Johnson Controls T-4002 Скачать руководство пользователя страница 5

T-4000 Technical Bulletin     5

T-4600 Set Point
Adjustment

The T-4600 is furnished with
HEATING and COOLING labels.
Apply each label to the
appropriate element to avoid
error in calibration or hook up.

Heating Set Point Adjustment
(See Fig. 6)

1.

Insert the test gage.

2.

Furnish restricted supply air
to the instrument.

3.

Note the ambient
temperature in the space.

4.

Turn the heating set point
dial to that temperature
(match it with the arrow).

T-4756 Set Point
Adjustment

Usually the heating set point is
made on the lower element with
a 15 psig (105 kPa) supply
pressure and the cooling set
point is made on the upper
element with a 20 psig (140 kPa)
supply pressure.  If your
application is different, use the
proper element and supply
pressure for the particular
application.  The T-4756 is
furnished with HEATING and
COOLING labels which can be
applied to the appropriate
element.

Heating Set Point Adjustment
(See Fig. 7)

1.

Insert the test gage.

2.

Furnish 15 psig supply
pressure for heating control
(lower dial).

3.

Note the ambient
temperature in the space.

4.

Turn the lower set point dial
to that temperature.

5.

Turn the lower calibration
screw on the heating
element until the output
pressure is at the mid spring
range of the controlled
device.

6.

Turn the lower set point dial
to the desired heating set
point.

5.

Turn the calibration screw on
that element until the output

pressure to the heating
apparatus is at the mid
spring range of the
controlled device.

6.

Turn the heating set point
dial to the desired set point.

Cooling Set Point Adjustment

Repeat the procedure for heating
adjustment on the other element.
Remember to use the other test
port and the proper value in step
5 for the mid spring range of the
controlled device.

Cooling Set Point Adjustment

1.

Insert the test gage.

2.

Furnish 20 psig supply
pressure for cooling control
(upper dial).

3.

Note the ambient
temperature in the space.

4.

Turn the upper set point dial
to that temperature.

5.

Turn the upper calibration
screw on the cooling
element until the pressure is
at the mid spring range of
the controlled spring range
of the controlled device.

6.

Turn the upper set point dial
to the desired temperature.

7.

Restore the supply pressure
for the desired cycle.

Fig. 7:  T-4756 Adjustments

Archived Document

Содержание T-4002

Страница 1: ...in test port fitting which accepts a hypodermic needle test probe and gage X 200 140 and G 2010 11 On older models the test port cap screw must be removed to accept a screw in test gage X 200 19 For these units a test port fitting T 4000 615 can be ordered All low volume output thermostats have hypodermic needle test points For units that require a screw in gage remember to replace the test port c...

Страница 2: ...sure returns to 3 psig 6 The change in dial setting divided by the 10 psig 70 kPa change in master pressure 14 psig 4 psig 10 psig is the actual range of readjustment If this is not the desired range move the range of readjustment slider sensitivity slider in Fig 1a toward the control port to decrease or away from the control port to increase the range of readjustment Readjust the slider screw to ...

Страница 3: ...roceed as follows 1 Remove the T 4054 from the mounting bracket and pull it away from the wall so the deadband adjusting screw on the back of the instrument is exposed see Fig 3 2 Turn the screw clockwise to increase or counter clockwise to decrease the deadband pressure until the gage reads the desired pressure Approximately one half turn will produce a 1 PSI 7 kPa change in deadband pressure 3 R...

Страница 4: ...use the proper element and supply pressure for the particular application The T 4506 is furnished with DAY and NIGHT labels which can be applied to the appropriate element Day Set Point Adjustment See Fig 5 1 Insert the test gage 2 Furnish 15 psig supply pressure for day control lower dial 3 Note the ambient temperature in the space 4 Turn the lower set point dial to that temperature 5 Turn the lo...

Страница 5: ...ture in the space 4 Turn the lower set point dial to that temperature 5 Turn the lower calibration screw on the heating element until the output pressure is at the mid spring range of the controlled device 6 Turn the lower set point dial to the desired heating set point 5 Turn the calibration screw on that element until the output pressure to the heating apparatus is at the mid spring range of the...

Страница 6: ...e supply pressure to 15 psig and rotate the lower dial to produce approximately 5 psig 35 kPa on the output gage 4 Increase the supply pressure to 20 psig and rotate the upper dial to produce approximately 15 psig on the output gage 5 Set the supply pressure to the desired switchover point 6 Slowly turn the switchover adjusting screw see Fig 8 clockwise to increase or counterclockwise to decrease ...

Страница 7: ...T 4000 Technical Bulletin 7 Notes Archived D ocum ent ...

Страница 8: ...8 T 4000 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53202 Printed in U S A Archived D ocum ent ...

Отзывы: