T9600
P/N 24-11447-00004 Rev. B Issue Date: 11 2020
Note
•
Terminal blocks changes depending on the application selected, check the table beside first
• The relay output are line voltage, they are connected with Terminal “L” internally
• The digital input “OCC” can assume different meaning depending on parameter 12 setting
• The T9603-T000-1JF0 does not feature the
and
M
button. To access the User Setting parameter list, press the
button 5 s instead. Press the
button to scroll through the list. Under User Setting menu, press the
button 5 s to access Service Setting parameter list. Press the
button to scroll
through the list.
1.
T9603-T000-1JF0 BI Input default 04 Warning. Options: 00: Occupancy Input, 04: Warning
PARAMETER SETTING (PART 2/2)
Code
T9600-
TF20-
1JS0
T9603-
T000-
1JF0
T9601-
TF20-
1JS0
T9600-
TF21-
1JS0 Parameter Name
Default Function
09
■
ECM-MAX-V
10 V
ECM Max voltage.
Max voltage below which the fan output is 100%.
Step: 0.5 V
Range: 0 V~10 V
10
■
■
STG-DFFR
3°C/5°F
floor heater Stage temperature difference
Step: 0.5°C (1°F)
Range: 0°C~10°C (0°F-18°F)
11
■
■
■
■
HTRSS
1°C/2°F Hysteresis for ON/OFF control
Range: 1~5
12
■
■
1
■
■
BI-FUNCTION
02
00: Occupancy Input
01: Dew Point Risk Input
02: Filter Alarm Input
03: Change Over Sensor Input
04: Warning
13
■
■
■
MODE-RST
00
00: No Restriction
01: Cooling only
02: Heating only
14
■
■
■
FAN-RST
03
00: No Fan
01: One Speed Fan
02: Two Speed Fan
03: Three Speed Fan
15
■
■
■
FAN-DB
01
Fan operation in deadband:
00: OFF
01: Low
16
■
■
■
UNOCC-FAN
00
Fan mode in unoccupied:
00: OFF
01: Low
17
■
■
HTG-STG
02
00: One Heating Stage - Fan Coil
01: One Heating Stage - Floor Heating
02: Two heating stage
18
■
■
■
■
BI-PLRT
01
BI polarity:
00: Normally Close
01: Normally Open
19
■
■
■
■
OCC-OVRD
00
Override the OCC-S value:
00: No Override
01: Occupied
02: Unoccupied
20
■
■
■
■
SNS-TYPE
00
00: JCI type 10K NTC
01: China type 10K NTC
21
■
■
■
FAN-DELAY
00
Fan off delay after valve closed, in seconds(0-99 s)
22
■
ECM-RLY
00
00: Disable
01: Enable
English
ALARM CODE DESCRIPTION
Item
Code Description
1
E1
Internal sensor warning.
2
HI
High temperature warning. Room temperature >55°C (>131°F)
3
LO
Low temperature warning. Room temperature <0°C (<32°F) or internal sensor opened.
4
E5
Dew point risk warning. Valves and fan are shut off when error is active.
8
E6
Filter alarm
9
E7
BI warning
flashes when there is a communication error.