Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
2. Restore the value to the original setting and press
Save
once again to complete testing that output.
Pressing the back icon from the main commissioning
menu or allowing the menu system to time out and
return to the home screen ends commissioning and
puts the control logic back in control of the outputs.
Sensor Priority
The TEC3000 supports various sources of sensor data
for use in control or display including internal sensors,
remote sensors (connected via an analog input), or
network overrides. The TEC uses the highest priority
connected input (internal sensors followed by remote
sensors and then network overrides) for control and
display. Not all sources are available for all sensors.
Network overrides operate on a timeout basis. When a
network point is written to by a supervisor, the point
activates an override for 15 minutes. If a new update is
written within 15 minutes, the timer is restarted for
another 15 minutes.
Menus and Submenus
In the following table the * indicates that the menus depend on your configuration.
Table 6: Menus and Submenus (Part 1 of 7)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
Setpoints
Occ Cooling Setpoint
72°F (22°C)
55 to 85°F (13 to 30°C)
Occ Heating Setpoint
68°F (20°C)
55 to 85°F (13 to 30°C)
Unocc Cooling Setpoint
80ºF (27°C)
55 to 85°F (13 to 30°C)
Unocc Heating Setpoint
60°F (15°C)
55 to 85°F (13 to 30°C)
Stby Cooling Setpoint
74°F (23°C)
55 to 85°F (13 to 30°C)
Stby Heating Setpoint
66°F (19°C)
55 to 85°F (13 to 30°C)
Humidity Setpoint*
50% RH
0 to 100% RH
*Dehumidification Enable = True
Schedule
Schedule Options
Optimal Start Enable
No
Yes or No
Occupancy Override Duration
120 minutes
0 to 300 minutes
Motion Sensor Timeout
15 minutes
0 to 240 minutes
0 = PIR sensor disabled
Manual Occupancy Mode
No Override
No Override, Occupied, Unoccupied
Schedule Source
Schedule
Schedule or External