T9600

P/N 24-11447-00004 Rev. B  Issue Date: 11 2020

English

PARAMETER SETTING (PART 2/2)

Code

T9600- 

TF20-

1JS0

T9603- 

T000-

1JF0

T9601- 

TF20-

1JS0

T9600- 

TF21-

1JS0 Parameter Name

Default Function

16

KEY-LOCK 

00

Key lock function:

00: No Lockout

01: Level 1 ->Lock all keys

02: Level 2 ->Lock the keys except Fan Speed and Temp 

Adjustment keys

03: Level 3 ->Lock the ON/OFF and Clock keys

04: Level 4 ->Lock the keys except ON/OFF key

17

TEMP-DISP

00

UI display room temperature or set point:

00: Room Temperature

01: Setpoint

18

UNIT

01

Unit selection:

00: IP

01: SI

19

DAMP-OPEN-TIME

0

Damper opening time, for AHU application

range 0-99 (0=75 s, 99=174 s)

20

SF-VERSION

Software version, read only

SERVICE SETTING (Setting through professional)

In the Setting page press 

 button for 3 seconds to get in Service page, the occupancy icon 

 shows. 

Press 

 to scroll forward and 

M

 button to 

scroll backward in the list and 

use 

 and 

 button to change parameter value. 

For T9603-T000-1JF0, press and hold 

 for 3 seconds to access 

the parameter list and press 

 to scroll foward through the list.

PARAMETER SETTING (PART 1/2)

Code

T9600- 

TF20-

1JS0

T9603- 

T000-

1JF0

T9601- 

TF20-

1JS0

T9600- 

TF21-

1JS0 Parameter name

Default Function

02

FRST-PRT

00

Frost protection:

00: No

01: Yes

03

FH-FAN

00

Enable/disable fan output when floor heater 

00: Disable

01: Enable

04

APPLICATION

00

T9600- TF20-1JS0: 

00: 2pipe FCU (relay)

01: 4pipe FCU (relay)

02: 2pipe 3 wire (relay)

03: 2pipe FCU (relay) with floor heating

04: 2pipe FCU (relay) with TiO2/ESP 

05: water source heat pump

T9601- TF20-1JS0: 

00: 2-pipe FCU (relay), ECM fan

01: 4-pipe FCU (relay), ECM fan

02: 2-pipe 3 wire (relay), ECM fan

03: 2-pipe FCU with floor heater, ECM fan

04: 2-pipe FCU with TiO2/ESP, ECM fan

05: water source heat pump, ECM fan

06: 2-pipe FCU (prop), ECM fan

07: 2-pipe FCU (prop) with floor heater, ECM fan

08: 2-pipe FCU (prop) with radiator, ECM fan

09. AHU

T9600- TF21-1JS0: 

00: 2-pipe FCU, three speed fan 

01: 4-pipe FCU, three speed fan

05

DOWN-SET-LIMIT

5°C/

41°F

lower setpoint limit

Range: 0°C~36°C (32°F-97°F)

06

UP-SET-LIMIT

35°C/

95°F

Upper setpoint limit

Range: 2°C~37°C (36°F~99°F)

07

FP-SP

5°C/

41°F

Frost protection setpoint.

Step: 0.5°C (1°F)

Range: 0°C~20°C (32°F-68°F)

08

ECM-MIN-V

3 V

ECM Min voltage.

Min voltage below which the fan output is 0%.

Step: 0.5 V

Range: 0 V~10 V

...Continued...

Содержание T9600

Страница 1: ...rademarks of Johnson Controls All other marks herein are the marks of their respective owners Copyright 2020 Johnson Controls All rights reserved Any unauthorized use or copying is strictly prohibited...

Страница 2: ...Med FAN 2 pipe 3 wire relay 2 3 L N L N 100 240 VAC 50 60Hz TiO2 ESP GND MODBUS NTC OCC B A COM V2 V1 Low Hi Med FAN 2 pipe FCU relay with TiO2 ESP 2 TiO2 ESP Cool Heat L N L N 100 240 VAC 50 60Hz FLO...

Страница 3: ...BUS NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2 COOL HEAT 0 10 V ECM FAN V3 2 pipe 3 wire relay with ECM fan 2 ECM GND NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2...

Страница 4: ...AN AO1 M FLOOR HEAT L N V1 V2 V3 Cool Heat 2 pipe FCU prop with radiator and ECM fan 2 ECM MODBUS NTC OCC COM L N F ON B A GND 100 240 VAC 50 60Hz ECM FAN FAN AO1 M HEAT COOL GND L N V1 V2 V3 AHU MODB...

Страница 5: ...system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the T9 Series thermostat...

Страница 6: ...TIO2ESP CTL 00 TIO2ESP control 00 Automatic 01 Manual For TIO2ESP application 15 BAUD_MODBUS 00 Baud rate for Modbus 00 9600 01 4800 Continued INSTRUCTIONS On Off Setting Press to turn on press again...

Страница 7: ...foward through the list PARAMETER SETTING PART 1 2 Code T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 Parameter name Default Function 02 FRST PRT 00 Frost protection 00 No 01 Yes 03...

Страница 8: ...C 0 F 18 F 11 HTRSS 1 C 2 F Hysteresis for ON OFF control Range 1 5 12 1 BI FUNCTION 02 00 Occupancy Input 01 Dew Point Risk Input 02 Filter Alarm Input 03 Change Over Sensor Input 04 Warning 13 MODE...

Страница 9: ...T9600 P N 24 11447 00004 Rev B Issue Date 11 2020 T9000 T9000 T9000 T9000 T9000 PCB PCB T9000 LCD M A B C D E A B C D E F G Tio2 ESP H I J K L M N O P Q R S T9600...

Страница 10: ...5 C 5 C 9 F 9 F 06 26 C 79 F 0 5 C 1 F 22 C 32 C 72 F 90 F 07 18 C 64 F 0 5 C 1 F 10 C 21 C 50 F 70 F 08 10 s 1 99 s 09 PB 5 1 10 10 KI 10 0 99 11 30 0 99 s 12 02 00 01 02 13 TiO2 ESP 00 00 01 15 00...

Страница 11: ...01 4 ECM 02 2 ECM 03 2 ECM 04 2 TiO2 ESP ECM 05 ECM 06 2 ECM 07 2 ECM 08 2 ECM 09 T9600 TF21 1JS0 00 2 01 4 05 5 C 41 F 0 C 36 C 32 F 97 F 06 35 C 95 F 2 C 37 C 36 F 99 F 07 5 C 41 F 0 C 20 C 32 F 68...

Страница 12: ...O O O O O O O O O O O O O SJ T11364 GB T26572 GB T26572 SJ T11364 RoHS SJ T11364 1 E1 2 HI 55 3 LO 1 0 2 4 E5 8 E6 9 E7 BI T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 14 03 00 01...

Страница 13: ...or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable terms set forth at www johnsoncontrols com techterms Your use of this...

Отзывы: