Johnson Controls T-5800 Series Скачать руководство пользователя страница 7

T-5800-3/T-5800-4 Technical Bulletin    7

4.

After removing the pressure
checking method from the
master balance “R”
reference, it is suggested
that the master balance
screw be sealed (using a
small dab of fingernail
polish).

5.

Return the master “M” input
pressure to the midpoint of
the desired working range
(Example: 30

°

F or 7.2 PSIG

on a 0 to 60

°

F working

range per Fig. 6).

6.

Apply a controlled variable
“CV” input pressure to the
value corresponding to the
value 7.2 PSIG master “M”
input setting (Example:
140

°

F or 9 PSIG per Fig. 6).

7.

Rotate the ratio dial (see
Fig. 13) to a position which
most closely represents the
required ratio setting
(Example:  2:1, outer scale
on dial and jumper in 1:1
position).

8.

Adjust the local set point
dial or the remote adjuster
(manual or automatic) to
produce an output pressure
on the controller gage equal
to the midpoint of the spring
range of the controlled
device.

Ratio and Set Point Checkout

1.

Apply the minimum master
“M” input pressure value
(Example:  0

°

F or 5.4 PSIG

per Fig. 6).

2.

Apply the corresponding
controlled variable “CV”
input pressure value
(Example:  200

°

F or

12.6 PSIG per Fig 6).

3.

Ratio Dial Adjustment:

Note:  Never adjust the
ratio dial when the master
“M” Input pressure is at
the midpoint of its
working range (Example:
30

°

F on a 0 to 60

°

F range

or 7.2 PSIG per Fig. 12).
No output signal change

will occur because the
internal ratio circuitry is in
a balanced condition, and
any previous ratio dial
setting (if not marked) will
be lost.

Adjust the ratio dial to cause
the receiver-controller
output to be at a pressure
value which would produce
the required controlled
variable “CV” input
(Example:  Direct acting T-
5800-3, N.O. heating valve
with a 3 to 7 PSIG spring
range; output should be
below the midpoint of the
spring range of the valve
which would produce the
required 200

°

F).

4.

Apply the maximum master
“M” input pressure value
(Example:  60

°

F or 9 PSIG

per Fig. 6).

5.

Apply the corresponding
controlled variable “CV”
input pressure value
(Example:  80

°

F or

5.4 PSIG per Fig. 6).

6.

Set Point dial Adjustment:

Adjust the set point dial to
cause the output pressure
to be at the opposite end of
the spring range of the
controlled device (Example:
Direct Acting T-5800-3, N.O.
heating valve with a
3 to 7 PSIG spring range;
output should be above the
midpoint of the spring range
of the valve which would
produce the required 80

°

F).

7.

Rotate the gain dial so that
“10:1” imprinted on the dial
lines up with the dial
reference point.

8.

The T-5800-3 is calibrated
and ready for system
operation.

Gain Adjustment (See Fig. 14)

Adjusting the gain dial will not
affect the controller set point;

however, the output pressure
may change when the gain dial
is adjusted.  Increasing the gain
will narrow the throttling range
(decrease offset), allowing the
control point to be closer to the
set point.  Decreasing the gain
will widen the throttling range,
forcing the control point away
from the set point.

Normally, having the gain arrow
set at the pointer represents a
reasonable gain adjustment
which would provide stability.
Increase the gain setting by
small increments until the
system becomes unstable and
begins to cycle.  Decrease the
gain setting slightly to remove
the cycling effect.  Doing so will
provide maximum controllability
with a minimum of offset.

Calibrating the T-5800-4
(see Fig. 15)

When connecting the T-5800-4
Receiver-Controller to an
operating system, the fan “F”
connection should either have
the “system in operation”
function signal (minimum of
12 PSIG) attached (example:
fan on-off or water circulation
pump on-off), or the connection
must be capped.

Pulling the P/PI jumper (see
Fig. 16) off of its spigot causes
the receiver-controller to operate
as proportional-only controller
(no integral function).  The
jumper must be connected

Содержание T-5800 Series

Страница 1: ...he T 5800 4 design Utilizing the fan F connection this feature allows the system to start up using proportional only control thus keeping the system from going out of control on startup as is inherent to PI automatic reset controllers when the system has been off for some time Refer to Product Data T 5800 for instrument specifications and additional details Installation The T 5800 Series Receiver ...

Страница 2: ... can be changed by interchanging the placement of the tube ends from one lower spigot to the other lower spigot see Figs 4 11 and 15 Each dual input T 5800 is furnished with a double 007 in orifice jumper and three yellow spigot caps see Fig 5 The orifice jumper provides a restricted source of supply to low volume non relay type transmitters For best results it is recommended that this jumper be u...

Страница 3: ...vice to the set point SP connection of the snap on input output connector A low volume restricted source of supply air less than 005 in orifice is automatically furnished therefore use 75 of the overall line length that is recommended for a 005 in orifice FC and PRV Test Points The FC and PRV test points and their associated adjustments are for FACTORY USE ONLY Supply Air Interruptions Both dual i...

Страница 4: ...4 T 5800 3 T 5800 4 Technical Bulletin Fig 8 X 200 173 Calibration Kit Fig 9 X 200 140 Test Probe with X 200 180 Series Transmission Gage and F 500 42 Adapter ...

Страница 5: ...ster manual or automatic to produce 9 PSIG 63 kPa using the appropriate method and gage as described above Turn the gain dial clockwise so that the word INCREASE imprinted on the dial is centered with the dial reference point Install the ratio selection jumper in the correct position see Fig 11 If the calculated ratio is less than or equal to 2 5 1 as is the case with the example where the calcula...

Страница 6: ...60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum master balance R pressure noted above is greater than or equal to 5 PSIG and the maximum master balance R pressure is less than 19 PSIG with a 20 PSIG supply ...

Страница 7: ...which would produce the required 200 F 4 Apply the maximum master M input pressure value Example 60 F or 9 PSIG per Fig 6 5 Apply the corresponding controlled variable CV input pressure value Example 80 F or 5 4 PSIG per Fig 6 6 Set Point dial Adjustment Adjust the set point dial to cause the output pressure to be at the opposite end of the spring range of the controlled device Example Direct Acti...

Страница 8: ...8 T 5800 3 T 5800 4 Technical Bulletin ...

Страница 9: ...e working range internally to a more linear portion of the ratio circuit 3 Vary the master input from minimum to maximum over its working range Example 0 to 60 F or 5 4 to 9 PSIG per Fig 6 Note The master M INPUT is limited to not less than 2 PSIG nor greater than 17 PSIG Note the pressure readings at the master balance R reference corresponding to these minimum and maximum points If the minimum m...

Страница 10: ...no further adjustments will be required If the control point does not stabilize at the set point value or if excessive cycling occurs proceed to the Integral Time Adjustment section Integral Time Adjustment See Figs 17 18 Adjusting the integral time dial will not affect the controller set point If the system response toward the set point is too slow decrease the integral time and or increase the g...

Страница 11: ...the P PI jumper must be disconnected and left vented for a period of time equal to the integral time dial setting Start up the system and reconnect the P PI jumper when the system becomes stable T 5800 100 Time Delay When Fan F Connection is Used After system startup if the system response is too slow the integral control function will act on the signal before the proportional control function set...

Страница 12: ...12 T 5800 3 T 5800 4 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Printed in U S A Milwaukee WI 53202 ...

Отзывы: