background image

 

 

   

 

Installation Instructions   

 

Issue Date  August 18, 2004 

 

© 

2004 Johnson Controls, Inc. 

1

 

 

TEC2104-1 Networked Multi-Stage Economizer Thermostat 

 

Application 

The TEC2104-1 is an N2 networked thermostat that 
provides control of single- or two-stage unitary rooftop 
units with economizers. The TEC2104-1 provides 
exceptional accuracy through the use of a unique 
Proportional-Integral (PI) time proportioning algorithm. 
The algorithm virtually eliminates temperature offset 
associated with traditional, differential-based on/off 
thermostats. The TEC2104-1 also uses an adaptive 
control logic algorithm to control the space 
temperature during recovery to minimize overshoot 
while providing maximum comfort. Economizer 
functions include a 0 to 10 VDC control signal, 
dry-bulb changeover strategy, adjustable minimum 
position, and mixed air setpoint control. 

The TEC2104-1 has Metasys® N2 communication 
capability. This communication allows the user to view 
and adjust parameters from a remote workstation. 
Additionally, the menu-driven backlit display, plain text 
menus, and five keys on the TEC2104-1 make 
operating the thermostat easy and intuitive. 

Note: 

In this document, Building Automation System 

(BAS) is a generic term that refers to the Metasys 
Network (Network Control Module [NCM] or 
N30 Series) and Companion (CPN) supervisory 
systems. The specific system names are used when 
referring to system-specific applications. 

Installation 

Location Considerations 

Locate the TEC2104-1 thermostat: 

• 

on a partitioning interior wall and approximately 
5 ft. (1.5 m) above the floor in a location of 
average temperature 

• 

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors 

• 

away from steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical 
interference 

To install the thermostat: 

1. 

Remove the security screw on the bottom of the 
thermostat cover using a Phillips-head 
screwdriver. Open the thermostat by pulling on 
the bottom side of the thermostat cover 
(Figure 1). 

2. 

Unlock the Printed Circuit Board (PCB) by 
carefully pressing the locking tabs to the right 
(Figure 2). Open the thermostat’s PCB to the left. 

3. 

Pull out approximately 6 in. (152 mm) of wires 
from the wall and insert the cable through the 
hole in the base. 

4. 

Align the base on the wall, and using the base as 
a template, mark the location of the two mounting 
holes on the wall. Confirm the thermostat base is 
installed with the proper side up. 

5. 

Use the supplied anchors and screws for 
mounting on drywall or plaster. Drill two 3/16 in. 
(4.7 mm) holes at the marked locations and tap 
nylon anchors flush to wall surface (Figure 3). 

6. 

Position base on the wall, insert screws through 
mounting base, and fasten into wall anchors. Do 
not overtighten screws. 

7. 

Swing the thermostat PCB back to the right to 
close. Gently press on the PCB to secure each of 
the locking tabs. 

8. 

Pull out the screw terminal blocks using the 
pull-tabs on each connector (Figure 4). 

Note: 

The number of terminals on the terminal 

blocks varies depending on the TEC model. 

IMPORTANT: 

Use this TEC2104-1 networked 

economizer thermostat only as an operating control. 
Where failure or malfunction of the TEC2104-1 could 
lead to personal injury or property damage to the 
controlled equipment or other property, additional 
precautions must be designed into the control 
system. Incorporate and maintain other devices such 
as supervisory or alarm systems or safety or limit 
controls intended to warn of, or protect against, 
failure or malfunction of the TEC2104-1.  

 

Part No. 24-9890-56, Rev. B 

www.johnsoncontrols.com 

Содержание TEC2104-1

Страница 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Страница 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Страница 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Страница 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Страница 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Страница 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Страница 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Страница 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Страница 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Страница 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Страница 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Страница 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Страница 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Страница 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Страница 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Страница 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Страница 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Страница 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Страница 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Отзывы: