background image

 

Configuring the Digital Inputs (DI1 and DI2) 

Press the configuration menu access key. The first 
prompt is to program Digital Inputs DI1 and DI2. 

The digital inputs display an alarm condition when the 
input is closed. An alarm message is included on the 
scrolling Status Display Menu and when the message 
is displayed, the backlight momentarily lights up. 

Each digital input can be programmed in one of four 
conditions. 

• 

None

 – No function is associated with the input. 

• 

Service

 – A Service alarm is displayed. 

• 

Filter

 – A Filter alarm is displayed. 

• 

RemOVR 

– Remote Override (OVR) contact. This 

disables all override menu functions of the 
thermostat. The override function is now controlled 
manually by a remote, momentarily closed 
contact. When configured in this mode, the input 
operates in a toggle mode. With this function 
enabled, it is now possible to toggle between 
unoccupied and occupied setpoints for the amount 
of time set by the temporary occupancy time 
parameter. 

When override is enabled through the digital 
inputs, an 

Override

 message appears in the 

Status Display Menu. 

To configure the digital inputs while in the Installer 
Configuration Menu: 

1.  Press YES to configure Digital Input 1 or NO to 

advance to Digital Input 2. 

2.  Use the UP/DOWN arrow keys to locate the 

desired function for Digital Input 1. Press YES to 
select the desired function. 

3.  Press YES to configure Digital Input 2 or NO to 

advance to the keypad lockout setup prompt. 

4.  Use the UP/DOWN arrow keys to locate the 

desired function for Digital Input 2. Press YES to 
select the desired function. 

The display now shows the keypad lockout setup 
prompt. See the 

Enabling the Keypad Lockout 

(Lockout) 

section for instructions. 

Note: 

Regardless of the digital input configuration 

(

None

Service

Filter, or RemOVR

) established 

through the local interface at the TEC2104-1, the 
states of DI1 and DI2 are communicated over the N2 
network. This enables the ability to communicate 
alarm conditions over the network without local 
annunciation on the TEC2104-1 display. 

Enabling the Keypad Lockout (Lockout) 

The TEC2104-1 has four levels of keypad lockout. The 
levels and degree of lockout are shown in Table 3. 

To set the keypad lockout level while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the keypad lockout 

setup prompt appears in the display. Press YES to 
enter the keypad lockout menu. 

2.  Use the UP/DOWN arrow keys to locate the 

desired lockout level. Press YES to select the 
level. 

The display now shows the power delay setup prompt. 
See the 

Setting the Power-Up Delay

 

(Pwr del)

 section 

for instructions. 

Table 3: Keypad Lockout Levels 

Function 

Level 0 

Level 1 

Level 2 

Occupancy 
Override 

Yes access 

Yes access 

No access 

Temperature 
Setpoints 

Yes access 

No access 

No access 

System Mode 
Setting 

Yes access 

Yes access 

No access 

Fan Mode 
Setting 

Yes access 

Yes access 

No access 

 

Setting the Power-Up Delay (Pwr del) 

On initial power-up of the TEC2104-1 (or each time 
power is removed and reapplied), there is a delay 
before any operation is authorized (fan, cooling, and 
heating). The delay time is adjustable between 10 and 
120 seconds. This parameter can also be used to 
sequence the start-up of multiple units in one location. 

Note: 

When adjusting the time with the UP/DOWN 

arrow keys, holding the keys down changes the time 
by 10-second intervals. 

To set the delay time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the power delay 

setup prompt appears in the display. Press YES to 
enter the power delay setup menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

power-up delay setting. Press YES to store the 
setting. 

The display now shows the frost protection setup 
prompt. See the 

Enabling Frost Protection (Frost pr)

 

section for instructions. 

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

9

 

Содержание TEC2104-1

Страница 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Страница 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Страница 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Страница 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Страница 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Страница 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Страница 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Страница 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Страница 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Страница 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Страница 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Страница 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Страница 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Страница 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Страница 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Страница 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Страница 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Страница 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Страница 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Отзывы: