Installation

The Series EC-5 Sprinklers must 

be installed in accordance with this 

section.
Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm).
A leak tight 1/2 in. NPT sprinkler joint 

should be obtained with a torque of 7 to 

14 lb-ft (9,5 to 19,0 N

·

m). A maximum 

of 21 lb-ft (28,5 N

·

m) of torque may be 

used to install sprinklers with 1/2 NPT 

connections. Higher levels of torque 

may distort the sprinkler inlet and 

cause leakage or impairment of the 

sprinkler.
Do not attempt to make-up for insuf-

ficient adjustment in the escutcheon 

plate by under- or over-tightening the 

sprinkler. Readjust the position of the 

sprinkler fitting to suit.

Series EC-5 Sidewall Sprinkler

The Series EC-5 Sidewall Sprinklers 

must be installed in accordance with 

the following instructions.

Step 1.

 Horizontal sidewall sprinklers 

are to be installed with their center-

line perpendicular to the back wall and 

parallel to the ceiling. The word “TOP” 

on the deflector is to face towards the 

ceiling.

Step 2.

 With pipe thread sealant 

applied to the pipe threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

6 Sprinkler Wrench (Ref. Figure 3). With 

reference to Figures 1, the W- Type 6 

Sprinkler Wrench is to be applied to the 

sprinkler wrench flats.

**

*

*

*

**

6

1

2

3

4

5

2-1/16"

(52,4 mm)

1-5/16"

(33,3 mm)

5/16"

(7,9 mm)

SURFACE

ESCUTCHEON

PLATE SEATING

1-1/2"

(38,1 mm)

Sealing Assembly

Compression Screw

Frame

-

1

Button

Deflector

-

-

-

-

-

4

6

5

2

3

Bulb

Components

WRENCH

FLATS

7/16"

(11,1 mm)

NOMINAL

MAKE-IN

DEFLECTOR

HAT

1/2"

NPT

7/16"

(11,1 mm)

CENTERLINE

OF SPRINKLER

WATERWAY

Pipe thread

connections per

ISO 7-1 can be

provided on

special request.

Temperature

rating is indicated

on Deflector.

MOUNTING

7/8" (22,2 mm)

1-1/8" (28,6 mm)

CLOSURE

MOUNTING

SURFACE

2-1/4" DIA.

(57,2 mm)

3/16" (4,8 mm)

7/16" (11,1 mm)

3/32"

(2,4 mm)

9/16±1/8"

(14,2±3,2 mm)

FACE OF

SPRINKLER

FITTING

2-7/8" DIA.

(73,0 mm)

FIGURE 1 

SERIES EC-5 EXTENDED COVERAGE 

HORIZONTAL SIDEWALL SPRINKLERS (TY3302)

FIGURE 2 

SERIES EC-5 RECESSED EXTENDED COVERAGE HORIZONTAL 

SIDEWALL SPRINKLER ASSEMBLY WITH TWO-PIECE 

3/8 INCH TOTAL ADJUSTMENT STYLE 50 RECESSED ESCUTCHEON

Содержание tyco EC-5 Series

Страница 1: ...ide wall position The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut NOTICE The Series EC 5 Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the stan dards of any other ...

Страница 2: ...ar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figures 1 the W Type 6 Sprinkler Wrench is to be ...

Страница 3: ...Sprinklers that have been exposed to corrosive products of combustion but have not operated should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like mu...

Страница 4: ...f Figures 1 and 2 4 Minimum spacing is for lateral distance between sprinklers located along a single wall Otherwise adjacent sprinklers i e sidewall sprinklers on an adjacent wall on an opposite wall or pendent sprinklers must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized 5 6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER TY...

Страница 5: ...oating P N specify from Table D Recessed Escutcheon Specify Style 50 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE RAL9010 1 POLYESTER 4 SIGNAL WHITE RAL9003 POLYESTER 9 CHROME PLATE...

Страница 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Отзывы: