background image

T500 Series Programmable Thermostats Product/Technical Bulletin    

15

Mode

Repeated pressing of the 

Mode

 button allows

selection from four modes of operation (five for the
T500HPP-1/Heat Pump model):

 When 

the 

Snowflake

   and the word 

COOL

 are

displayed, the thermostat is in the cooling mode.
When the thermostat is calling for cooling, the
snowflake will flash.

 When 

the 

Flame

   and the word 

HEAT

 are

displayed, the thermostat is in the heating mode.
When the thermostat is calling for heating, the
flame will flash.

 When 

the 

Flame

   and 

E Ht

 (emergency heat)

are displayed, the thermostat will control using the
emergency heat with the compressor locked out.
(T500HPP-1/Heat Pump only.)

 When 

the 

Snowflake   

and the

 Flame   

symbols

and word 

AUTO

 are displayed, the thermostat will

automatically change over between heating and
cooling.

Note:

The thermostat never allows less than a 1

°

C

(2

°

F) difference between the heating and

cooling setpoints.

 When 

OFF

 is displayed, the equipment will not

operate.

Note:

Use caution when using the 

OFF

 mode in

extremely cold weather.

Celsius/Fahrenheit

Press the 

∨∨∨∨

 

and

 

∧∧∧∧

 

buttons simultaneously to alternate

between Celsius and Fahrenheit display.

F

uzzy Logic Control

Over time, the T500 learns how long it takes the
system to meet the load. If the system can change the
room temperature quickly, the T500 allows the
thermostat to drift further from setpoint before starting
the equipment. If the system takes a longer period of
time to change the room temperature, it will not allow
the temperature to drift as far from setpoint. The T500
also takes into account the minimum On/Off times.
The 2-minute On/Off time allows the equipment to
cycle more frequently at smaller differentials than the
4-minute On/Off time. For multi-stage applications, the

T500 does not bring on the next stage of cooling or
heating if it knows that the system can change the
temperature by 6 degrees in 1 hour, or 1 degree in
10 minutes. To verify thermostat

 

operation, force the

next stage on by changing the setpoint

 

more than

2 degrees.

F

an 

If continuous fan is not selected, the fan will operate
automatically and the fan symbol will be off. To select
continuous fan operation, press the Fan button. The
fan symbol 

 will be displayed. (See Figure 20.) See

Smart Fan DIP switch in Table 1.

Mode

Clock

Set Temp 

Outdoor

Fan

Program

Resume

Hold

66

4:22

Mo

AM

Press to
select 
continuous
fan 
operation.

Figure 20: Selecting Continuous Fan Operation

Outdoor Button

When an outdoor temperature sensor (order
separately) is connected to the T500 thermostat, you
can display the current outdoor temperature by
pressing the 

Outdoor

 button. If the sensor option is

not connected, the thermostat will display “— —”.

See the 

Ordering Information

 section.

Содержание T500HCP-1

Страница 1: ...and installation is simple and fast for reduced cost Figure 1 T500 Series Programmable Thermostats Features and Benefits Low Profile Design Complements any decor No Batteries Required Retains schedule...

Страница 2: ...t power supply before wiring connections are made to prevent electrical shock or possible damage to the equipment Installation and Wiring Note When replacing an existing thermostat remove and use wire...

Страница 3: ...CAUTION Equipment Damage Hazard Before applying power make all wiring connections and check the connections Short circuited or improperly connected wires may result in permanent damage to the unit Fig...

Страница 4: ...locking mechanism press the lock piece up and into the base while gently prying open the thermostat at the same time Use caution to avoid cracking the thermostat base or cover Thermostat Base Plastic...

Страница 5: ...d of the night event Smart Fan remembers the fan selection automatic cycling or continuous fan for the morning day and evening events and reverts back Off Allows the fan to cycle with equipment or run...

Страница 6: ...4 5 2 Events Per Day Smart Fan Enabled Heat Cool 2 Minute Minimum On Keyboard Locked Fan Immediate with Heat Call Fan On with Plenum Switch Figure 7 T500HCP 1 Factory Set DIP Switch Settings All Off...

Страница 7: ...t mode Y2 Energizes compressor No 2 on call for second stage heating or cooling W1 Energizes auxiliary heat as last stage heating or first stage in emergency heat Y1 Energizes compressor No 1 on call...

Страница 8: ...eating See Note Y1 Energizes compressor contactor See Note Energizes on call for cooling See Note G Energizes fan on call for heating or cooling or by pressing Fan button R Independent switching volta...

Страница 9: ...Designations Terminal Function W2 Energizes on a call for second stage heat Y2 Energizes on a call for second stage cooling W1 Energizes on a call for first stage heat Y1 Energizes on a call for firs...

Страница 10: ...2 RS V RS1 RS2 Remote Sensor if used Thermostat Equipment Electronics If the transformer T2 is to power all of the loads R and 24 must be connected by inserting jumper J 1 located above the relays If...

Страница 11: ...2 Field contact switches 2nd Stage Compressor Electronics COM OCC all other events NO NC COM UNOCC night event if thermostat loses power NO NC Thermostat Equipment Hpp 1diag If the transformer T2 is t...

Страница 12: ...en W1 and Y1 and wire O or B as shown Conventional Single Stage Heat Cool between W1 and Y1 and wire as shown in Figure 12 Note that the O and B terminals are not used in this application If the trans...

Страница 13: ...cs COM OCC events NO NC COM UNOCC night event or if thermostat NO NC Thermostat Equipment Reverse Valve If the transformer T2 is to power all of the loads R and 24V must be connected by inserting jump...

Страница 14: ...e heat is activated internally controlled Right An external switch on the LED 1 Display enables the wrench symbol see Table 1 Thermostat Operation Overview Mode Clock Set Temp Outdoor Fan Program Resu...

Страница 15: ...system can change the room temperature quickly the T500 allows the thermostat to drift further from setpoint before starting the equipment If the system takes a longer period of time to change the roo...

Страница 16: ...ontrol the temperature according to the setpoint of the latest event Table 7 is an example of event times and setpoints for a given week using a 4 event program See the owner s manual for a blank tabl...

Страница 17: ...s the Mode button until heat is displayed 2 Press the Set Temp button The mode heat or cool event morning day evening or night symbols and the present setpoint will be displayed 3 Press the or buttons...

Страница 18: ...rogram settings to the selected days of the week 9 Repeat the procedures for Setting the Event Times for any remaining unprogrammed days of the week 10 When finished verify that all events are program...

Страница 19: ...d Unlocked To implement a temporary change from the current event setpoint for a 3 hour period 1 Press the or buttons to change the scheduled setpoint 3 C or 6 F The current mode of operation will app...

Страница 20: ...able 10 Optional Accessories Power Failures If power fails AC will be displayed for 2 hours After 2 hours the display will go blank If power is restored in the first 2 hours the internal clock will be...

Страница 21: ...nsformer of the proper rating Keyboard inoperative Keyboard locked Switch the keyboard DIP switch to the unlocked position Thermostat will not call for heat Compressor delay still in progress Wait equ...

Страница 22: ...unt Sensor SEN 500 3 Conversion Module ACC 500 1 Thermostat Wall Plate ACC 500 2 Replacement and Repair Parts The SEN 500 series of products allows for easy replacement of the sensor For a replacement...

Страница 23: ...d T500MSP 1 only Single Pole Double Throw The normally open contact is closed in the night event or if the thermostat loses power The normally closed contact is closed in all other events Thermostat M...

Страница 24: ...ipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense The performance specifications are nomin...

Отзывы: