mullion will act as a baffle, when in 

the case of the Pendent Vertical Side-

wall, the mullion extends to the back of 

the sprinkler deflector, and in the case 

of the Horizontal Sidewall, the mullion 

extends to the sprinkler wrench flat.
(Refer to Figures 3B-1 and  3B-2)

Minimum Distance from 

Standard Sprinklers

6 ft (1,83 m) unless separated by a 

baffle 

Sprinkler Location

•  Mullioned Glazing Assemblies: 

Locate window sprinklers within 

each mullioned glazing segment. 

Refer to Figure 3B-1.

•  Butt-Jointed Glazing Assemblies: 

Locate window sprinklers on maxi-

mum 8 ft (2,44 m) centers. Refer to 

Figure 3B-2.

Maximum Distance from 

Vertical Mullion

4 ft (1,22 m)
(Refer to Figure 3B-1)

Minimum Distance from 

Vertical Mullions

4 in. (101,6 mm)
(Refer to Figure 3B-1)

Intermediate Horizontal Mullions

Intermediate Horizontal Mullions were 

not tested with the Model WS Window 

Sprinklers. Their use is outside the 

scope of the “Specific Application” 

Listing for the window sprinklers. Refer 

to Figure 3B-3.

Deflector Location

Sprinkler Deflectors must be located as 

described below in order to ensure that 

the entire surface of the glass window 

is covered. Sprinkler Deflectors are 

positioned with respect to the window 

frame, not the ceiling.
•  Horizontal Sidewall: Locate within 

the outside edge of the window 

frame from 1/2 in. to 4 in. (12,7 mm to 

101,6 mm) away from the glass and  

2 in. ± 1 in. (50,8 mm ± 25,4 mm) 

down from the top of  the exposed 

glass. Refer to Figure 3C.

•  Pendent Vertical Sidewall: Locate 4 

in. to 12 in. (101,6 mm to 304,8 mm) 

from the face of the glass and 3 in. 

± 1 in. (76,2 mm ± 25,4 mm) down 

from the top of exposed glass. Refer 

to Figure 3D.

Minimum Clearance from Face of 

Glass to Combustible Materials

For glass types other than FireLite Plus 

WS ceramic glass by TGP, all com-

bustible materials shall be kept 2 in. 

(50,8 mm) from the front face of the 

glass. This can be accomplished by a 

minimum 36 in. (914,4 mm) pony wall or 

other method acceptable to the author-

ity having jurisdiction.

Escutcheon Assemblies

The Model WS Window Sprinklers 

can be used with any metallic flush or 

extended escutcheons, provided the 

dimensions from the sprinkler deflector 

to the window frame and glass surface 

as specified in this data sheet are main-

tained. These sprinklers are not listed 

for recessed applications.

Recommended Hydraulic 

Requirements

The authority having jurisdiction should 

be consulted to determine the hydraulic 

requirements for each installation.

Interior Protection Sprinklered 

Building

Identify which compartmented area 

has the most hydraulically demand-

ing window sprinklers. Calculate up to 

the most demanding 46.5 linear feet of 

Model WS Window Sprinklers on one 

side of the glazing. The 46.5 linear feet 

(14,2 linear meters) is based upon 1.2 

x the square root of the system area 

of operation, when the system area of 

operation is 1500 sq.-ft. in accordance 

with NFPA 13 Light/Ordinary Hazard 

density curves.

Содержание tyco WS

Страница 1: ...nklers is based on their fast response thermal sensitivity and on their specially designed deflectors that ensure that the spray pattern wets the entire surface of the window Based on successful testing the Model WS Window Sprinklers can be used as interior protection of windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Mat...

Страница 2: ...ulb allowing the sprinkler to activate and water to flow Temperature 1 5 8 DIA 41 3 mm NPT WATERWAY OF SPRINKLER CENTERLINE NOMINAL MAKE IN 7 16 11 1 mm Screw Deflector 6 THREAD 1 2 RELIEF Components Button Sealing Compression Frame Assembly 1 5 4 2 3 Bulb 54 0 mm FLATS WRENCH 2 1 8 WINDOW 20 6 mm 13 16 TOWARDS DEFLECTOR ORIENT INDICATED TOP DEFLECTOR OF SPRINKLER SPRINKLER FRAME ARMS 1 2 3 4 5 6 ...

Страница 3: ...parated by a baffle or mullion of sufficient depth to act as a baffle A mullion will act as a baffle when in the case of the Pendent Vertical Side wall the mullion extends to the back of the sprinkler deflector and in the case of the Horizontal Sidewall the mullion extends to the sprinkler wrench flat Refer to Figures 3B 1 and 3B 2 Minimum Distance from Standard Sprinklers 6 ft 1 83 m unless separ...

Страница 4: ...or sprinkler spacing less than 6 ft 1 83 m Maximum Pressure per Sprinkler Horizontal Sidewall 70 psi 4 83 bar The 70 psi is only for cold solder purposes If there is a baffle or a mullion of sufficient depth to act as a baffle separating the sprinklers the maximum pressure is 175 psi 12 07 bar Vertical Sidewall 175 psi 12 07 bar When acceptable to the Authority Having Jurisdiction the Model WS Spe...

Страница 5: ...indow Sprinklers is 6 0 baffle by a baffle or mullion of MULLION MINIMUM SPRINKLER MODEL WS OR VERTICAL HORIZONTAL 0 4 101 6 mm MINIMUM 4 0 1 22 m MAXIMUM 8 0 2 44 m MAXIMUM when intermediate horizontal Window Sprinklers are NOT listed to protect windows mullions are present MULLION WS SPRINKLER VERTICAL MODEL INTERMEDIATE MULLION HORIZONTAL OR FIGURE 3B B 1 TO B 3 WINDOW MULLIONS AND BUTT JOINTS ...

Страница 6: ...sition with the center line of the sprinkler per pendicular to the glass surface Orient the sprinkler so that the word Top indicated on the sprinkler deflector is facing the top of window frame Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 With reference to Figures 1 or 2 apply End A of W Type 20 Sprinkler Wrench only Figur...

Страница 7: ...m its bulb Refer to the Instal lation section for additional information The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards recognized by the Approval agency e g NFPA 25 in addition to the stan dards of any authorities having jurisdic tion Contact the installing co...

Страница 8: ...fy Model WS Specific Application Window Sprinkler TY3488 Pendent Vertical Sidewall with specify tem perature rating specify finish and P N specify 155 F 68 C Natural Brass 50 304 1 155 Signal White RAL9003 Polyester 50 304 4 155 Jet Black RAL9005 Polyester 50 304 5 155 Chrome Plated 50 304 9 155 200 F 93 C Natural Brass 50 304 1 200 Signal White RAL9003 Polyester 50 304 4 200 Jet Black RAL9005 Pol...

Отзывы: