TFP298

Page 3 of 6

Series EC-5 Recessed 

Sidewall Sprinkler

The Series EC-5 Recessed Sidewall 

Sprinklers must be installed in accor-

dance with the following instructions.

Step A.

 Horizontal sidewall sprinklers 

are to be installed with their center-

line perpendicular to the back wall and 

parallel to the ceiling. The word “TOP” 

on the deflector is to face towards the 

ceiling.

Step B.

 After installing the Style 50 

sprinkler threads and with pipe thread 

sealant applied to the pipe threads, 

hand tighten the sprinkler into the 

sprinkler fitting.

Step C.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

7 Recessed Sprinkler Wrench (Ref. 

Figure 4). With reference to Figure 

1, the W-Type 7 Recessed Sprinkler 

Wrench is to be applied to the sprin-

kler wrench flats.

Step D.

 After the wall has been 

installed or the finish coat has been 

applied, slide on the Style 50 Closure 

over the Series EC-5 Sprinkler and 

push the Closure over the Mounting 

Plate until its flange comes in contact 

with the wall.

Care and 

Maintenance

The Series EC-5 Sprinklers must be 

maintained and serviced in accordance 

with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Absence of an escutcheon, which is 

used to cover a clearance hole, may 

delay the time to sprinkler operation in 

a fire situation.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.

Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprin-

kler that has a cracked bulb or that has 

lost liquid from its bulb. (Ref. Installa-

tion Section).
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards of 

the National Fire Protection Association 

(e.g., NFPA 25), in addition to the stan-

dards of any other authorities having 

jurisdiction. The installing contractor or 

sprinkler manufacturer should be con-

tacted relative to any questions.
It is recommended that automatic 

sprinkler systems be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national code.

K

TYPE

TEMP. 

RATING

BULB 

LIQUID

SPRINKLER FINISH

NATURAL 

BRASS

CHROME 

PLATED

POLYESTER

b,c

5.6 

1/2 in. 

NPT

EC-HSW 

(TY3302)

135°F (57°C)

Orange

1, 2, 4

155°F (68°C)

Red

1, 2, 3, 4

200°F (93°C)

Green

1, 2, 4

5.6 

1/2 in. 

NPT

RECESSED 

EC-HSW

a

 

(TY3302)

135°F (57°C)

Orange

1, 2, 4

155°F (68°C)

Red

1, 2, 3, 4

200°F (93°C)

Green

1, 2, 4

NOTE:

1.  UL Listed per Table B
2.  C-UL Listed per Table B
3.  FM Approved per Table C
4.  Approved by the City of New York under MEA 113-04-E
a.  Installed with Style 50 Recessed Escutcheon
b.  Frame and deflector only
c.  Sprinkler is available in Polyester color finishes as indicated in Table D

WRENCH RECESS

(END "A" USED

FOR TY3302)

WRENCH

RECESS

PUSH WRENCH

IN TO ENSURE

ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

FIGURE 3 

W-TYPE 6 SPRINKLER 

WRENCH

FIGURE 4 

W-TYPE 7 RECESSED  

SPRINKLER WRENCH

TABLE A 

LABORATORY LISTINGS AND APPROVALS

(REFER TO THE DESIGN CRITERIA SECTION)

Содержание tyco EC-5 Series

Страница 1: ...ide wall position The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut NOTICE The Series EC 5 Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the stan dards of any other ...

Страница 2: ...ar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figures 1 the W Type 6 Sprinkler Wrench is to be ...

Страница 3: ...Sprinklers that have been exposed to corrosive products of combustion but have not operated should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like mu...

Страница 4: ...f Figures 1 and 2 4 Minimum spacing is for lateral distance between sprinklers located along a single wall Otherwise adjacent sprinklers i e sidewall sprinklers on an adjacent wall on an opposite wall or pendent sprinklers must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized 5 6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER TY...

Страница 5: ...oating P N specify from Table D Recessed Escutcheon Specify Style 50 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE RAL9010 1 POLYESTER 4 SIGNAL WHITE RAL9003 POLYESTER 9 CHROME PLATE...

Страница 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Отзывы: