background image

TFP312

Page 5 of 6

Care and 

Maintenance

TYCO Model ESFR-25 Early Suppres-

sion, Fast Response 25.2K Pendent 

Sprinklers must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and notify all personnel who may be 

affected by this action.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprin-

kler that has a cracked bulb or that has 

lost liquid from its bulb. See Installation 

section for additional information.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associ-

ation, such as NFPA 25, in addition to 

the standards of any authorities having 

jurisdiction. Contact the installing con-

tractor or product manufacturer with 

any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and part number 

(P/N).

Sprinkler Assemblies

Specify: Model ESFR-25 Early Sup-

pression, Fast Response 25.2K 

Pendent Sprinklers (TY9226), (specify 

temperature rating), with Natural Brass 

finish, P/N (specify):

165°F (74°C) . . . . . . . . . . . . . . . . . . 58-441-1-165  

212°F (100°C) . . . . . . . . . . . . . . . . . 58-441-1-214

Special Order 

Sprinkler Assemblies with 

ISO 7-1 Thread Connection

Specify: Model ESFR-25, Early Sup-

pression, Fast Response 25.2K 

Pendent Sprinklers (TY9226) with 

ISO 7-1 thread connection, (specify 

temperature rating), with Natural Brass 

finish, P/N (specify):

165°F (74°C) . . . . . . . . . . . . . . . . . . 58-442-1-165  

212°F (100°C) . . . . . . . . . . . . . . . . . 58-442-1-214

Sprinkler Wrench

Specify: W-Type 1 Sprinkler Wrench, 

P/N 56-872-1-025

Installation

TYCO Model ESFR-25 Early Suppres-

sion, Fast Response 25.2K Pendent 

Sprinklers must be installed in accor-

dance with this section.

General Instructions

Damage to the fusible Link Assem-

bly during installation can be avoided 

by handling the sprinkler by the frame 

arms only and by using the appropri-

ate sprinkler wrench. Do not apply 

pressure to the fusible Link Assembly. 

Failure to do so can lead to an unstable 

link assembly and premature activation 

of the sprinkler. Damaged sprinklers 

must be replaced.
A leak-tight 1 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 20 to 30 

lb-ft (26,8 to 40,2 N∙m). Higher levels 

of torque can distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.

Note:

 Install the Model ESFR-25 Pendent 

Sprinkler in the pendent position (see Figure 

2).

Step 1.

 With pipe thread sealant 

applied, hand-tighten the sprinkler into 

the sprinkler fitting. Do not apply pres-

sure to the Link Assembly, and handle 

the Model ESFR-25 Pendent Sprinkler 

only by the Frame arms.

Step 2.

 Wrench-tighten the Model 

ESFR-25 Pendent Sprinkler using only 

the W-Type 1 Sprinkler Wrench (see 

Figure 2) and by fully engaging (seating) 

the wrench on the sprinkler wrench 

flats (see Figure 1).

Step 3.

 After installation, inspect the 

Link Assembly of each Model ESFR-25 

Pendent Sprinkler for damage. In par-

ticular, verify that the Link Assembly 

and Hook are positioned as illustrated 

in Figure 1, and that the Link Assem-

bly is not bent, creased, or forced out 

of normal position in any way. Replace 

damaged sprinklers.

"FITTING SIDE"

TOWARDS SPRINKLER

FITTING

WRENCH

RECESS

FIGURE 2 

W-TYPE 1 

SPRINKLER WRENCH