background image

601V-B02A-NC Rev 4-Issue Date 11 2012

T6634-TE21/22 LCD Digital Fan Coil Thermostat (Modulating/Floating) - Installation Instructions

T6634-TE21/22 

液晶数字式风机盘管温控器

 (

调节型

/

浮点型

) -

安装说明

  Up/Down (

& ) Adjustment Button

  To adjust the Temperature Setpoint, simply pressing the 

 and   button, allows 5-seconds 

for setting to take effect. After 5-seconds without further adjustment, the screen returns by 
displaying the ambient temperature.

  Fan ( ) Speed Button

 

Cooling or Heating Mode Operation

  T66-TE/, has  speeds fan control (No Fan Stop); Auto (

), High (

), Middle (

), 

Low (

) fan. Short press the ( ) button switches through the sequence. The selected icon will 

flash, the icon is selected after 5 seconds. The selected icon appears highlighted on the LCD. 

 

Fan only Operation

  T66-TE/, has  speeds fan control; High (

), Middle (

), Low (

) fan. Short 

press the ( ) button switches through the sequence. The selected icon will flash, the icon is 
selected after 5 seconds. The selected icon appears highlighted on the LCD.

  Note: 

Every time switch On the T6000 Series thermostat, the low speed fan will be initiated. 

These soft-start feature prevent high startup current, while provides energy saving to 
electricity consumption. After -seconds, the required fan speed will be started.

 

Remote Temperature sensor(T6634-TE21-9JR0) 

  When remote sensor is connected, the built-in sensor will be disable.

 

/

 (

▲和

调节按钮

 

调节温度设定点

仅需按▲和 按钮

, 5

秒内设置有效。

5

秒后还没有输入调节,屏幕将

返回显示环境温度。

 

风机

 ( ) 

速度按钮

 

制冷、制热模式操作

  T66-TE/

温控器有

种风机速度(没有风机停),自动

 (

), 

 (

), 

 (

), 

 (

风速。按

 ( ) 

按钮,将循环显示。被选的模式图标闪烁,

5s

后自动确认图标被

选中,选定后图标将不再闪烁,正常显示在屏幕上。

 

仅风机操作

  T66-TE/

温控器有

种风机速度,高

 (

), 

 (

), 

 (

风速。按

 ( ) 

钮,将循环显示。被选的模式图标闪烁,

5s

后自动确认图标被选中,选定后图标将不

再闪烁,正常显示在屏幕上。

 

注意

每一次开关

T6000

系列温控器,开始时都将启动低速风机。这一软启动特点防

止了高启动电流,同时节约了用电,

秒以后,风机按设定运转。

 

外接温度传感器(

T6634-TE21-9JR0

 

当温控器接上外置传感器时,内置

NTC

传感器自动失效。

1/Table1: 

T66-TE-9JS0, T66-TE-9JS0, T66-TE-9JR0

注:

T66-TE-9JR0 

没有

Unoccupied/

有人

/

无人模式

2: 

T66-TE/

系列工厂设置

Table2: 

 T66-TE/ Series Factory Settings

:T66-TE-9JR0

没有第

7

项和第

8

 

设定差值

 

在关机状态下按

 M 

 

 

键待

   

符号出现,再按

   

键,进入运行参数设置状态。

   

键切换功能, 或▲调整相对应功能的参数,功能含义见表

。(调整时慢些进

行,尤其在按

   

键时,不能在一秒钟内按一次以上)

 

标定

 

    T6000

系列温控器不需现场标定。

 

故障检修

 

电源中断,温控器模式和所有设置回到最近使用和设置过的状态。

 

维修和替换

 

不要试图现场维修

T6000

系列温控器。如果温控器不能正常工作,请与附近

Johnson 

Controls

®

 

办事处联系。当联系办事处更换产品的时候,请说明外部标签或参数表上

印有的类型

/

型号。

  Setting Parameter

  To enable the operation mode, hold down the 

M

 and 

 till   icon appears when the 

thermostat is turned off, after which press   . Press   to switch functions, press 

 or 

 

to adjust the parameter. 

See Table  for the functions.

Slowly press the key, only pressing 

once is allowed in s when press   

  Calibration

  Do not calibrate the T6000 Series thermostat in the field.

  Troubleshooting

  After a power outage, the thermostat mode and all settings return as most recently used or 

set.

  Repair and Replacement

  Do not attempt to repair the T6000 Series thermostat. In case of an improperly functioning 

control, contact the nearest Johnson Controls

®

 representative, and specify the desired product 

code number. When contacting the supplier for a replacement please state the type/model 
number of the control located on the data plate or cover label.

Function / 

功能

Icon / 

图形

Cool Mode / 

制冷模式

Heat Mode / 

加热模式

Fan only Mode / 

仅风机

Unoccupied / 

有人

/

无人模式

功能

Function

出厂设置

Factory 

setting

设定范围

Setting range

失电重启

Restart when power failure

1  00

00

:关闭

 01 

开启

 02

:恢复到断电前状态

00: OFF 01: ON 02: Recover to previous status

设定温度上限值范围

Max.Temp setpoint range

2  30

下限~

30

/Min. temp

30

设定温度下限值范围

Min.Temp setpoint range

3  05

5

℃~上限

/5

℃~

Max. temp

房间温度与设定温度显示选择

Display room temp or set temp

4  00 

0: Room Temp

1: Set Temp

温度校准

 Temp differential 

5  00

-5

5

℃(

-9

9

);

°C/°F

6  00 

0: 

℃;

1: °F

无人模式制冷温度

Unoccupied Temp Setpoint cooling

7  28

23-30

无人模式制热温度

Unoccupied Temp Setpoint 

heating

8  18

16-23

Stime

9  01

1-99s

ZBAND

A  0.3

0.0-9.9

KP

B  10

1-99

KI

C  01

0-99

KD

D  00

0-99

低温保护设置

Low temp protection setting

E  00

00

:低温保护关闭。

 Protection OFF

01

:低温保护开启。

Protection ON

(仅用于

T6634-TE21-9JS0

T6634-TE21-9JR0/

Only T6634-TE21-9JS0 and T6634-TE21-9JR0

最小开度设置

Min. position

E  00

0-30%  

(仅用于

T6634-TE22-9JSO

              (Only for T6634-TE22-9JSO)

正反转定义

CW or CCW

F  00

0: 

逆时针开,顺时针关;

 1: 

逆时针关,顺时针开

   

  

(仅用于

T6634-TE22-9JSO

0: CCW for open  1: CW for open

  

Only for T6634-TE22-9JSO

总行程时间设置

 Running time

L   80

30-160s

(仅用于

T6634-TE22-9JSO

               (Only for T6634-TE22-9JSO)

低温保护设置

Low temp protection setting

H  00

00

:低温保护关闭。

 Protection OFF

01

:低温保护开启。

Protection ON

(仅用于

T6634-TE22-9JS0/only for T6634-

TE22-9JS0

Отзывы: