background image

TFP340

Page 3 of 6

Storage Type

NFPA

FM Global

Sprinkler Type

Standard Coverage

Storage

Response Type

SR

SR

System Type

Wet

Wet

Temperature Rating ºF (ºC)

1

165°F (74°C)

1

212°F (100°C)

286°F (141°C)

165°F (74°C)

1

212°F (100°C)

286°F (141°C)

Open Frame (i.e., no solid shelves) Single, Double, Multiple-

Row, or Portable Rack Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13

Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13

Refer to FM 2-0 and 8-3

Roll Paper Storage 

(Refer to the Standard)

Refer to NFPA 13

Refer to FM 8-21

Flammable/Ignitable Liquid Storage 

(Refer to the Standard)

Refer to NFPA 30

Refer to FM 7-29

Aerosol Storage 

(Refer to the Standard)

Refer to NFPA 30B

Refer to FM 7-31

Automotive Components in Portable Racks 

(Control mode only; refer to the Standard)

N/A

N/A

NOTES

1.  Refer to Table C for laboratory listings and approvals.
N/A – Not Applicable

SPRINKLER 

TYPE

TEMPERATURE 

RATING

FRAME 

COLOR

SPRINKLER FINISH

NATURAL 

BRASS

CHROME 

PLATED

LEAD 

COATED

WAX 

COATED

WAX-OVER-LEAD 

COATED

UPRIGHT 

(TY5111 & TY5811)

165°F (74°C)

Unpainted

1, 2, 3, 4

1, 2, 3, 4

212°F (100°C)

White

286°F (141°C)

Blue

1, 2, 3, 4

1*, 2*, 3*, 4*

PENDENT 

(TY5211)

165°F (74°C)

Unpainted

1, 2, 3, 4

1, 2, 4

212°F (100°C)

White

286°F (141°C)

Blue

1, 2, 4

1*, 2*, 4*

NOTES

1.  UL Listed
2.  C-Ul Listed

3.  FM Approved
4.  Approved by the City of New York (NYC) under MEA 291-04-E
*  Listed/Approved for a maximum ceiling temperature of 150 °F (66 °C)

TABLE B 

SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS 

 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

TABLE C 

11.2K SERIES ELO-231 UPRIGHT & PENDENT SPRINKLERS, STANDARD RESPONSE 

LABORATORY LISTINGS AND APPROVALS