Model ESFR-25 

25.2 K-factor Pendent Sprinkler 

Early Suppression, Fast Response

Page 1 of 6 

MARCH 2020 

TFP312

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

to obtain complete installation guide-

lines. The general guidelines in this 

data sheet are not intended to provide 

complete installation criteria.

Sprinkler 

Identification 

Number (SIN)

See Table A for sprinkler identification 

number.

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved 

VdS Approved 

NYC Approved under MEA 356-01-E 

LPCB Certified (Cert. Nos. 094b and 007l) 

CE Certified (Certificate of Conformity 

1725-CPR-F0010)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Compression Screw . . . . . . . . . .  Stainless Steel 

Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL 

Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL 

Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel 

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Sealing Assembly  . . Beryllium Nickel w/TEFLON 

Ejection Spring . . . . . . . . . . . . . . . . . .  INCONEL

Additional Technical Data

See Table A for additional technical 

data.

substantially lower-end head pres-

sures, as compared to ESFR Sprinklers 

having nominal K-factors of 14.0 and 

16.8. This feature offers flexibility when 

sizing system piping, as well as possi-

bly reducing or eliminating the need for 

a system fire pump.
Also, Model ESFR-25 Sprinklers permit 

use of a maximum deflector-to-ceiling 

distance of 18 in. (460 mm) versus 14 

in. (356 mm). Additionally, a storage 

arrangement of 40 ft (12,2 m) with a 

ceiling height of 45 ft (13,7 m) does not 

require in-rack sprinklers as do other 

ESFR Sprinklers having nominal K-fac-

tors of 14.0 and 16.8.
The Model ESFR-25 Sprinklers are 

listed by Underwriters Laboratories 

(UL) for specific applications with 

a maximum storage height of 43 ft  

(13,1 m) with a maximum ceiling height 

of 48 ft (14,6 m) without the require-

ment for in-rack sprinklers. Refer to the 

Specific Application Listing (UL) for the 

design criteria.
Applications for the TYCO ESFR Sprin-

klers are expanding beyond currently 

recognized installation standards. For 

information on research fire tests, such 

as with flammable liquids and aerosols, 

that may be acceptable to an author-

ity having jurisdiction, contact Techni-

cal Services.

NOTICE

The Model ESFR-25 Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the National Fire Pro-

tection Association (NFPA), in addition 

to the standards of any authorities 

having jurisdiction, such as FM Global. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
In all cases, the appropriate NFPA or 

FM Global installation standard, or 

other applicable standard, must be 

referenced to ensure applicability and 

General 

Description

TYCO Model ESFR-25 Pendent Sprin-

klers are Early Suppression, Fast 

Response (ESFR) sprinklers having a 

nominal K-factor of 25.2 (see Figure 1). 

They are suppression-mode sprinklers 

that are especially advantageous as a 

means of eliminating the use of in-rack 

sprinklers when protecting high-piled 

storage.
The Model ESFR-25 Sprinklers are pri-

marily used for ceiling-only sprinkler 

protection of, but not limited to, the fol-

lowing storage applications:
•  most encapsulated or non-encap-

sulated common materials including 

cartoned, unexpanded plastics

•  uncartoned (exposed) expanded 

plastics in accordance with NFPA 13 

and FM Global standards

•  some storage arrangements of rub-

ber tires, roll paper, flammable liq-

uids, aerosols, and automotive 

components

For more specific criteria, see Table 

B as well as the applicable design 

standard.
The Model ESFR-25 Pendent Sprin-

klers provide the system designer 

with hydraulic and sprinkler place-

ment options not presently available to 

the traditional ESFR sprinklers having 

nominal K-factors of 14.0 and 16.8. In 

particular, the Model ESFR-25 Sprin-

kler has been designed to operate at 