background image

Series RFII-MRI — 5.6 K-factor

Non-Magnetic Concealed Pendent Sprinklers

Quick & Standard Response, Standard Coverage

Page 1 of 4 

JULY 2020 

TFP182

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Series RFII-MRI 5.6 K-fac-

tor, Non-Magnetic Concealed Pendent 

Sprinklers Quick Response (3 mm bulb) 

and Standard Response (5 mm bulb), 

are decorative sprinklers featuring a 

flat cover plate designed to conceal 

the sprinkler. 
The RFII-MRI Sprinkler is intended for 

use inside of the MRI environment, that 

is, in the MR system room and close to 

the scanner unit. However, this sprin-

kler is not intended for use directly 

inside of the MR system, such as within 

the bore of the scanner unit. During 

the intended use, the RFII-MRI Sprin-

kler must be mounted at the ceiling to 

the fixed fire protection piping system 

of the MR system room. Under these 

conditions, per non-clinical testing to 

ASTM F2052-15, the RFII-MRI Sprin-

kler was found to be acceptable for use 

under a static magnetic field of 7-Tesla 

or less. Standard MRI apparatus are 

typically in the 3 Tesla range.
Each sprinkler is comprised of sepa-

rately ordered components: a 

Cover 

Plate/Retainer Assembly and a Sprin-

kler/Support Cup Assembly. 

The sep-

arable, two-piece assembly design 

provides the following benefits:
•  Allows installation of the sprinklers 

and pressure testing of the fire pro-

tection system prior to installation of 

a suspended ceiling or application of 

the finish coating to a fixed ceiling.

•  Permits the removal of suspended 

ceiling panels for access to building 

service equipment without having 

to first shut down the fire protection 

system and remove sprinklers.

•  Provides for 1/2 in. (12,7 mm) of ver-

tical adjustment to allow a measure 

of flexibility in determining the length 

of fixed piping to cut for the sprinkler 

drops.

The RFII-MRI Sprinklers are shipped 

with a Disposable Protective  Cap. The 

Protective Cap is temporarily removed 

during installation and replaced to help 

protect the sprinkler during ceiling 

installation or finish. The tip of the Pro-

tective Cap can be used to mark the 

center of the ceiling hole into plaster 

board or ceiling tiles by gently pushing 

the ceiling product against the Pro-

tective Cap. When ceiling installa-

tion is complete, the Protective Cap is 

removed and the Cover Plate/Retainer 

Assembly is installed.
As an option, the RFII-MRI Standard 

Response (5 mm bulb) Sprinkler can 

be fitted with a silicone Air and Dust 

Seal, see Figure 5. The Air and Dust 

Seal is intended for sensitive areas 

where it is desirable to prevent air and 

dust from the area above the ceiling to 

pass through the cover plate.

NOTICE

The RFII-MRI Sprinklers described 

herein must be installed and main-

tained in compliance with this docu-

ment and with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA), in addition to 

the standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition. 

The installing contractor or sprinkler 

manufacturer should be contacted with 

any questions.

Sprinkler 

Identification 

Number (SIN)

TY3530 — 3 mm bulb

TY3550 — 5 mm bulb