TFP340
Page 3 of 6
Storage Type
NFPA
FM Global
Sprinkler Type
Standard Coverage
Storage
Response Type
SR
SR
System Type
Wet
Wet
Temperature Rating ºF (ºC)
1
165°F (74°C)
1
212°F (100°C)
286°F (141°C)
165°F (74°C)
1
212°F (100°C)
286°F (141°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13
Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13
Refer to FM 2-0 and 8-9
Idle Pallet Storage
Refer to NFPA 13
Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage
Refer to NFPA 13
Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard)
Refer to NFPA 13
Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard)
Refer to NFPA 30
Refer to FM 7-29
Aerosol Storage
(Refer to the Standard)
Refer to NFPA 30B
Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
N/A
N/A
NOTES
1. Refer to Table C for laboratory listings and approvals.
N/A – Not Applicable
SPRINKLER
TYPE
TEMPERATURE
RATING
FRAME
COLOR
SPRINKLER FINISH
NATURAL
BRASS
CHROME
PLATED
LEAD
COATED
WAX
COATED
WAX-OVER-LEAD
COATED
UPRIGHT
(TY5111 & TY5811)
165°F (74°C)
Unpainted
1, 2, 3, 4
1, 2, 3, 4
212°F (100°C)
White
286°F (141°C)
Blue
1, 2, 3, 4
1*, 2*, 3*, 4*
PENDENT
(TY5211)
165°F (74°C)
Unpainted
1, 2, 3, 4
1, 2, 4
212°F (100°C)
White
286°F (141°C)
Blue
1, 2, 4
1*, 2*, 4*
NOTES
1. UL Listed
2. C-Ul Listed
3. FM Approved
4. Approved by the City of New York (NYC) under MEA 291-04-E
* Listed/Approved for a maximum ceiling temperature of 150 °F (66 °C)
TABLE B
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TABLE C
11.2K SERIES ELO-231 UPRIGHT & PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS