T500 Series Programmable Thermostats Product/Technical Bulletin
DIP Switch
(Cont.)
Switch
Selection
Description
6
On
T500HPP-1, T500MSP-1 only:
Allows multi-stage heating or cooling.
Off
T500HPP-1, T500MSP-1 only:
Allows single-stage heating or cooling.
7
LED 1 icon
off/on
(See Table 5.)
T500HPP-1, T500MSP-1 only:
Optional selection: LCD icon comes on with LED 1.
8
LED 2 icon
off/on
(See Table 5.)
T500HPP-1, T500MSP-1 only:
Optional selection: LCD icon comes on with LED 2.
4 Events Per Day
Smart Fan Disabled
Heat/Cool: 4 Minute
(Minimum On)
Keyboard Unlocked
O
N
1
3
2
4
5
2 Events Per Day
Smart Fan Enabled
Heat/Cool: 2 Minute
(Minimum On)
Keyboard Locked
Fan Immediate
with Heat Call
Fan On with
Plenum Switch
Figure 7: T500HCP-1 Factory-Set DIP Switch
Settings (All Off)
RS2
RS1
W1
Y1
G
R
24V
24V(c)
Heating
Cooling
Fan
Common
Hcp-1wire
RS+V
Figure 8: T500HCP-1 Wiring Terminals
Table 2: T500HCP-1 Output Terminal
Designations
Terminal
Function
W1
Energizes on call for heating
Y1
Energizes on call for cooling
G
Energizes fan on call for heating or
cooling or by pressing
Fan
button
R
Independent switching voltage
24V
24 VAC from equipment transformer
24V(c)
24 VAC (common) from equipment
transformer
RS2
RS1
RS+V
Connections for outdoor air
temperature or indoor remote
sensors; refer to instructions included
with sensors.