Setting the Mechanical Cooling Mode (C mech) 

This setting determines whether to allow the operation 
of mechanical cooling if the free cooling (economizer) 
cannot maintain the cooling setpoint. 

• 

Selecting 

off

 means the mechanical cooling never 

operates at the same time as the free cooling. This 
option typically applies when the mixed air 
temperature sensor is installed after the 
mechanical cooling coils. 

• 

Selecting 

on

 enables mechanical cooling to 

operate when the free cooling (economizer) 
cannot maintain the cooling setpoint. This option 
typically applies when the mixed air temperature 
sensor is installed before the mechanical cooling 
coils. 

To set the mechanical cooling mode while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the mechanical 

cooling mode prompt appears in the display. Press 
YES to enter the Mechanical Cooling Mode Menu. 

2.  Use the UP/DOWN arrow keys to choose on or off. 

Press YES to store the selection. 

The display now shows the Mixed Air Setpoint Menu. 
See the 

Setting the Mixed Air Temperature Setpoint

 

(Mix stpt)

 section for instructions. 

Setting the Mixed Air Temperature Setpoint 
(Mix stpt) 

The mixed air temperature setpoint establishes the 
mixed air temperature when operating in the 
economizer mode. The economizer is adjusted 
accordingly to maintain the mixed air temperature 
setpoint. 

The mixed air temperature setpoint is adjustable from 
50 to 90

°

F (10 to 32

°

C). 

To adjust the mixed air temperature setpoint while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the mixed air 

setpoint prompt appears in the display. Press YES 
to enter the Mixed Air Setpoint Menu. 

2.  Use the UP/DOWN arrow keys to adjust the mixed 

air setpoint. Press YES to store the temperature. 

The display mixed air temperature prompt is now 
displayed. See the 

Displaying the Mixed Air 

Temperature (Display)

 section for instructions. 

Displaying the Mixed Air Temperature (Display) 
(Only Available if Mixed Air Temperature Sensor is 
Installed) 

The mixed air temperature can be displayed if a mixed 
air temperature sensor is installed. The temperature 
can be used to help service and troubleshoot the 
equipment and economizer operation. The mixed air 
temperature is only accessible through the Installer 
Configuration Menu. 

To access the mixed air temperature while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the display mixed 

air temperature prompt appears in the display. 
Press YES to display mixed air temperature. 

2.  The mixed air temperature is displayed. After 

about 45 seconds the TEC2104-1 returns to the 
Status Display Menu or press YES to advance to 
the exit menu display. 

3.  Press YES to exit the Installer Configuration Menu 

or press NO to return to the beginning of the menu 
(digital input configuration). 

Operation 

Programming/Operating the TEC2104-1 

Once the TEC2104-1 is configured through the 
Installer Configuration Menu, the thermostat’s 
operating parameters can be programmed through the 
Main User Menu (access the Main User Menu by 
pressing the MENU key during normal thermostat 
operation). The Main User Menu contains the basic 
operating features of the TEC2104-1. The Main User 
Menu uses Auto Help. When there is a pause in 
programming activity, Auto Help automatically appears 
in the Main User Menu. To exit Auto Help, continue 
with the Programming selection. 

When the thermostat is in the Main User Menu and is 
left unattended for 45 seconds, it reverts to the Status 
Display Menu. 

14    

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions 

Содержание TEC2104-1

Страница 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Страница 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Страница 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Страница 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Страница 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Страница 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Страница 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Страница 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Страница 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Страница 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Страница 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Страница 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Страница 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Страница 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Страница 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Страница 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Страница 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Страница 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Страница 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Отзывы: