Figure 7: Relay output wiring
Callout
Description
1
AUX terminals
2
PGM terminals
3
Relay (RM-1 and RM-2)
4
To normally open connection
5
To normally closed connection
6
To COM terminal
Wiring a fire zone to the PGM2 configured as a 2-wire loop
When you wire a 2-wire smoke detector, observe the following guidelines:
•
You must connect 2-wire smoke detectors in parallel.
•
You can wire a maximum of 18 smoke detectors on a 2-wire loop.
•
Do not exceed a wire resistance of 24 Ω across the entire loop.
•
Do not use smoke detectors from different manufacturers on the same circuit as their
operation may be impaired. Refer to the smoke detector installation sheet when you position
detectors.
•
For UL and ULC residential fire applications, use only the AUX2 output to provide power to
smoke and CO detectors.
If you program PGM2 for use with a 2-wire smoke detector, you must wire it according to the
following figure:
17
PG8HRDW8 and PG9HRDW8 IQ Hardwire PowerG Wired to Wireless Converter Installation Manual