6    T-4000 Technical Bulletin

Switchover Point
Adjustment for T-4506,
T-4516, and T-4756

The above thermostats are
factory set to switch from one
element to the other at 17 psig
for a typical 15-20 psig supply
system.  If a different supply
system is to be used, proceed
with the following instructions to
reset the switchover point to a
value between the two supply
pressures.  The switch point is
adjustable from 15 to 20 psig
(105 to 140 kPa).

1.

Remove the controller from
the mounting bracket.

2.

Connect a variable pressure
source to the supply
connection and attach a
gage to the output
connection.

3.

Set the supply pressure to
15 psig and rotate the
lower dial to produce
approximately 5 psig
(35 kPa) on the output gage.

4.

Increase the supply pressure
to 20 psig and rotate the
upper dial to produce
approximately 15 psig on the
output gage.

5.

Set the supply pressure to
the desired switchover point.

6.

Slowly turn the switchover
adjusting screw (see Fig. 8)
clockwise to increase or
counterclockwise to
decrease the switch point
until the output changes.
Note:  Do not turn the
switchover adjusting
screw more that 3-1/2
complete revolutions in
either direction.

7.

Recheck the switchover
point by increasing and
decreasing the supply
pressure over the switch
point to see that switchover
occurs at the desired value.

8.

Remove the gage and tubing
and replace the instrument
on the mounting bracket.

Archived Document

Содержание T-4002

Страница 1: ...in test port fitting which accepts a hypodermic needle test probe and gage X 200 140 and G 2010 11 On older models the test port cap screw must be removed to accept a screw in test gage X 200 19 For these units a test port fitting T 4000 615 can be ordered All low volume output thermostats have hypodermic needle test points For units that require a screw in gage remember to replace the test port c...

Страница 2: ...sure returns to 3 psig 6 The change in dial setting divided by the 10 psig 70 kPa change in master pressure 14 psig 4 psig 10 psig is the actual range of readjustment If this is not the desired range move the range of readjustment slider sensitivity slider in Fig 1a toward the control port to decrease or away from the control port to increase the range of readjustment Readjust the slider screw to ...

Страница 3: ...roceed as follows 1 Remove the T 4054 from the mounting bracket and pull it away from the wall so the deadband adjusting screw on the back of the instrument is exposed see Fig 3 2 Turn the screw clockwise to increase or counter clockwise to decrease the deadband pressure until the gage reads the desired pressure Approximately one half turn will produce a 1 PSI 7 kPa change in deadband pressure 3 R...

Страница 4: ...use the proper element and supply pressure for the particular application The T 4506 is furnished with DAY and NIGHT labels which can be applied to the appropriate element Day Set Point Adjustment See Fig 5 1 Insert the test gage 2 Furnish 15 psig supply pressure for day control lower dial 3 Note the ambient temperature in the space 4 Turn the lower set point dial to that temperature 5 Turn the lo...

Страница 5: ...ture in the space 4 Turn the lower set point dial to that temperature 5 Turn the lower calibration screw on the heating element until the output pressure is at the mid spring range of the controlled device 6 Turn the lower set point dial to the desired heating set point 5 Turn the calibration screw on that element until the output pressure to the heating apparatus is at the mid spring range of the...

Страница 6: ...e supply pressure to 15 psig and rotate the lower dial to produce approximately 5 psig 35 kPa on the output gage 4 Increase the supply pressure to 20 psig and rotate the upper dial to produce approximately 15 psig on the output gage 5 Set the supply pressure to the desired switchover point 6 Slowly turn the switchover adjusting screw see Fig 8 clockwise to increase or counterclockwise to decrease ...

Страница 7: ...T 4000 Technical Bulletin 7 Notes Archived D ocum ent ...

Страница 8: ...8 T 4000 Technical Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53202 Printed in U S A Archived D ocum ent ...

Отзывы: