TFP312

Page 2 of 6

Operation

The fusible link assembly is com-

prised of two link halves that are joined 

together by a thin layer of solder. When 

the rated temperature is reached, the 

solder melts and the two link halves 

separate, activating the sprinkler and 

flowing water.

Design 

Criteria

The following general guidelines pro-

vided for the TYCO Model ESFR-25 

Pendent Sprinklers can be used for a 

quick reference.
The National Fire Protection Associa-

tion (NFPA) and FM Global (FM Approv-

als) provide installation standards that 

must be used to properly design an 

automatic sprinkler system utilizing 

Early Suppression, Fast Response 

(ESFR) Sprinklers. The guidelines pro-

vided by NFPA and FM Global may 

differ. Consequently, the appropri-

ate standard must be used for a given 

installation.
General guidelines are not intended to 

provide complete installation criteria. 

In all cases, the appropriate NFPA or 

FM Global installation standard must 

be referenced to ensure applicabil-

ity and to obtain complete installation 

guidelines. See Table B for additional 

information.

In addition to this technical data sheet, 

the following data sheets describe 

other TYCO ESFR Sprinklers:

• 

TFP313 

Model ESFR-22 (TY8226) 

 

K=22.4 Pendent Sprinkler

• 

TFP315 

Model ESFR-17 (TY7226) 

 

K=16.8 Pendent Sprinkler

• 

TFP316 

Model ESFR-17 (TY7126) 

 

K=16.8 Upright Sprinkler

• 

TFP317 

Model ESFR-17 (TY7223) 

 

K=16.8 Pendent Sprinkler

• 

TFP318 

Model ESFR-1 (TY6226) 

 

K=14.0 Pendent Sprinkler

• 

TFP319 

Model ESFR-14 (TY6236) 

 

K=14.0 Pendent Sprinkler

• 

TFP320

 

Model ESFR-17 (TY7229) 

 

K=16.8 Pendent Sprinkler

Roof Construction

Unobstructed or obstructed construc-

tion, such as smooth ceiling, bar joists, 

beam and girder. Where the depths of 

the solid structural members, as in 

beams and stem, exceed 12 in. (302 

mm), install ESFR Sprinklers in each 

channel formed by the structural 

members.

Ceiling Slope

Maximum 2 in. rise for 12 in. run (16.7%)

Maximum Coverage Area

100 ft² (9,3 m²)

Item

Description

Sprinkler Identification Number (SIN)

TY9226

K-factor, gpm/psi

½

 (Lpm/bar

½

)

25.2 gpm/psi

½

 (362,9 Lpm/bar

½

)

Temperature Rating ˚F (˚C)

165˚F (74˚C)  

212˚F (100˚C)

Thread Size

1 in. NPT or ISO 7-R 1

Sprinkler Orientation

Pendent

Maximum Working Pressure, psi (bar)

175 psi (12,1 bar)

Components:

2

3

6

4

5

9

8

7

1

1" NPT

WRENCH

FLATS

3-13/16"

(96,8 mm)

9/16"

(14,3 mm)

NOMINAL

MAKE-IN

2" (50,8 mm)

1-13/16"

(46,0 mm)

THERMAL

SENSING

ELEMENT

TEMPERATURE

RATING

- Hook

4

-

9

-

7
8 -

5
6

-
- Link Assembly

Ejection Spring

Sealing

Assembly

Button

Strut

-

2
3 -

1 -

Compression

Screw

Deflector

Frame

FIGURE 1  

MODEL ESFR-25 PENDENT SPRINKLER, 25.2K 

EARLY SUPPRESSION, FAST RESPONSE

TABLE A 

MODEL ESFR-25 PENDENT SPRINKLER 

TECHNICAL DATA