Johnson Controls T-5800 Series Скачать руководство пользователя страница 9

T-5800-3/T-5800-4 Technical Bulletin    9

in order for the system to have
normal proportional plus integral
control.

The T-5800-4 has an
automatic/manual integral
control cutout feature when the
fan “F” connection is used.  This
feature keeps the system from
going out of control on startup
(after it’s been off for some time)
by allowing the system to start
up using proportional-only
control.  If it is determined that
there is not a need for the cutout
feature, cap the unused fan “F”
connection.  Doing so will allow
normal proportional plus integral
control of the system at all
times, provided that the P/PI
jumper is connected.

With the supply air ON, balance
the receiver-controller by setting
the following:

Pull the P/PI jumper off of its

spigot so that the receiver-
controller will operate as a
proportional-only controller
(no integral function).

Adjust the local set point dial

or the remote adjuster
(manual or automatic) to
produce 9 PSIG  (63 kPa)
using the appropriate
method and gage as
described previously.

Install the ratio selection

jumper in the correct position
(see Fig. 15).  If the
calculated ratio is less than
or equal to 2.5:1 (as is the
case with the example where
the calculated ratio is 2:1),
the jumper should be
installed in the 1:1 position.
If the calculated ratio is
greater than 2.5:1, the
jumper should be installed in
the 3:1 position.

Turn the ratio dial so that
“1:1 (3:1)” imprinted on the
dial lines up with the dial
reference point.

Receiver-Controller Preset
(See Example Fig. 6)

Utilize one of the pressure
checking methods described

previously to obtain a master “M”
input pressure reading, a master
balance “R” pressure reading,
and a controlled variable “CV”
input pressure reading.

1.

Apply a master “M” input
pressure equal to the
midpoint of the desired
working range (Example:
30

°

F on a 0 to 60

°

F working

range or 7.2 PSIG as
highlighted in Fig. 12).

2.

Rotate the master balance
screw (see Fig. 10) located
in the center of the receiver-
controller (clockwise to
increase or counterclockwise
to decrease) to produce a
9 PSIG (63 kPa) gage
reading at the master
balance “R” reference.
Doing so will shift the
working range (internally) to
a more linear portion of the
ratio circuit.

3.

Vary the master input from
minimum to maximum over
its working range (Example:
0 to 60

°

F or 5.4 to 9 PSIG

per Fig. 6).  Note:  The
master “M” INPUT is
limited to not less than
2 PSIG nor greater than
17 PSIG.
  Note the pressure
readings at the master
balance “R” reference
corresponding to these
minimum and maximum
points.

If the minimum master
balance “R” pressure noted
above is greater than or equal
to 5 PSIG and the maximum
master balance “R” pressure
is less than 19 PSIG (with a
20 PSIG supply), no further
adjustments are required.  If
the minimum master balance
“R” pressure is less than
5 PSIG, rotate the master
balance screw (clockwise to
increase) so that the minimum
pressure is greater than
5 PSIG and the maximum
does not exceed 19 PSIG.

4.

After removing the pressure
checking method from the
master balance “R”
reference, it is suggested
that the master balance
screw be sealed (using) a

small dab of fingernail
polish).

5.

Return the master “M” input
pressure to the midpoint of
the desired working range
(Example: 30

°

F or 7.2 PSIG

on a 0 to 60

°

F working

range per Fig. 6).

6.

Apply a controlled variable
“CV” input pressure to the
value corresponding to the
7.2 PSIG master “M” input
setting (Example:  140

°

F or

9 PSIG per Fig. 6).

7.

Rotate the ratio dial (see
Fig. 13) to a position which
most closely represents the
required ratio setting
(Example:  2:1, outer scale
on dial and jumper in
1:1 position).

8.

Adjust the local set point dial or
the remote adjuster (manual or
automatic) to produce an
output pressure on the
controller gage equal to the
midpoint of the spring range of
the controlled device.

Ratio and Set Point Checkout

1.

Apply the minimum master
“M” input pressure value
(Example:  0

°

F or 5.4 PSIG

per Fig. 6).

2.

Apply the corresponding
controlled variable “CV”
input pressure value
(Example:  200

°

F or

12.6 PSIG per Fig 6).

3.

Ratio Dial Adjustment:

Note:  Never adjust the ratio
dial when the master “M”
Input pressure is at the
midpoint of its working
range (Example:  30

°

F on a

0 to 60

°

F range or 7.2 PSIG

per Fig. 12).  No output
signal change will occur
because the internal ratio
circuitry is in a balanced
condition, and any previous
ratio dial setting (if not
marked) will be lost.

Adjust the ratio dial to cause
the receiver-controller
output to be at the midpoint

Содержание T-5800 Series

Страница 1: ...he T 5800 4 design Utilizing the fan F connection this feature allows the system to start up using proportional only control thus keeping the system from going out of control on startup as is inherent to PI automatic reset controllers when the system has been off for some time Refer to Product Data T 5800 for instrument specifications and additional details Installation The T 5800 Series Receiver ...

Страница 2: ... can be changed by interchanging the placement of the tube ends from one lower spigot to the other lower spigot see Figs 4 11 and 15 Each dual input T 5800 is furnished with a double 007 in orifice jumper and three yellow spigot caps see Fig 5 The orifice jumper provides a restricted source of supply to low volume non relay type transmitters For best results it is recommended that this jumper be u...

Страница 3: ...vice to the set point SP connection of the snap on input output connector A low volume restricted source of supply air less than 005 in orifice is automatically furnished therefore use 75 of the overall line length that is recommended for a 005 in orifice FC and PRV Test Points The FC and PRV test points and their associated adjustments are for FACTORY USE ONLY Supply Air Interruptions Both dual i...

Страница 4: ...4 T 5800 3 T 5800 4 Technical Bulletin Fig 8 X 200 173 Calibration Kit Fig 9 X 200 140 Test Probe with X 200 180 Series Transmission Gage and F 500 42 Adapter ...

Страница 5: ...ster manual or automatic to produce 9 PSIG 63 kPa using the appropriate method and gage as described above Turn the gain dial clockwise so that the word INCREASE imprinted on the dial is centered with the dial reference point Install the ratio selection jumper in the correct position see Fig 11 If the calculated ratio is less than or equal to 2 5 1 as is the case with the example where the calcula...

Страница 6: ...60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum master balance R pressure noted above is greater than or equal to 5 PSIG and the maximum master balance R pressure is less than 19 PSIG with a 20 PSIG supply ...

Страница 7: ...which would produce the required 200 F 4 Apply the maximum master M input pressure value Example 60 F or 9 PSIG per Fig 6 5 Apply the corresponding controlled variable CV input pressure value Example 80 F or 5 4 PSIG per Fig 6 6 Set Point dial Adjustment Adjust the set point dial to cause the output pressure to be at the opposite end of the spring range of the controlled device Example Direct Acti...

Страница 8: ...8 T 5800 3 T 5800 4 Technical Bulletin ...

Страница 9: ...e working range internally to a more linear portion of the ratio circuit 3 Vary the master input from minimum to maximum over its working range Example 0 to 60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum m...

Страница 10: ...no further adjustments will be required If the control point does not stabilize at the set point value or if excessive cycling occurs proceed to the Integral Time Adjustment section Integral Time Adjustment See Figs 17 18 Adjusting the integral time dial will not affect the controller set point If the system response toward the set point is too slow decrease the integral time and or increase the g...

Страница 11: ...the P PI jumper must be disconnected and left vented for a period of time equal to the integral time dial setting Start up the system and reconnect the P PI jumper when the system becomes stable T 5800 100 Time Delay When Fan F Connection is Used After system startup if the system response is too slow the integral control function will act on the signal before the proportional control function set...

Страница 12: ...12 T 5800 3 T 5800 4 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Printed in U S A Milwaukee WI 53202 ...

Отзывы: