background image

ECOTIMER M Floor temperature controller

HRT 6145-50

+

_

M C

1 2 3 4 5 6 7

Setting range approx.

10 to 40°C

Mains voltage:

230 V ~ ± 10% , 50 Hz

Switching current (max.) approx.

12 (4) A

Switching capacity

2.7 kW

Switch temperature differential:

0.7 K

Temperature sensor:

NTC to DIN 44574
4 m long

Perm. ambient temperature:

-10 to +40°C

Connection cables:

2.5 mm

2

Energy class:

VII = 3.5%

Function

ECOTIMER M is a 10 to 40 °C floor temperature controller with a timer. It enables one or two heating times a day.
Example of one heating time: 6:00 to 22:00 for a living room, Example of two heating times: 6:00 to 9:00 and 17:00 to
22:00 for a bathroom. The reduced heating times with the setback temperature are in between. The set floor temperature
is shown as a ramp at the bottom of the display. It can be changed at any time during heating times by pressing the

+

or

buttons. It is also displayed as a numerical value. The actual room temperature is shown as a numerical value on the
display. The setback temperature by which the controller reduces the set floor temperature is programmed once. The
timer can be switched off, and this causes the device to constantly regulate the heating temperature (continuous
operation).

The M button (=Mode) is pressed to set the following operating modes:

Off

(empty circle shown on left of display)

Continuous operation

(circle with centre displayed on left of display)

Timer

(clock symbol displayed on left of display)

Freeze stop is active in all operating modes (also in Off mode) and prevents the floor temperature from going below 5°C.

The device has the following factory settings for the timer and the setback temperature:

Setback temperature

(temperature value by which the set temperature is reduced during the setback time) 3° C

Start of 1st heating time

6:00 each day

End of 1st heating time

22:00 each day

No second heating time

.

Simultaneously pressing

M

and

C

resets the device to these factory settings regardless of the current operating mode.

Connecting and commissioning

ATTENTION

: Work on the 230 V mains supply must only be carried out by authorised electricians. When connecting the

device, the safety regulations of the VDE (German Association for Electrical, Electronic & Information Technologies) and
the local utility companies must be observed. “Normally closed” valves are required for controlling hot water heating.

L N PE

TANN L L1

TA (not assigned)

Heating

Floor temperature sensor

.

Mounting

: The temperature controller is mounted in a standard Ǿ 55 mm conduit box 

(to DIN 49073, part 1). When using additional intermediate terminals, use of a deep
conduit box is recommended. The device is connected according to the circuit diagram
shown. The connection cables must be straight and must be stripped by approx. 5 mm.
Mounting height approx. 1.5 m above the floor. Attention! Fit the support ring above the
wallpaper and mount the controller on the conduit box using the self-tapping screws.
Then place the frame on the conduit box.

Attention:

Before pushing on the cover plate, ensure that the internal sensor (bottom

left) is pointing diagonally downwards. The sensor should not touch the controller
housing. The floor temperature sensor must be laid in a protective tube at heating mat
level in the centre between the heating mats. The sensor cable must be laid in a
separate protective tube and must not be laid together with the power supply cables

Danger:

Avoid electric shock. Be aware that in the event of a fault, the power

may be present on the sensor line. may be present on the sensor line.