T9600

P/N 24-11447-00004 Rev. B  Issue Date: 11 2020

English

USER SETTING

Press 

 and 

 button for 5 seconds at power off mode to get in parameter list. Press 

 to scroll forward and 

M

 button to scroll backward in 

the list and use 

 and 

 button to change parameter value. For T9603-T000-1JF0, press and hold 

 for 3 seconds to access the parameter 

list and press 

 to scroll foward through the list.

PARAMETER SETTING (PART 1/2)

Code

T9600- 

TF20-

1JS0

T9603- 

T000-

1JF0

T9601- 

TF20-

1JS0

T9600- 

TF21-

1JS0 Parameter name

Default Function

02

MAC (Modbus)

01

Mac address for Modbus 

1-96

04

MUTE

00

Enable/disable the beep when push touch button:

00: Disable

01: Enable

05

OFFSET

0°C/

0°F

Offset to be compensate the room temperature:  

Step: 0.5°C (1°F)”

Range: 5°C~-5°C (9°F- -9°F)

06

UNOCC-CLG-SP

26°C/

79°F

Cooling setpoint unoccupied mode. 

Not available for Boiler application

Step: 0.5°C (1°F)

Range: 22°C~32°C (72°F-90°F)

07

UNOCC-HTG-SP

18°C/

64°F

Heating setpoint unoccupied mode.

Step: 0.5°C (1°F)

Range: 10°C~21°C (50°F-70°F)

08

SMPL-TM

10 s

Sample time,

PID parameter, only for PID

Range: 1~99 s

09 

PB

5

Proportion band,

PID parameter, only for PID

Range: 1~10

10

KI

10

Integration parameter,

PID parameter, only for PID

Range: 0~99

11

BL-TIMER

30

Backlight timer.

Range: 0~99 s

12

PWR-F-RSTT

02

Restart after power failure:

00: OFF

01: ON

02: Recovery

13

TIO2ESP-CTL

00

TIO2ESP control: 

00: Automatic

01: Manual

For TIO2ESP application

15

BAUD_MODBUS

00

Baud rate for Modbus:

00: 9600

01: 4800

...Continued...

INSTRUCTIONS 

On/Off Setting: Press   to turn on, press again to turn off, close the fan and valve. 

Mode Selection: Press 

M

 to change the working mode,   for cooling,   for heating,   for venting,   for auto cooling or 

heating mode.   is available only for 4-pipe application or 2-pipe application when BI-FUNCTION is Change Over Sensor 

input. 

Temperature Setting: Press either   or   button to increase or decrease the temperature by 0.5°C/1°F. 

Fan Speed Adjustment: Press   to switch the fan mode, auto 

 flash, high 

, medium  , low   fan. 

Note: Fan stops at Floor Heating Mode, until FH-FAN parameter set to enable, for single stage floor heating application only. 

Delay On/Off setup: Press and hold   button 5 seconds, then “ON” appears, press   button to switch On or Off delay, 

then press   or   to adjust the minute by 30 minutes. 

Note: Time-On/Off setting performs only once within one day. 

Delay On/Off Cancel: Press and hold   button 5 seconds, then “ON” appears, press   button to switch to check On or Off 

delay time, then press   or   adjust the time to “00:00”. 

Lock setup: If   Lock function is enabled, the thermostat locks automatically after 30 seconds unused.

 

Unlock function: Press and hold the   button 5 seconds to unlock. T9603-T000-1JF0 has no   button, press and hold the 

 button 5 seconds to unlock instead. 

Tio2/ESP Manual: When Tio2/ESP function is set to Manual, press   button once, to switch Tio2/ESP On or Off.

Содержание T9600

Страница 1: ...rademarks of Johnson Controls All other marks herein are the marks of their respective owners Copyright 2020 Johnson Controls All rights reserved Any unauthorized use or copying is strictly prohibited...

Страница 2: ...Med FAN 2 pipe 3 wire relay 2 3 L N L N 100 240 VAC 50 60Hz TiO2 ESP GND MODBUS NTC OCC B A COM V2 V1 Low Hi Med FAN 2 pipe FCU relay with TiO2 ESP 2 TiO2 ESP Cool Heat L N L N 100 240 VAC 50 60Hz FLO...

Страница 3: ...BUS NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2 COOL HEAT 0 10 V ECM FAN V3 2 pipe 3 wire relay with ECM fan 2 ECM GND NTC OCC COM L N L F ON B A GND N 100 240 VAC 50 60Hz FAN V1 V2...

Страница 4: ...AN AO1 M FLOOR HEAT L N V1 V2 V3 Cool Heat 2 pipe FCU prop with radiator and ECM fan 2 ECM MODBUS NTC OCC COM L N F ON B A GND 100 240 VAC 50 60Hz ECM FAN FAN AO1 M HEAT COOL GND L N V1 V2 V3 AHU MODB...

Страница 5: ...system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the T9 Series thermostat...

Страница 6: ...TIO2ESP CTL 00 TIO2ESP control 00 Automatic 01 Manual For TIO2ESP application 15 BAUD_MODBUS 00 Baud rate for Modbus 00 9600 01 4800 Continued INSTRUCTIONS On Off Setting Press to turn on press again...

Страница 7: ...foward through the list PARAMETER SETTING PART 1 2 Code T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 Parameter name Default Function 02 FRST PRT 00 Frost protection 00 No 01 Yes 03...

Страница 8: ...C 0 F 18 F 11 HTRSS 1 C 2 F Hysteresis for ON OFF control Range 1 5 12 1 BI FUNCTION 02 00 Occupancy Input 01 Dew Point Risk Input 02 Filter Alarm Input 03 Change Over Sensor Input 04 Warning 13 MODE...

Страница 9: ...T9600 P N 24 11447 00004 Rev B Issue Date 11 2020 T9000 T9000 T9000 T9000 T9000 PCB PCB T9000 LCD M A B C D E A B C D E F G Tio2 ESP H I J K L M N O P Q R S T9600...

Страница 10: ...5 C 5 C 9 F 9 F 06 26 C 79 F 0 5 C 1 F 22 C 32 C 72 F 90 F 07 18 C 64 F 0 5 C 1 F 10 C 21 C 50 F 70 F 08 10 s 1 99 s 09 PB 5 1 10 10 KI 10 0 99 11 30 0 99 s 12 02 00 01 02 13 TiO2 ESP 00 00 01 15 00...

Страница 11: ...01 4 ECM 02 2 ECM 03 2 ECM 04 2 TiO2 ESP ECM 05 ECM 06 2 ECM 07 2 ECM 08 2 ECM 09 T9600 TF21 1JS0 00 2 01 4 05 5 C 41 F 0 C 36 C 32 F 97 F 06 35 C 95 F 2 C 37 C 36 F 99 F 07 5 C 41 F 0 C 20 C 32 F 68...

Страница 12: ...O O O O O O O O O O O O O SJ T11364 GB T26572 GB T26572 SJ T11364 RoHS SJ T11364 1 E1 2 HI 55 3 LO 1 0 2 4 E5 8 E6 9 E7 BI T9600 TF20 1JS0 T9603 T000 1JF0 T9601 TF20 1JS0 T9600 TF21 1JS0 14 03 00 01...

Страница 13: ...or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable terms set forth at www johnsoncontrols com techterms Your use of this...

Отзывы: