T-4000 Technical Bulletin     3

T-4054 Deadband and Set
Point Adjustment
(See Fig. 2)

The T-4054 can easily be
adjusted to suit the application by
changing the settings on the
heating and cooling dials.  If the
thermostat has been tampered
with or is out of adjustment,
proceed with the following
instructions to recalibrate the
instrument.

Note:  On deadband applications
which have overlapping spring
ranges, it is suggested that a
C-9200 or other sequencing
device be used to bias the
cooling valve spring range to
compensate for spring range
shift.

Deadband Setting

If it is necessary to check or reset
the deadband setting, proceed as
follows:

Turn the lower set point dial to 85F
on direct acting models or 55F on
reverse acting models.  Turn the
upper set point dial to 55F on direct
acting models or 85F on reverse
acting models.  Insert a hypodermic
needle test probe into the test
connection.  The reading on the test
gage is the actual deadband
pressure.

If it is necessary to adjust this
pressure to meet application
requirements, proceed as follows:

1.

Remove the T-4054 from the
mounting bracket and pull it
away from the wall so the
deadband adjusting screw
on the back of the instrument
is exposed (see Fig. 3).

2.

Turn the screw clockwise to
increase or counter-
clockwise to decrease the
deadband pressure until the
gage reads the desired
pressure.  Approximately
one half turn will produce a
1 PSI (7 kPa) change in
deadband pressure.

3.

Return the set point dials to
the original settings.

Set Point Calibration
(See Fig. 2)

1.

Set the lower set point dial to
85F for direct or 55F for
reverse acting models.

2.

Note the ambient
temperature at the element.

3.

Set the upper dial to this
temperature (direct acting
model:  heating, reverse
acting model:  cooling).

4.

Turn the upper calibration
screw until the control
pressure is in the middle of
the spring range of the
controlled device (heating).

5.

Set the lower dial to the
temperature noted in step 2
(direct acting model:
cooling, reverse model:
heating).

6.

Turn the lower calibration
screw until the control
pressure is in the middle of
the spring range of the
controlled device (cooling).

7.

Turn the upper dial to the
desired set point.

Fig. 2:  T-4054 Adjustments

T-4054 Operational Graph

Fig. 3:  Back View of T-4054

Archived Document

Содержание T-4002

Страница 1: ...in test port fitting which accepts a hypodermic needle test probe and gage X 200 140 and G 2010 11 On older models the test port cap screw must be removed to accept a screw in test gage X 200 19 For these units a test port fitting T 4000 615 can be ordered All low volume output thermostats have hypodermic needle test points For units that require a screw in gage remember to replace the test port c...

Страница 2: ...sure returns to 3 psig 6 The change in dial setting divided by the 10 psig 70 kPa change in master pressure 14 psig 4 psig 10 psig is the actual range of readjustment If this is not the desired range move the range of readjustment slider sensitivity slider in Fig 1a toward the control port to decrease or away from the control port to increase the range of readjustment Readjust the slider screw to ...

Страница 3: ...roceed as follows 1 Remove the T 4054 from the mounting bracket and pull it away from the wall so the deadband adjusting screw on the back of the instrument is exposed see Fig 3 2 Turn the screw clockwise to increase or counter clockwise to decrease the deadband pressure until the gage reads the desired pressure Approximately one half turn will produce a 1 PSI 7 kPa change in deadband pressure 3 R...

Страница 4: ...use the proper element and supply pressure for the particular application The T 4506 is furnished with DAY and NIGHT labels which can be applied to the appropriate element Day Set Point Adjustment See Fig 5 1 Insert the test gage 2 Furnish 15 psig supply pressure for day control lower dial 3 Note the ambient temperature in the space 4 Turn the lower set point dial to that temperature 5 Turn the lo...

Страница 5: ...ture in the space 4 Turn the lower set point dial to that temperature 5 Turn the lower calibration screw on the heating element until the output pressure is at the mid spring range of the controlled device 6 Turn the lower set point dial to the desired heating set point 5 Turn the calibration screw on that element until the output pressure to the heating apparatus is at the mid spring range of the...

Страница 6: ...e supply pressure to 15 psig and rotate the lower dial to produce approximately 5 psig 35 kPa on the output gage 4 Increase the supply pressure to 20 psig and rotate the upper dial to produce approximately 15 psig on the output gage 5 Set the supply pressure to the desired switchover point 6 Slowly turn the switchover adjusting screw see Fig 8 clockwise to increase or counterclockwise to decrease ...

Страница 7: ...T 4000 Technical Bulletin 7 Notes Archived D ocum ent ...

Страница 8: ...8 T 4000 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53202 Printed in U S A Archived D ocum ent ...

Отзывы: