Figure 8: 2-wire smoke detector wiring
AUX2
1
PGM
3
4
-
+
2
+
-
+
-
Callout
Description
1
2200 Ω end-of-line resistor
The following table lists compatible 2-wire smoke detectors:
Table 8: 2-wire smoke detectors
Detector name
FSA-210X
FSA-210XLST
FSA-210XRST
C2WTA-BA (ULC)
FSA-210XT
FSA-210XR
FSA-210XLRST
2W-B (UL)
FSA-210XS
FSA-210XRT
C2W-BA (ULC)
2WT-B (UL)
FSA-210XST
FSA-210XRS
C2WT-BA (ULC)
2WTA-B (UL)
Note:
For the DSC FS210 series, X in the detector name represents A for ULC and B for UL
listed models.
Note:
If you use System Sensor detectors on a 2-wire loop, do not combine UL and ULC
detectors. For more information, refer to the System Sensor installation manual.
Note:
Do not connect accessories, such as a PRM-2W or any other polarity reversal module, to
2-wire smoke detectors.
The UL compatibility ID for the FSA-210B series is FS200, and for the System Sensor models is A.
Note:
For ULC listed installations, use FSA-210A series detectors or FSA-410A series detectors.
Note:
You must calculate and test the current draw.
Table 9: 2-wire smoke detector initiation circuit
Item
Specification
Class, supervised, power limited
Class B IDC. 2-wire smoke detector interface
Compatibility identifier
PG9HRDW8
DC output voltage
10.0 VDC to 13.8 VDC
Detector load
2 mA maximum
SEOL
2200 Ω
Maximum capacitance
10 μF
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual