T-5800-3/T-5800-4 Technical Bulletin    5

representative equipped with the
proper tools.  An X-200-173
Calibration Kit (see Fig. 8,
ordered separately) is available
for making adjustments and
pressure checks on the T-5800.
This kit provides all of the
necessary gages, regulators,
and connectors for a more
convenient and quicker
calibration procedure.

An X-200-140 Hypodermic
Needle Test probe and
appropriate gage (see Fig. 9,
ordered separately) is also
available for troubleshooting,
test point readings, or final set
point adjustments under actual
job conditions.  Note:  Figure 10
illustrates an alternative
method of checking pressure
readings on the T-5800 where
use of a hypodermic needle
test probe is prohibited.

Calibrating the T-5800-3
(See Fig. 11)

With the supply air ON, balance
the receiver-controller by setting
the following:

Adjust the local set point dial

or the remote adjuster
(manual or automatic) to
produce 9 PSIG (63 kPa)
using the appropriate
method and gage as
described above.

Turn the gain dial clockwise

so that the word
“INCREASE” imprinted on
the dial is centered with the
dial reference point.

Install the ratio selection

jumper in the correct position
(see Fig. 11).  If the
calculated ratio is less than
or equal to 2.5:1, (as is the
case with the example where
the calculated ratio is 2:1),
the jumper should be

installed in the 1:1 position.

If the calculated ratio is
greater than 2.5:1, the
jumper should be installed in
the 3:1 position.

Turn the ratio dial so that
“1:1 (3:1)” imprinted on the
dial lines up with the dial
reference point.

Receiver-Controller Preset
(See Example Fig. 6)

Utilize one of the pressure
checking methods described
previously to obtain a master “M”
input pressure reading, a master
balance “R” pressure reading,
and a controlled variable “CV”
input pressure reading.

1.

Apply a master “M” input
pressure equal to the
midpoint of the desired
working range (Example:
30°F on a 0 to 60°F working
range or 7.2 PSIG as
highlighted in Fig. 12).

Содержание T-5800 Series

Страница 1: ...he T 5800 4 design Utilizing the fan F connection this feature allows the system to start up using proportional only control thus keeping the system from going out of control on startup as is inherent to PI automatic reset controllers when the system has been off for some time Refer to Product Data T 5800 for instrument specifications and additional details Installation The T 5800 Series Receiver ...

Страница 2: ... can be changed by interchanging the placement of the tube ends from one lower spigot to the other lower spigot see Figs 4 11 and 15 Each dual input T 5800 is furnished with a double 007 in orifice jumper and three yellow spigot caps see Fig 5 The orifice jumper provides a restricted source of supply to low volume non relay type transmitters For best results it is recommended that this jumper be u...

Страница 3: ...vice to the set point SP connection of the snap on input output connector A low volume restricted source of supply air less than 005 in orifice is automatically furnished therefore use 75 of the overall line length that is recommended for a 005 in orifice FC and PRV Test Points The FC and PRV test points and their associated adjustments are for FACTORY USE ONLY Supply Air Interruptions Both dual i...

Страница 4: ...4 T 5800 3 T 5800 4 Technical Bulletin Fig 8 X 200 173 Calibration Kit Fig 9 X 200 140 Test Probe with X 200 180 Series Transmission Gage and F 500 42 Adapter ...

Страница 5: ...ster manual or automatic to produce 9 PSIG 63 kPa using the appropriate method and gage as described above Turn the gain dial clockwise so that the word INCREASE imprinted on the dial is centered with the dial reference point Install the ratio selection jumper in the correct position see Fig 11 If the calculated ratio is less than or equal to 2 5 1 as is the case with the example where the calcula...

Страница 6: ...60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum master balance R pressure noted above is greater than or equal to 5 PSIG and the maximum master balance R pressure is less than 19 PSIG with a 20 PSIG supply ...

Страница 7: ...which would produce the required 200 F 4 Apply the maximum master M input pressure value Example 60 F or 9 PSIG per Fig 6 5 Apply the corresponding controlled variable CV input pressure value Example 80 F or 5 4 PSIG per Fig 6 6 Set Point dial Adjustment Adjust the set point dial to cause the output pressure to be at the opposite end of the spring range of the controlled device Example Direct Acti...

Страница 8: ...8 T 5800 3 T 5800 4 Technical Bulletin ...

Страница 9: ...e working range internally to a more linear portion of the ratio circuit 3 Vary the master input from minimum to maximum over its working range Example 0 to 60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum m...

Страница 10: ...no further adjustments will be required If the control point does not stabilize at the set point value or if excessive cycling occurs proceed to the Integral Time Adjustment section Integral Time Adjustment See Figs 17 18 Adjusting the integral time dial will not affect the controller set point If the system response toward the set point is too slow decrease the integral time and or increase the g...

Страница 11: ...the P PI jumper must be disconnected and left vented for a period of time equal to the integral time dial setting Start up the system and reconnect the P PI jumper when the system becomes stable T 5800 100 Time Delay When Fan F Connection is Used After system startup if the system response is too slow the integral control function will act on the signal before the proportional control function set...

Страница 12: ...12 T 5800 3 T 5800 4 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Printed in U S A Milwaukee WI 53202 ...

Отзывы: