Installation Instructions
Issue Date August 18, 2004
©
2004 Johnson Controls, Inc.
1
TEC2104-1 Networked Multi-Stage Economizer Thermostat
Application
The TEC2104-1 is an N2 networked thermostat that
provides control of single- or two-stage unitary rooftop
units with economizers. The TEC2104-1 provides
exceptional accuracy through the use of a unique
Proportional-Integral (PI) time proportioning algorithm.
The algorithm virtually eliminates temperature offset
associated with traditional, differential-based on/off
thermostats. The TEC2104-1 also uses an adaptive
control logic algorithm to control the space
temperature during recovery to minimize overshoot
while providing maximum comfort. Economizer
functions include a 0 to 10 VDC control signal,
dry-bulb changeover strategy, adjustable minimum
position, and mixed air setpoint control.
The TEC2104-1 has Metasys® N2 communication
capability. This communication allows the user to view
and adjust parameters from a remote workstation.
Additionally, the menu-driven backlit display, plain text
menus, and five keys on the TEC2104-1 make
operating the thermostat easy and intuitive.
Note:
In this document, Building Automation System
(BAS) is a generic term that refers to the Metasys
Network (Network Control Module [NCM] or
N30 Series) and Companion (CPN) supervisory
systems. The specific system names are used when
referring to system-specific applications.
Installation
Location Considerations
Locate the TEC2104-1 thermostat:
•
on a partitioning interior wall and approximately
5 ft. (1.5 m) above the floor in a location of
average temperature
•
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•
away from steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical
interference
To install the thermostat:
1.
Remove the security screw on the bottom of the
thermostat cover using a Phillips-head
screwdriver. Open the thermostat by pulling on
the bottom side of the thermostat cover
(Figure 1).
2.
Unlock the Printed Circuit Board (PCB) by
carefully pressing the locking tabs to the right
(Figure 2). Open the thermostat’s PCB to the left.
3.
Pull out approximately 6 in. (152 mm) of wires
from the wall and insert the cable through the
hole in the base.
4.
Align the base on the wall, and using the base as
a template, mark the location of the two mounting
holes on the wall. Confirm the thermostat base is
installed with the proper side up.
5.
Use the supplied anchors and screws for
mounting on drywall or plaster. Drill two 3/16 in.
(4.7 mm) holes at the marked locations and tap
nylon anchors flush to wall surface (Figure 3).
6.
Position base on the wall, insert screws through
mounting base, and fasten into wall anchors. Do
not overtighten screws.
7.
Swing the thermostat PCB back to the right to
close. Gently press on the PCB to secure each of
the locking tabs.
8.
Pull out the screw terminal blocks using the
pull-tabs on each connector (Figure 4).
Note:
The number of terminals on the terminal
blocks varies depending on the TEC model.
IMPORTANT:
Use this TEC2104-1 networked
economizer thermostat only as an operating control.
Where failure or malfunction of the TEC2104-1 could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices such
as supervisory or alarm systems or safety or limit
controls intended to warn of, or protect against,
failure or malfunction of the TEC2104-1.
Part No. 24-9890-56, Rev. B
www.johnsoncontrols.com