Programming Overview 

There are three menus used to view, program, and 
configure the TEC2104-1 thermostats: 

The 

Status Display Menu

 displays during normal 

thermostat operation. The menu continually scrolls 
through the following parameters: 

• 

Room Temperature 

• 

System Mode 

• 

Schedule Status (Occupied/Unoccupied/Override 
[see Note]) 

Note: 

Override displays only when in the 

Overrride mode. 

• 

Auxiliary Temperature (Displays outdoor or other 
auxiliary temperatures. Requires the sensor to be 
wired to the Auxiliary/Outdoor Air Sensor terminal 
OS [Figure 5].) 

• 

Applicable Alarms (The backlight lights up as an 
alarm condition is displayed.) 

To temporarily stop the scrolling, press the up 
arrow/SCROLL key. 

Use the 

Main User Menu

 to access and change the 

thermostat’s basic operating parameters. Access the 
menu by pressing the MENU key during normal 
thermostat operation. 

Use the 

Installer Configuration Menu

 to set up the 

thermostat for application specific operation. Access 
the menu by removing the front cover and pressing the 
configuration key, labeled CONFIG (Figure 7). 

Configuring the TEC2104-1 

The TEC2104-1 ships from the factory with default 
settings for all configurable parameters. The default 
settings are shown in Table 2. To reconfigure the 
parameters, follow the steps in this section for the 
corresponding parameters. The parameters must be 
set up first by accessing the Installer Configuration 
Menu. Access the Installer Configuration Menu by 
removing the front cover and pressing the 
configuration key (Figure 7). 

Exit the Installer Configuration Menu any time by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it, press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

Table 2: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section

.

 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section

.

 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See the 

Enabling the Keypad Lockout 

(Lockout) 

section

.

 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See the 

Setting the Power-Up Delay 

(Pwr del) 

section

.

 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See the 

Enabling Frost Protection 

(Frost pr) 

section

.

 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See the 

Setting the Maximum Heating 

Setpoint (Heat max) 

section

.

 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See the 

Setting the Minimum Cooling 

Setpoint (Cool min) 

section

.

 

 

Sets the Anti-Short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See the 

Setting the Anti-Short Cycle 

Timer (Anticycl) 

section

.

 

 

Sets the Heating Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Heating 

Stage Cycles per Hour (Heat cph) 

section

.

 

 

Sets the Cooling Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Cooling 

Stage Cycles per Hour (Cool cph) 

section

.

 

Continued on next page . . . 

RoomTemp
75.0

°

F

 

DI1
set? Y/N

 

DI2
set? Y/N 

Lockout
set? Y/N 

Pwr del
set? Y/N 

Frost pr
set? Y/N 

Heat max
set? Y/N 

Cool min
set? Y/N 

Anticycl
set? Y/N 

Heat cph
set? Y/N 

Cool cph
set? Y/N 

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

7

 

Содержание TEC2104-1

Страница 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Страница 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Страница 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Страница 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Страница 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Страница 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Страница 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Страница 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Страница 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Страница 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Страница 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Страница 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Страница 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Страница 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Страница 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Страница 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Страница 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Страница 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Страница 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Отзывы: