Basic Controls—System 350 P352AB Electronic Pressure Control Series Product/Technical Bulletin

C

heckout Procedure

Before applying power, make sure installation and
wiring connections are according to job specifications.
After necessary adjustments and electrical
connections have been made, put the system in
operation and observe at least three complete
operating cycles before leaving the installation.

T

roubleshooting

If the System 350 control modules do not appear to
function properly, verify that the proper mode (DA or
RA) has been selected on each control module. Then
perform the following procedures to determine the
problem.

IMPORTANT:

The control and the controlled
equipment must be powered and
operating at a stable pressure to
perform many of the following
procedures.

Equipment Needed:

  A reliable pressure gauge connected near the

transducer.

  A reliable and accurate Digital Voltmeter (DVM)

capable of measuring AC voltage and DC voltages
down to ± 0.1 VDC in the 0 to 10 VDC range.

!

 WARNING:

Risk of Electrical Shock.

To perform the following
procedures it is necessary to
power the control and the
controlled equipment while the
control cover is removed. Do not
touch any exposed metal
components with anything other
than properly insulated tools or
insulated probes of the digital
voltage meter. Failure to use
properly insulated tools and
probes can result in severe
electrical shock if live line voltage
parts are contacted.

1. Check for proper supply voltage to the Control.

a. Before powering control and equipment, check

that all of the wiring is correct and all of the
connections are tight.

b. Apply power to the control.

c. With the DVM, check the voltage between the

24V and the COM terminals on the terminal
block on the upper left side of the control.

If an external 24 VAC transformer powers
the control

, select AC volts on the DVM. The

voltage must be between 20 and 30 VAC.

If a Y350R Power Module powers the
control

, select DC volts on the DVM. The

voltage must be between 16 and 38 VDC.

d. If the DVM reading is within the indicated

voltage range, proceed to Step 2.

e. If the DVM reading is 

not

 within the indicated

voltage ranges, replace the external
transformer or the Y350R Power Module, and
recheck for proper supply voltage.

2. Check for proper supply voltage to the

pressure transducer.

a. Select DC volts on the DVM and measure the

voltage (

VDC

S

) between VDC and the COM

terminals on the terminal block on the upper
left side of the control.

The voltage must be 5.0 VDC (± 0.1 VDC).
If the voltage is in this range proceed to
Step 3.

b.  If the voltage is out of this range, power down

the controlled equipment and disconnect it
from the control. Disconnect the transducer
from the control. With the control powered,
measure the voltage (

VDC

S

) between VDC

and the COM terminals on the terminal block
on the upper left side of the control.

The voltage must be 5.0 VDC (± 0.1 VDC).
If the voltage is in this range, replace the
transducer. If the voltage is out of range,
replace the control.

3. Check pressure transducer for proper output

signal voltage.

a. Measure and record the voltage (

Vo

) between

the SEN and the COM terminals on the control
terminal block.

b. At the same time, observe and record the

pressure reading (

psi

T

) on the gauge.

Содержание System 350 P352AB Series

Страница 1: ... all System 350 products the P352AB control is housed in a NEMA 1 high impact thermoplastic enclosure The modular design provides easy snap together connections for quick installation and future expandability Figure 1 P352AB Electronic Pressure Control Features and Benefits Modular Design Provides the flexibility to add S352A Stage Modules D352 Display Module and Y350R Power Module Plug together C...

Страница 2: ...ontrol operates on 24 VAC and has an SPDT relay output A front panel LED lights to indicate when the relay is energized The P352AB controls are used with the P399 Electronic Pressure Transducers which are available in several pressure ranges and provide a ratiometric analog signal 0 5 to 4 5 VDC based on the sensed pressure IMPORTANT The P352AB controls use an input signal from the P399 Electronic...

Страница 3: ...ED illuminates Note The P352AB controls are configured for DA mode at the factory Refer to Figure 5 for an example of a typical Direct Acting Reverse Acting application Dimensions 1 3 16 2 3 8 61 7 16 11 1 1 2 40 1 8 4 DIN Rail Mount 7 8 22 Conduit Hole Mounting Slots For No 6 Screws 5 127 2 15 16 75 2 3 8 61 7 8 22 2 1 4 57 2 0 m 13 ft 4 0 m or Wiring Harness 6 1 2 ft P399 Transducer CONTROLS CON...

Страница 4: ...fter power is applied to the control a more accurate setting of the setpoint can be made by utilizing the D352A Pressure Display Module 6 Replace the cover on the control and fasten in place with screws 7 Restore power to system Module Connector Concealed Setpoint Adjustment Dial Differential Potentiometer N C Relay N O Terminals COM Output Relay Energized LED Indicator Jumper Position at J1 Rever...

Страница 5: ...te signal The DA RA relay will remain energized until the error is corrected Adjustments S352A Stage Module Perform the following steps to adjust the S352A stage module settings See Figure 4 Refer to Figure 5 for an illustration of the S352A Stage Modules in a typical Direct Acting Reverse Acting application WARNING Risk of Electrical Shock Disconnect power supply to avoid possible electrical shoc...

Страница 6: ...han one disconnect may be required to completely de energize equipment IMPORTANT Make all wiring connections in accordance with the National Electrical Code and all local regulations Use copper conductors only Do not exceed the control s electrical ratings Transducer Wiring The P352AB control supplies 5 VDC power to the P399 Electronic Pressure Transducer The transducer is wired to three of the fo...

Страница 7: ...te and tape Do not ground this end of cable shield 120 VAC Figure 6 System 350 Powered by an External Transformer Using 120 VAC Power Supply 120 VAC P352AB Y350R S352A S352A D352A S352A Load Load Load Load Isolate and tape Do not ground this end of cable shield P399 Transducer Wiring Harness White SEN Red VDC Black COM Wire Terminal Block 24V COM VDC SEN N O Terminals COM Output N C Relay Shield C...

Страница 8: ...and equipment check that all of the wiring is correct and all of the connections are tight b Apply power to the control c With the DVM check the voltage between the 24V and the COM terminals on the terminal block on the upper left side of the control If an external 24 VAC transformer powers the control select AC volts on the DVM The voltage must be between 20 and 30 VAC If a Y350R Power Module pow...

Страница 9: ...e Note Depending on the accuracy of the instrumentation used to measure the actual pressure at the transducer psiT and the transducer output voltage Vo the actual and calculated pressure may not exactly agree 10 90 50 Output Voltage of Power Supply 4 5 VDC 2 5 VDC 0 5 VDC 500 psi P352AB 3 P399B Pressure psi P352AB Model P399 Transducer 100 psi P352AB 2 P399A P 3 5 2 A B 2 P352AB 3 P352AB 4 Figure ...

Страница 10: ...what the On and Off setpoint pressure values are for each module f If a stage module LED and relay do not perform as expected adjust the differential and offset potentiometers to their minimum value and repeat the previous checks g If a stage module still does not perform properly replace the stage module 6 Check the display module for proper operation If there is no display module in the system s...

Страница 11: ...sure connection 0 to 500 psis 1 4 in SAE female flare pressure connection Electronic Pressure Transducers for the P352AB 4 P399CAA 1C P399CAC 1C 0 to 750 psis 1 8 in NPT male pressure connection 0 to 750 psis 1 4 in SAE female flare pressure connection Wiring Harness WHA P399 400C WHA P399 200C 13 1 ft 4 0 m length 6 6 ft 2 0 m length Display Module D352AA 2C Digital Pressure Display Module Stage ...

Страница 12: ...ty 125 VA at 24 240 VAC Ambient Temperature Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Ambient Humidity 0 to 95 RH Non condensing Material Case Cover NEMA 1 High Impact Thermoplastic Agency Listing UL Listed CCN XAPX File E27734 UL Listed for Canada CCN XAPX7 File E27734 Only one voltage source may be used Add on Modules S352A Y350R D352 Relay Contacts SPDT 10 Amperes Non ind...

Отзывы: