background image

TFP340

Page 4 of 6

Installation

TYCO Series ELO-231 11.2K Stan-

dard Response, Standard Coverage 

Upright and Pendent Sprinklers must 

be installed in accordance with this 

section.
A leak-tight 3/4 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 10 to  

20 lb-ft (13,4 to 26,8 N

m). A leak-

tight 1/2 in. NPT sprinkler joint should 

be obtained by applying a minimum-

to-maximum torque of 7 to 14 lb-ft  

(9,5 to 19,0 N

m). Higher levels of 

torque can distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
Do not attempt to make up for insuf-

ficient adjustment in the escutcheon 

plate by under- or over-tightening the 

sprinkler. Re-adjust the position of the 

sprinkler fitting to suit.
The Series ELO-231 Upright and 

Pendent Sprinklers must be installed 

in accordance with the following 

instructions:

Step 1.

 Pendent sprinklers are to be 

installed in the pendent position, and 

upright sprinklers are to be installed in 

the upright position.

Step 2.

 With pipe thread sealant 

applied to the pipe threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

3 Sprinkler Wrench (Ref. Figure 2), 

except that an 8 in. or 10 in. adjust-

able Crescent wrench is to be used 

for wax coated sprinklers. With refer-

ence to Figure 1, the W-Type 3 Sprin-

kler Wrench or the adjustable wrench, 

as applicable, is to be applied to the 

wrench flats.

When installing wax-coated sprinklers 

with the adjustable wrench, additional 

care needs to be exercised to prevent 

damage to the wax coating on the 

sprinkler wrench flats or frame arms 

and, consequently, exposure of bare 

metal to the corrosive environment. 

The jaws of the wrench should be 

opened sufficiently wide to pass over 

the wrench flats without damaging the 

wax coating. Before wrench-tightening 

the sprinkler, the jaws of the wrench are 

to be adjusted to just contact the sprin-

kler wrench flats. After wrench-tight-

ening the sprinkler, loosen the wrench 

jaws before removing the wrench.
After installation, the sprinkler 

wrench flats and frame arms must 

be inspected and the wax coating 

re-touched (repaired) whenever the 

coating has been damaged and bare 

metal is exposed. The wax coating on 

the wrench flats can be retouched by 

gently applying a heated 1/8 in. diam-

eter steel rod to the areas of wax that 

have been damaged, to smooth it 

back over areas where bare metal is 

exposed.

Note

Only retouching of the wax coating 

applied to the wrench flats and frame 

arms is permitted, and the retouching 

is to be performed only at the time of 

the initial sprinkler installation.
The steel rod should be heated only 

to the point at which it can begin to 

melt the wax, and appropriate precau-

tions need to be taken, when handling 

the heated rod, in order to prevent the 

installer from being burned.
If attempts to retouch the wax coating 

with complete coverage are unsuc-

cessful, additional wax can be ordered 

in the form of a wax stick (the end of 

which is color coded). Only the correct 

color-coded wax is to be used, and 

retouching of wrench flats and frame 

arms is only permitted at the time 

of initial sprinkler installation. With 

the steel rod heated as previously 

described, touch the rod to the area 

requiring additional wax with the rod 

angled downward, and then touch 

the wax stick to the rod approximately 

1/2 in. away from the area requiring 

retouching. The wax will melt and run 

down onto the sprinkler.

Care and 

Maintenance

TYCO Series ELO-231 11.2K Standard 

Response, Standard Coverage Upright 

and Pendent Sprinklers must be main-

tained and serviced in accordance with 

this section.
Before closing a fire protection system 

control valve for maintenance work on 

the fire protection system that it con-

trols, permission to shut down the 

affected fire protection system must 

be obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be  

painted, plated, coated or otherwise 

altered after leaving the factory. Modi-

fied or over-heated sprinklers must be 

replaced.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced.
Frequent visual inspections are rec-

ommended to be initially performed 

for corrosion resistant sprinklers, after 

the installation has been completed, to 

verify the long term potential integrity 

of the sprinkler coatings. Thereafter, 

annual inspections per NFPA 25 should 

suffice; however, instead of inspecting 

from the floor level, a random sampling 

of close-up visual inspections should 

be made, so as to better determine the 

exact sprinkler condition and the long 

term integrity of the corrosion resistant 

coating, as it may be affected by the 

corrosive conditions present.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associ-

ation, such as NFPA 25, in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
It is recommended that automatic 

sprinkler systems be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

"FITTING SIDE"

FITTING

TOWARDS SPRINKLER

RECESS

WRENCH

(END "A")

FIGURE 2 

W-TYPE 3 

SPRINKLER WRENCH

Отзывы: