Johnson Controls TEC3620 Series Скачать руководство пользователя страница 13

FlexSys

 Thermostat Zone Controller / LCD Touch Screen

TEC - 3620

Model:

©2016 Johnson Controls   |   The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local           

                                                Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

© 2016 AirFixture, LLC

13

Installation / Operation Manual

V160919

TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification

Capability Installation Instructions

Setup and Adjustments

Overview

Figure 19 shows the thermostat controller home 

screen. The home screen can be customized to show 

or hide various elements from the occupant. See 

Table 3 for a listing of the touchscreen icons and 

Table 6 to identify the home screen settings under the 

Display Settings. When screen customization is used in 

conjunction with a passcode, the building owner can 

control which options the occupant can access and 

adjust.   

The humidity level is displayed on the home screen if 

there is a humidity sensor in the unit, or if the 

thermostat controller has a network override written to 

it.

Customizing the Home Screen

1. Press the Menu icon.
2. Press 

Display Settings

.

3. Enable or disable elements of the home screen as 

appropriate for the building owner and occupants.

4. Set the passcode on the thermostat controller to 

prevent the occupants from changing settings that 

they should not have access to change.

UI Icons

Table 3 describes the home screen touchable icons. 

Press and release a UI icon to activate the TEC. 

Additional touchable icons appear based on the menu, 

and those icons are also described in Table 3.   

Figure 19: Thermostat Controller 

Home Screen

Table 3:  Touchscreen Icons (Part 1 of 2)

Icon

Icon Name

Description

Menu 

Displays the 

configuration screens 

where various settings 

may be adjusted.

Alarm

Indicates that the 

thermostat controller 

has triggered an 

alarm.

Unit Power

On

Off

Powers the thermostat 

controller on or off.

Note:

This icon 

disables all equipment 

control, but does not 

physically power down 

the unit.

Network

Communication

Indicates that the 

thermostat controller 

detected a supervisory 

controller and both are 

online.

Arrow

Increases or 

decreases a value 

depending on the 

configuration screen.

Run/Hold

Displays the current 

setpoint. Hold mode is 

enabled by pressing 

the button.

No Hold/Hold

Displays the current 

setpoint. Hold mode is 

not enabled.

Hold/Hold

Displays the active 

setpoint. Hold mode is 

not enabled.

Right Arrow

Proceeds to the next 

screen.

Fan Override

On

Auto

Quiet

Adjusts the fan 

override between On, 

Auto, and Quiet.

Additional Touch Screen Icons

Home

Returns the display to 

the main home screen.

Содержание TEC3620 Series

Страница 1: ...s setup and operation quick and easy Multiple fan configurations are supported for fan coil equipment types single speed multi speed two or three discrete speeds variable speed EC motors 0 to 10 VDC control Some models support dehumidification on two pipe fan coil units with reheat and four pipe fan coil units with or without reheat When no heating is required the thermostat controller monitors sp...

Страница 2: ...w for sufficient clearance to insert a USB drive into the USB port This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not in...

Страница 3: ...e 3 3 Align the thermostat controller mounting base on the wall with the security screw on the top and use the base as a template to mark the two mounting hole locations Note If you need to install the thermostat controller on an electrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This...

Страница 4: ...ds of each wire 1 4 in 6 mm and connect them to the appropriate screw terminals as indicated in Table 2 and Figure 10 or Figure 11 Note For more details on wiring the MS TP Communications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Figure 5 Securing the Thermostat Controller Mounting Base to the Wall FIG TEC Backplane1 CAUTION Risk of Electric Shock Disconnect the pow...

Страница 5: ...rting them into the terminal connectors 4 Set the bus end of line termination switch to the desired location The bus end of line EOL termination switch allows you to designate the thermostat controller as the end of the Field Controller FC Bus and N2 Bus The default position is OFF If the thermostat controller is at the end of a daisy chain of devices on the FC Bus and N2 Bus set the EOL switch to...

Страница 6: ...len Head Adjustment Tool order separately to reinstall the security screw on the top of the thermostat controller cover 7 Remove the protective plastic cover sheet from the display Table 1 TEC3000 Model Names and Code Numbers Name Code Number Name Code Number TEC3310 00 TEC3610 0A TEC3311 01 TEC3611 0B TEC3312 02 TEC3612 0C TEC3313 03 TEC3613 0D TEC3320 04 TEC3620 0E TEC3321 05 TEC3621 0F TEC3322 ...

Страница 7: ...Label Function TEC3310 TEC3311 TEC3312 TEC3313 Floating FC VAV and On Off FC1 TEC3610 TEC3611 TEC3612 TEC3613 Floating FC VAV and On Off FC1 24 V 24 VAC hot from transformer FAN H Fan high FAN M Fan medium FAN L Fan on single speed variable speed Fan low multi speed AUX Auxiliary binary output AUX Auxiliary power COM 24 VAC common from transformer CLG O Cool open Floating Cooling NC On Off CLG C C...

Страница 8: ...tion Operation Manual V160919 TEC3000 Series On Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification Capability Installation Instructions 8 Note VAV and 2 pipe systems should connect their valve to the heating output Figure 10 On Off Wiring Diagram See Table 2 for Terminal Identification 24 V High Med FAN H AUX TB1 CLG C Low Fan on Fan Common Hot Heating Common Hot FAN ...

Страница 9: ...stallation Operation Manual V160919 TEC3000 Series On Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification Capability Installation Instructions Note VAV and 2 pipe systems should connect their valve to the heating output Figure 11 Floating Wiring Diagram See Table 2 for Terminal Identification 24 V High Med FAN H AUX TB1 CLG C Low Fan on Fan Heating FAN M FAN L AUX FIG ...

Страница 10: ...eating output Figure 12 Floating Control Pressure Dependent VAV Room Temperature Control Thermostat Minimum and Maximum Position Adjusted on Actuator Floating Actuator COS COM 24V HTG O HTG C FIG model_1_clng_only Figure 13 Floating Control Pressure Dependent VAV with Changeover Sensor Switch FIG model_1_htng_clng_chngvr Changeover Sensor Room Temperature Control Thermostat Minimum and Maximum Pos...

Страница 11: ...on Instructions Note VAV and 2 pipe systems should connect their valve to the heating output Figure 15 Floating Control Two Pipe Heating and Cooling Hydronic Valve Control Fan Coil Application FIG model_1_htng_clng_hdrnc Room Temperature Control Thermostat COS COM 24V HTG O HTG C Figure 16 Floating Control Two Pipe Heating and Cooling Hydronic Valve Control with Changeover Fan Coil Application FIG...

Страница 12: ...cation or misuse of its products 2016 AirFixture LLC 12 Installation Operation Manual V160919 TEC3000 Series On Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification Capability Installation Instructions Note VAV and 2 pipe systems should connect their valve to the heating output Figure 18 Floating Control Floating Two Pipe and Four Pipe Fan Coil Applications Two Pipe App...

Страница 13: ...ings 3 Enable or disable elements of the home screen as appropriate for the building owner and occupants 4 Set the passcode on the thermostat controller to prevent the occupants from changing settings that they should not have access to change UI Icons Table 3 describes the home screen touchable icons Press and release a UI icon to activate the TEC Additional touchable icons appear based on the me...

Страница 14: ...Press Update 5 Press Backup A message appears stating that the file will be saved to a USB drive 6 Press Confirm if you have the correct firmware version The firmware is loaded onto the USB drive 7 After the firmware is loaded onto the USB drive remove the USB drive from the TEC3000 Restoring the Settings 1 Ensure the TEC screen is on 2 Insert the USB drive into the right side of the TEC See Figur...

Страница 15: ...uration Menu The thermostat controller comes from the factory with default settings for all configuration parameters The UI menu navigation and default settings are shown in Table 6 Before any outputs turn on the controller must be configured for the equipment connected to it You need to start from the home screen to perform any of the following tasks Screen Reset The current screen returns to the...

Страница 16: ...tup 3 Press Supply Fan 4 Press Medium Speed On Cmd and adjust accordingly 5 Press High Speed On Cmd and adjust accordingly 6 Press to save and to return to the previous screen For VSF control the output is configurable for any range between 0 V and 10 V The parameters are Start Voltage Full Speed Voltage and Minimum Command Start Voltage is the voltage output at which the fan begins running and Fu...

Страница 17: ... General 4 Press Fan Mode and select On Auto or Smart 5 Press to save and to return to the previous screen Changeover Pressure Dependent VAV systems and 2 pipe fan coils require changeover detection in order to switch seasonal operation between heating and cooling modes The TEC supports the following methods for changeover automatic changeover using an analog sensor thermistor automatic changeover...

Страница 18: ... return to the previous screen This point is also exposed to the BAS through the point DEHUM EN To adjust the dehumidification setpoint 1 Press the Menu icon 2 Press Setpoints 3 Press Dehumidification and adjust accordingly 4 Press to save and to return to the previous screen This point is also exposed to the BAS through the point DEHUM SP Temperature Setpoints The thermostat controller provides a...

Страница 19: ...ncy source from To select the schedule source 1 Press the Menu icon 2 Press Schedule 3 Press Schedule Options 4 Press Schedule Source and select Local or BAS Table 4 Occupancy Determination Effective Occupancy Criteria Occupancy Source Occupancy Status Manual Occupancy Mode Occupancy BI Temporary Occupancy Occupancy Schedule Local or BAS Motion Sensor Occ Override Occupied Override Occupied Unoccu...

Страница 20: ...ncy source If that schedule is not set the default occupancy is continuously occupied Setting the local schedule A weekly occupancy schedule with up to four occupancy events per day can be set locally on the TEC and operate independently of a supervisor To set the schedule 1 See Selecting Schedule Source to ensure the schedule source is set to Local 2 Press the Menu icon 3 Press Schedule 4 Press S...

Страница 21: ...nu icon 2 Press Schedule 3 Press Schedule Options 4 Press Manual Occupancy Mode and select Occupied Unoccupied or No Override 5 Press to save and to return to the previous screen This option is also exposed to the BAS through the point OCCOVRD MODE Enabling Optimal Start The TEC supports an advanced optimal start algorithm The algorithm works in conjunction with a local schedule to pre heat or pre...

Страница 22: ...uously tunes the controller parameters to automatically optimize the control performance to match the equipment and zone By default PRAC is enabled and immediately begins to tune To reset tuning at any time to the factory defaults 1 Press the Menu icon 2 Press Control Setup 3 Press General 4 Press Reset PID Tuning and select Yes 5 Press to save and to return to the previous screen PRAC automatic t...

Страница 23: ...Reheat installed parameter is set to True the Aux output is used for Reheat Output The setting for the Aux Mode is ignored when reheat is enabled Commissioning Mode The thermostat controller has a built in commissioning mode designed to allow you to quickly test equipment wiring and functionality Commissioning mode temporarily disables the control logic allowing you to manually command any individ...

Страница 24: ...iority connected input internal sensors followed by remote sensors and then network overrides for control and display Not all sources are available for all sensors Network overrides operate on a timeout basis When a network point is written to by a supervisor the point activates an override for 15 minutes If a new update is written within 15 minutes the timer is restarted for another 15 minutes Me...

Страница 25: ... Instructions 25 Display Settings Passcode Enable No Yes or No Passcode NA 0000 to 9999 Passcode Enable Yes Brightness Setting 8 0 to 10 most dim to brightest Enable Backlight Timeout Yes Yes or No Units IP IP or SI Time N A Time Zone Central Many options Set Time Format 24 hour 24 hour or 12 hour Date N A Set Date Format YYYY MM DD YYYY MM DD or Day Month DD YYYY or MM DD YYYY Show Fan Icon Yes Y...

Страница 26: ...o Reset PID Tuning No Yes or No Auto PID Tuning Enable Yes Yes or No Dehumidification Enable No Yes or No Fan coil units with humidity sensor Aux Mode Not Used Not Used Occupied NO Occupied NC Occupied Fan NO Occupied Fan NC On Off Inputs BI1 Configuration Disabled Disabled Occupancy Occupancy Override Remote PIR Dirty Filter Service Fan Lock Open Door Open Window BI2 Configuration Disabled Disabl...

Страница 27: ...dress 1 1 to 255 N2 communication mode BACnet Device Address 4 4 to 127 BACnet MSTP communication mode MSTP Baud Rate Auto Auto 1200 9600 19200 38400 76800 BACnet MSTP communication mode BACnet Encoding Type BACnet MSTP Communication Mode ISO 10646 UCS 2 ISO 10646 UCS 2 ANSI X3 4 US ASCII Equipment Setup General Unit Type 4 Pipe 2 Pipe 4 Pipe VAV Heating Cooling Device Type Floating On Off Floatin...

Страница 28: ...Fan coil units only variable speed fan Med Fan Speed On Cmd 33 0 to 100 Fan coil units only multi speed fan High Fan Speed On Cmd 66 0 to 100 Fan coil units only multi speed fan Reheat Reheat Installed False True or False When set to True the Aux Output is used for Reheat Output Reheat Min Damper Position 20 0 to 100 VAV units with reheat installed Reheat Fan Required No Yes or No Fan coil units w...

Страница 29: ...nreliable Temperature Dehumidification Idle Cooling Heating Cooling Unavailable Heating Unavailable Cooling Unavailable due to Changeover Cooling Unavailable due to OA Temp Cooling Unavailable due to Control Mode Heating Unavailable due to Changeover Heating Unavailable due to OA Temp Heating Unavailable due to Control Mode Supply Air Temperature 75 F 50 to 250 F 45 to 121 C Changeover State Chang...

Страница 30: ...stat Controllers with Dehumidification Capability Installation Instructions Commissioning Supply Air Temperature Display Current Temperature Heat Command 0 0 to 100 Cool Command 0 0 to 100 Supply Fan No Yes or No Aux No Yes or No Update View Version 1 0 0 1067 Current Release of Software Load Firmware Attempting to access USB File List from USB drive Restore Local Storage File List from USB drive1...

Страница 31: ...m Adjustable1 8 in 203 mm TE 6311A 1 Averaging 8 ft 2 4 m TE 6315M 1 TE 6315V 21 17 ft 5 2 m TE 6316M 1 TE 6316V 21 Duct 4 in 102 mm TE 631GM 1 8 in 203 mm TE 6311M 1 TE 6311P 1 18 in 457 mm TE 631JM 1 Flange 4 in 102 mm TE 631GV 2 8 in 203 mm TE 6311V 2 Flush N A TE 6310F 0 TE 6310F 1 Outside air 3 in 76 mm TE 6313P 1 Strap mount 3 in 76 mm TE 631S 1 Wall2 N A TE 6314P 1 Well 6 in 152 mm TE 631AM...

Страница 32: ...lange 4 in 102 mm TE 634GV 2 8 in 203 mm TE 6341V 2 Outside air 3 in 76 mm TE 6343P 1 Wall2 N A TE 6344P 1 Well 8 in 203 mm TE 6342M 1 6 in 152 mm TE 634AM 2 Thermistor 10k ohm Type II Adjustable 8 in 203 mm TE 6361A 1 Duct 4 in 102 mm TE 636GM 1 8 in 203 mm TE 6361M 1 TE 6361P 1 18 in 457 mm TE 636JM 1 Flange 4 in 102 mm TE 636GV 2 8 in 203 mm TE 6361V 2 Flush N A TE 6360F 0 TE 6360F 1 Outside ai...

Страница 33: ...ipment connected to the BI configured for a Dirty Filter alarm is triggering the alarm Replace the filter in the equipment per the manufacturer s instructions Calibration Corrupt Factory calibration data is lost or is not installed Contact Johnson Controls product sales and support Changeover Fail The Supply Temperature Sensor is not installed has failed or has been disconnected and the TEC can no...

Страница 34: ...e Causes Solutions The controller displays Idle with a Unit Status of Cooling Unavailable due to Changeover despite being above cooling setpoint or with a status of Heating Unavailable due to Changeover despite being below the setpoint The 2 pipe fan coil VAV system does not have a changeover sensor and switch connected or the sensor switch has failed 1 Check the wiring of the supply temperature s...

Страница 35: ...imes and is set incorrectly for the equipment zone or user preference There is a tradeoff between reduced control band size and increased energy usage and equipment wear from increased cycling 1 To tighten the control band reduce the minimum on off time settings Minimal control band is achieved with a 60 second minimum on off time 2 To loosen the control band increase the minimum on off time setti...

Страница 36: ...ds to incorrectly identify themselves Contact Johnson Controls product sales and support The controller displays Controller Fault An internal fault was detected and the controller was unable to recover Contact Johnson Controls product sales and support The Bell icon is displayed on the TEC home page The fault has been detected on the TEC See Table 8 for TEC fault causes and resolution Partial Rest...

Страница 37: ...aximum per Network Automation Engine NAE 4 000 ft 1 219 m maximum cable length Temperature Range Backlit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C typical calibrated Humidity 5 RH from 20 to 80 RH at 50 to 90 F 10 to 32 C Minimum Deadband 2F ...

Отзывы: