Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
Control Setup
General
Control Mode
Auto
Auto, Cooling, or Heating
Unit Enable
Enable
Enable or Shutdown
Fan Mode*
Smart
Not Used, On, Auto, Smart
* Fan coil units only
Max Setpoint Offset
3
0 to 20 degrees (F or C based on Units
setting under Display Settings menu)
Fan On Delay*
30 seconds
0 to 120 seconds
* Fan coil units only
Fan Off Delay*
30 seconds
0 to 120 seconds
* Fan coil units only
Frost Protection
Yes
Yes or No
Reset PID Tuning*
No
Yes or No
Auto PID Tuning Enable
Yes
Yes or No
Dehumidification Enable*
No
Yes or No
* Fan coil units with humidity sensor
Aux Mode
Not Used
Not Used, Occupied NO, Occupied NC,
Occupied Fan NO, Occupied Fan NC, On,
Off
Inputs
BI1 Configuration
Disabled
Disabled, Occupancy, Occupancy
Override, Remote PIR, Dirty Filter,
Service, Fan Lock, Open Door, Open
Window
BI2 Configuration
Disabled
Disabled, Occupancy, Occupancy
Override, Remote PIR, Dirty Filter,
Service, Fan Lock, Open Door, Open
Window
Supply Temp Type
Analog Sensor
Analog Sensor, Heating NC, Cooling NC
* Non four-pipe units only
Supply Temp Sensor*
Nickel
Nickel, Platinum, A99B, 2.25k ohm
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
* SAT Mode = Analog Sensor,
non four-pipe
Supply Temp Offset*
0
-5 to 5 (F or C based on Units setting
under Display Settings menu
* Analog Sensor
Zone Temp Sensor
Nickel
Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
Zone Temp Offset
0
-5 to 5 (F or C based on Units setting
under Display Settings menu
Humidity Offset
0% RH
-15% to 15% RH
Reset Sensors
No
Yes or No
Table 6: Menus and Submenus (Part 3 of 7)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values