T9600

P/N 24-11447-00004 Rev. B  Issue Date: 11 2020

Note

• 

Terminal blocks changes depending on the application selected, check the table beside first

• The relay output are line voltage, they are connected with Terminal “L” internally 

• The digital input “OCC” can assume different meaning depending on parameter 12 setting

• The T9603-T000-1JF0 does not feature the 

 and 

M

 button. To access the User Setting parameter list, press the 

 button 5 s instead. Press the 

 

button to scroll through the list. Under User Setting menu, press the 

 button 5 s to access Service Setting parameter list. Press the 

 button to scroll 

through the list.

1. 

T9603-T000-1JF0 BI Input default 04 Warning. Options: 00: Occupancy Input, 04: Warning  

PARAMETER SETTING (PART 2/2)

Code

T9600- 

TF20-

1JS0

T9603- 

T000-

1JF0

T9601- 

TF20-

1JS0

T9600- 

TF21-

1JS0 Parameter Name

Default Function

09 

ECM-MAX-V

10 V

ECM Max  voltage.

Max  voltage below which the fan output is 100%.

Step: 0.5 V

Range: 0 V~10 V

10

STG-DFFR

3°C/5°F

floor heater Stage temperature difference

Step: 0.5°C (1°F)

Range: 0°C~10°C (0°F-18°F)

11

HTRSS

1°C/2°F Hysteresis for ON/OFF control

Range: 1~5

12

1

BI-FUNCTION

02

00: Occupancy Input

01: Dew Point Risk Input

02: Filter Alarm Input

03: Change Over Sensor Input

04: Warning

13

MODE-RST

00

00: No Restriction

01: Cooling only

02: Heating only

14

FAN-RST

03

00: No Fan

01: One Speed Fan

02: Two Speed Fan

03: Three Speed Fan

15

FAN-DB

01

Fan operation in deadband:

00: OFF

01: Low

16

UNOCC-FAN

00

Fan mode in unoccupied:

00: OFF

01: Low

17

HTG-STG

02

00: One Heating Stage - Fan Coil

01: One Heating Stage - Floor Heating

02: Two heating stage

18

BI-PLRT

01

BI polarity: 

00: Normally Close

01: Normally Open

19

OCC-OVRD

00

Override the OCC-S value:

00: No Override

01: Occupied

02: Unoccupied

20

SNS-TYPE

00

00: JCI type 10K NTC

01: China type 10K NTC

21

FAN-DELAY

00

Fan off delay after valve closed, in seconds(0-99 s)

22

ECM-RLY

00

00: Disable

01: Enable

English

ALARM CODE DESCRIPTION

Item

Code  Description

E1 

Internal sensor warning. 

HI 

High temperature warning. Room temperature >55°C (>131°F)

LO 

Low temperature warning. Room temperature <0°C (<32°F) or internal sensor opened.

E5 

Dew point risk warning. Valves and fan are shut off when error is active.

8

E6

Filter alarm

9

E7

BI warning

   

  flashes when there is a communication error.

Содержание T9600

Страница 1: ...rademarks of Johnson Controls All other marks herein are the marks of their respective owners Copyright 2020 Johnson Controls All rights reserved Any unauthorized use or copying is strictly prohibited...

Страница 2: ...Med FAN 2 pipe 3 wire relay 2 3 L N L N 100 240 VAC 50 60Hz TiO2 ESP GND MODBUS NTC OCC B A COM V2 V1 Low Hi Med FAN 2 pipe FCU relay with TiO2 ESP 2 TiO2 ESP Cool Heat L N L N 100 240 VAC 50 60Hz FLO...

Страница 3: ...BUS NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2 COOL HEAT 0 10 V ECM FAN V3 2 pipe 3 wire relay with ECM fan 2 ECM GND NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2...

Страница 4: ...AN AO1 M FLOOR HEAT L N V1 V2 V3 Cool Heat 2 pipe FCU prop with radiator and ECM fan 2 ECM MODBUS NTC OCC COM L N F ON B A GND 100 240 VAC 50 60Hz ECM FAN FAN AO1 M HEAT COOL GND L N V1 V2 V3 AHU MODB...

Страница 5: ...system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the T9 Series thermostat...

Страница 6: ...TIO2ESP CTL 00 TIO2ESP control 00 Automatic 01 Manual For TIO2ESP application 15 BAUD_MODBUS 00 Baud rate for Modbus 00 9600 01 4800 Continued INSTRUCTIONS On Off Setting Press to turn on press again...

Страница 7: ...foward through the list PARAMETER SETTING PART 1 2 Code T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 Parameter name Default Function 02 FRST PRT 00 Frost protection 00 No 01 Yes 03...

Страница 8: ...C 0 F 18 F 11 HTRSS 1 C 2 F Hysteresis for ON OFF control Range 1 5 12 1 BI FUNCTION 02 00 Occupancy Input 01 Dew Point Risk Input 02 Filter Alarm Input 03 Change Over Sensor Input 04 Warning 13 MODE...

Страница 9: ...T9600 P N 24 11447 00004 Rev B Issue Date 11 2020 T9000 T9000 T9000 T9000 T9000 PCB PCB T9000 LCD M A B C D E A B C D E F G Tio2 ESP H I J K L M N O P Q R S T9600...

Страница 10: ...5 C 5 C 9 F 9 F 06 26 C 79 F 0 5 C 1 F 22 C 32 C 72 F 90 F 07 18 C 64 F 0 5 C 1 F 10 C 21 C 50 F 70 F 08 10 s 1 99 s 09 PB 5 1 10 10 KI 10 0 99 11 30 0 99 s 12 02 00 01 02 13 TiO2 ESP 00 00 01 15 00...

Страница 11: ...01 4 ECM 02 2 ECM 03 2 ECM 04 2 TiO2 ESP ECM 05 ECM 06 2 ECM 07 2 ECM 08 2 ECM 09 T9600 TF21 1JS0 00 2 01 4 05 5 C 41 F 0 C 36 C 32 F 97 F 06 35 C 95 F 2 C 37 C 36 F 99 F 07 5 C 41 F 0 C 20 C 32 F 68...

Страница 12: ...O O O O O O O O O O O O O SJ T11364 GB T26572 GB T26572 SJ T11364 RoHS SJ T11364 1 E1 2 HI 55 3 LO 1 0 2 4 E5 8 E6 9 E7 BI T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 14 03 00 01...

Страница 13: ...or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable terms set forth at www johnsoncontrols com techterms Your use of this...

Отзывы: