TFP312

Page 3 of 6

In some cases, the installation stan-

dards permit a greater coverage area.

Minimum Coverage Area

64 ft² (5,8 m²) per  

NFPA 13 / FM Global 2-0

Maximum Spacing

12 ft (3,7 m) for building heights up to 

30 ft (9,1 m)
10 ft (3,1 m) for building heights greater 

than 30 ft (9,1 m).
In some cases, installation standards 

permit a greater spacing.

Minimum Spacing

8 ft (2,4 m)

Minimum Clearance to Commodity

36 in. (914 mm)

NFPA 

Deflector-to-Ceiling Distance

6 in. to 18 in. (152 mm to 457 mm)

FM Global 

Centerline of Thermal Sensing 

Element-to-Ceiling Distance

Refer to FM Global 2-0 for Storage 

Sprinklers.

Specific 

Application 

Listing (UL)

TYCO Model ESFR-25 Pendent Sprin-

klers are listed by Underwriters Labo-

ratories (UL) for Specific Applications 

with a ceiling height greater than 45 

ft (13,7 m) up to and including 48 ft  

(14,6 m), and a storage arrange-

ment up to and including 43 ft (13,1 

m). See Table C for guidelines for the 

TYCO Model ESFR-25 Pendent Sprin-

kler Specific Applications Listing (UL) 

Design Criteria. See Table C for addi-

tional information.

Storage Type

NFPA

FM Global

Sprinkler Type

ESFR

Storage

Response Type

FR

QR

System Type

Wet

Wet

Temperature Rating ˚F (˚C)

165˚F (74˚C)  

212˚F (100˚C)

165˚F (74˚C)  

212˚F (100˚C)

Open Frame (i.e., no solid shelves), Single, Double, Multiple-

Row, or Portable Rack Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM Global 

2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM Global 

2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13

Refer to FM Global 

2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13

Refer to FM Global 

2-0 and 8-3

Roll Paper Storage 

(Refer to the Standard)

Refer to NFPA 13

Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage 

(Refer to the Standard)

Refer to NFPA 30

Refer to FM Global 7-29

Aerosol Storage 

(Refer to the Standard)

Refer to NFPA 30B

Refer to FM Global 7-31

Automotive Components in Portable Racks 

(Control mode only; refer to the Standard)

Refer to NFPA 13

N/A

N/A – Not Applicable

TABLE B 

MODEL ESFR-25 PENDENT SPRINKLER 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW